43
2018/10
Subindex 66: Set Default Parameterization
Structure of the reset command:
Subindex 67: Teach Mode
Structure of the Teach command:
Entity_
Port
IO-Link
subindex
Read
Write
Length
Description
0
66
w
4 byte
Writing this object sets the IO-Link master
back to factory settings. Any parameter set-
ting and configuration is overwritten. The
data storage buffer is deleted as well.
Byte 3
Byte 2
Byte 1
Byte 0
0xEF
0xBE
0xAD
0xDE
Entity_
Port
IO-Link
subindex
Read
Write
Length
Description
0
67
w
1 byte
The master reads all data (device-ID, ven-
dor-ID, serial number, etc.) from the con-
nected device and saves them. All all previ-
ously saved device data are overwritten.
Byte 0
0x00
Teaching all 4 ports
0x01
Teaching port 1
0x02
Teaching port 2
0x03
Teaching port 3
0x04
Teaching port 4
0x05 - 0xFF
reserved
Содержание BL20-E-4IOL
Страница 1: ...Your Global Automation Partner BL 4IOL IO Link Master Modules for BL20 and BL67 Operating instructions...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 6: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 4...
Страница 10: ...Notes on the Product Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 8...
Страница 12: ...For Your Safety Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 10...
Страница 73: ...71 2018 10 Activate the read access via a rising edge at REQ Fig 25 Activating the read access...
Страница 91: ...30 subsidiaries and over 60 representations worldwide www turck com D301333 2018 10 D301333...