Turbo Master EcoNet Plus EC++LS Скачать руководство пользователя страница 23

U s e   A n d   M a i n t e n a n c e   I n s t r u c t i o n s

 

M a s t e r   E c o N e t   P l u s   E C + + L S     R S 4 8 5

 

 

I n M n   1 8     E P E  
e n     R e v . 0 0  

T U R B O   S r l

    D u s t   F i l t e r   C o m p o n e n t s  

V i a   P o   3 3 / 3 5   2 0 8 1 1   C e s a n o   M a d e r n o   ( M B )   I t a l y     T e l   + + 3 9   0 3 6 2   5 7 4 0 2 4     F a x   + + 3 9   0 3 6 2   5 7 4 0 9 2  

2 3  

 

Trouble Shooting 

FAQ

 

F a u l t  

P o s s i b l e   C a u s e  

S o l u t i o n  

The display does not 

light up. 

Burnt fuse. 

Power voltage. 

Check the protection fuse on the power voltage. 

Check that the power voltage is present and 

compliant with that required for the device 

(terminals 1 and 3). 

The outputs do not 

light up. 

Output voltage. 

Wiring to solenoid 

valves. 

Check that the timer and solenoid vale output 

voltage agree. 

Check wiring between timer and solenoid valves. 

The differential 

pressure reading is 

not correct. 

Obstructed pneumatic 

connections. 

Damaged pipes. 

Check that the differential pressure is 0.00 

kPa with the pipes disconnected. In this case, 

check that the connection pipes between device 

and filter are not obstructed or damaged. 

The cleaning cycle is 

not carried out. 

The economizer is in 
economy mode and 

therefore does not 

start up. 

Adjust the start-up pressure threshold or set the 

economizer to MANUAL mode. 

Does the economizer 

occasionally reset? 

 

Check that there are no unfiltered pulse loads on 

the power line (spot welding machines, welding 

machines, plasma cutters etc.). Install a filter on 

the economizer power line, if needed. 

Does post-cleaning 

start during normal 

cleaning? 

 

Change the post-cleaning start-up threshold by 

lowering it. 

Does post-cleaning 

fail to start when the 

normal cleaning cycle 

ends? 

 

Activate post-cleaning from the advanced 

configuration menu. 

Check that the measured pressure is lower than 

the post-cleaning activation pressure when the 

fan is off. 

Do the alarms fail to 

activate signaling 

devices? 

 

The alarm devices must be powered by voltage 
external to the economizer. A relay opening is 
needed to activate them. 

Does 0.0 kPa-mm 

Bar-mm H20-Inch 
w.c. fail to appear 

when the fan is off? 

 

Set the reading to 0 under the zero dP option in 

the Calibration/Test menu. 

Do alarm messages 

appear? 

 

Check the Alarms menu. 

 

 

 

 

 

 

 

 

Содержание Master EcoNet Plus EC++LS

Страница 1: ...LS RS485 I n Mn 18 E PE en Rev 00 TURBO Srl Du s t F i l t e r C om p on en t s Vi a P o 3 3 3 5 2 0 8 1 1 Ce san o M a de rn o M B I t al y Te l 3 9 0 3 6 2 5 7 4 0 2 4 Fa x 3 9 0 3 6 2 5 7 4 0 9 2...

Страница 2: ...Menu _____________________________________________________________ 17 Counter Menu _______________________________________________________________________ 18 Operation Description____________________...

Страница 3: ...lve fault or minimum and maximum clogging Interface menu available in five languages Operating modes manual automatic proportional special manual Selectable pressure unit of measure kPa millibar mm H2...

Страница 4: ...uts proportionate to dP value for remote pressure reading from 4 to 20 mA x 2 Power Consumption 28 Watt maximum load Alarm Relays 2 normally closed 485 type serial transmission interfaces with Modbus...

Страница 5: ...t e r C om p on en t s Vi a P o 3 3 3 5 2 0 8 1 1 Ce san o M a de rn o M B I t al y Te l 3 9 0 3 6 2 5 7 4 0 2 4 Fa x 3 9 0 3 6 2 5 7 4 0 9 2 5 Container Features ABS base and polycarbonate lid IP65 d...

Страница 6: ...The electrical supply of the unit must be protected by a differential switch 230 Vac 30 mA and a bipolar magneto thermic 230 Vac 10 A positioned in a place easily accessible Before working on the equ...

Страница 7: ...s cable diameter minimum of 4 mm and a maximum of 8 mm with clamping nut by 19 mm Any use not described in this user instruction manual or incorrect use of the device may cause damage to the device or...

Страница 8: ...r C om p on en t s Vi a P o 3 3 3 5 2 0 8 1 1 Ce san o M a de rn o M B I t al y Te l 3 9 0 3 6 2 5 7 4 0 2 4 Fa x 3 9 0 3 6 2 5 7 4 0 9 2 I n Mn 18 E PE Rev 0 0 en Electrical Connections To connect t...

Страница 9: ...r u c t i o n s Master EcoNet Plus EC LS RS485 I n Mn 18 E PE en Rev 00 TURBO Srl Du s t F i l t e r C om p on en t s Vi a P o 3 3 3 5 2 0 8 1 1 Ce san o M a de rn o M B I t al y Te l 3 9 0 3 6 2 5 7...

Страница 10: ...ut indicated with IN connect the other electro valves sequentially using the wiring harness with the PG7 connectors respecting the IN OUT polarity assemble the gaskets to ensure the IP seal of the cir...

Страница 11: ...eumatic valves in the input indicated with IN 1 Pneumatic valve with remote control actuation 2 Connection hose between the remote pilot and the valve 3 Enclosure box with integrated pilots for valve...

Страница 12: ...s always displayed during normal operations Menu Provides access to settings it is used as RESET in the event of alarms Keys Increase and decrease the display contrast on the main screen In the other...

Страница 13: ...se the arrows to select Main Set Up Press OK Basic Set Up Items Use the arrows to select the item to be set Use keys to increase or decrease the value and change the item conditions for example switch...

Страница 14: ...Stop Cleaning Enter the end cleaning dP value for Autom operating mode only Advanced Settings Press the Menu key in the home page Use the arrows to select Advanced Set Up Press OK Advanced Set Up Ite...

Страница 15: ...Time sec Interval between valve openings in cycles with fan off 1 sec 7200 sec Precoating Enables the Precoating function Enter the dP value where the pre coating function is kept enabled When exceede...

Страница 16: ...Alarms Press OK Alarm Menu Items Use the arrows to select the item to be set Keys to increase decrease the value or change an item condition such as Enable Disable Press exit to save and exit dP Dirt...

Страница 17: ...nals 17_18 on connector P13 on the electronic board Replace Filters h Calibration Test Menu Press the Menu key in the home page Use the arrows to select Calibration Test Press OK Calibration Test Menu...

Страница 18: ...the 20mA output which corresponds to dP full scale Counter Menu Press the Menu key in the home page Use the arrows to select the Counter item to be set Press OK Counter Menu Read Only Items Hours Pow...

Страница 19: ...ion time pause time and the number of solenoid valves connected to the device are set In Manual Operating Mode the signal 24 Vdc at terminals 22_23 connector P11 is always active Automatic Operating M...

Страница 20: ...and pause time between these cycles for the connected solenoid valves With this mode unlike manual mode the device only runs the solenoid valves for the set number of cycles and will remain in stand...

Страница 21: ...must be voltage free normally open and connected to terminals 38_39 connector P13 see wiring diagram 4 20 mA Out Function This function lets you check pressure readings from remote through 4 20mA tra...

Страница 22: ...menu section When an alarm is triggered it is signalled on the display by a blinking row that is normally occupied by the operating mode The menu key is used for RESET and keys can be used to scroll a...

Страница 23: ...es between device and filter are not obstructed or damaged The cleaning cycle is not carried out The economizer is in economy mode and therefore does not start up Adjust the start up pressure threshol...

Страница 24: ...d do not rub with abrasive sponges Scrapping Dispose of properly after use Dispose of the product according to laws in force for electronic equipment This device is for use in a dust collection system...

Страница 25: ...Cleaning dP 0 40 kPa 00400 A d v a n c e d S e t t i n g P a r a m e t e r S e t t i n g V a l u e dP Fan Recognition 0 10 kPa 00100 Cleaning Cycles Fan Off 2 00002 Time Impulse Valve 200 m seconds 0...

Страница 26: ...V i a P o 3 3 3 5 2 0 8 1 1 C e s a n o M a d e r n o I t a l y Declares that the product S e r i a l M a s t e r E c o n o m i z e r Model E c o N e t P l u s E C P L S 1 2 8 Complies with the follo...

Отзывы: