Maintenance

 

 

The  only  parts  which  may  be  replaced  are  fuses.  All  other  operations  must  be  carried  out  by  the 
manufacturer. 

 

Scrapping 

Dispose  of  properly  after  use.  Dispose  of  the  product  according  to  laws  in  force  for  electronic 
equipment. 

 

This device is for use in a dust collection system and is therefore part of a fixed installation.  

 

Default Settings 

 

The default settings are: 
 
 

Function 

number

 

Description

 

Set value

 

F02

 

Solenoid valve activation time.

 

0.20 sec

 

F03

 

Pause time between solenoid valves in normal cycle.

 

020 sec

 

F04

 

Number of outputs.

 

F05

 

Output voltage: 24Vdc, 24Vac, 115ac, 230ac.

 

115 Vac

 

F06

 

Manual solenoid valve activation.

 

F13

 

Number of cycles after fan stop.

 

F14

 

Pause time between solenoid valves in cycle with fan off.

 

010 sec

 

F15

 

Maintenance frequency in 10h (1=10h, 100=1000h).

 

100 

F16

 

Maintenance deadline alarm on (1) or off (0).

 

F17

 

Maintenance hour counter reset: set 1 and confirm to reset the 
maintenance hour counter.

 

F24 

Exclusion of valve in short circuit.

 

 

Warranty 

 

The warranty lasts for two years. The manufacturer will replace any faulty electronic component at 
their own facilities only, unless otherwise authorised by the manufacturer. 

Warranty Exclusions 

 

The warranty will be cancelled in case of: 

 

Signs of unauthorised tampering and repairs. 

 

Incorrect use of the device not respecting technical data.  

 

Incorrect electric connections.  

 

Failure to respect system standards.  

 

Use not in accordance with EC standards.  

 

Atmospheric events (lightening, electrostatic discharges, power surges). 
 

Содержание E1T Series

Страница 1: ... USER MANUAL Usa Vr 01 03 2016 Manual Release 1 24 Hardware Release 1 3 TURBO s r l Electronic Control Systems For Dust Collectors e mail info turbocontrols it web www turbocontrols eu Tel 39 0 362 574024 Fax 39 0 362 574092 ...

Страница 2: ...e lid Degree of protection to water and dust IP65 EN60529 Shock resistance IK07 2 Joule EN62262 Performance of the Device LED display with 7 segments 3 digits 0 8 each Operating times expressed in seconds with selectable ranges for any application Power supplier 115 230 Vac 50 60 Hz selectable via jumper must also set with F05 optional 24 Vac Vdc Output voltage 24Vdc 24 115 230Vac selectable by me...

Страница 3: ... cleaning enable Fan contact post cleaning The solenoid valves connected to the unit are normally closed The activation of a solenoid valves causes them to open and consequently let out a jet of air Alarm Relays The alarm relays has two voltage free contacts on terminals 4 5 Relay 1 and 6 7 relay 2 Maximum permitted load 3A 250Vac 2A 24Vdc Fuse 1 x 1 A 230Vac 1 x 1 A 115Vac 1 x 3 A 24Vac optional ...

Страница 4: ...with a minimum cross section area of 0 75 mm for all control signals Use flame retardant cables with a minimum cross section area of 0 75 mm to connect to the power supply Use flame retardant cables with a minimum cross section area of 0 75 mm to connect to the indicating relays Any use not described in this user instruction manual or incorrect use of the device may cause damage to the device or t...

Страница 5: ...e the manual solenoid test by selecting function F06 Press and to select a function from F01 to Fxx increase decrease values view the total hour counter and the maintenance counter Press OK to confirm data and reset the alarms Menu Diagram Press SET see figure 2 Figure 2 Press and to select the required function Press OK to confirm Increase or decrease the value of the parameter Press OK to confir...

Страница 6: ...cleaning cycles after stopping the fan Possible values 01 99 step 1 Default 00 F14 Post cleaning mode pause time fan off Possible values 001 seconds 999 seconds step 1 seconds Default 010 seconds F15 Maintenance frequency expressed in tens of hours e g 1 10h 10 100h Possible values 001 999 step 1 Default 100 1000h F16 Maintenance deadline alarm enable Possible values 0 disabled 1 enabled Default 0...

Страница 7: ...05 set to 230V Voltage out of range detected To use 230V valves switch the device off and move the output voltage selection jumper to 230V If the jumper is in the correct position press OK then SET select the F05 function with and set a24 d24 or 115 as jumper and press OK E06 Solenoid valve current lower than minimum threshold or disconnected solenoid valve Check correct connection of the solenoid...

Страница 8: ...ated at the programmable frequencies The firing and pausing times can be set on the configuration menu Cleaning Function With Fan Off PCC This function allows to carry out one or more cleaning cycles the number of cycles is defined by F13 when the fan is off The on or off state of the fan is determined by the state of contacts 12 13 contacts open fan off The pulse time of the valves will always be...

Страница 9: ...9 Connection Diagram ...

Страница 10: ...output 7 Relay contact 2 39 Solenoid 9 output 12 Fan input 40 Solenoid 10 output 13 Fan input 41 Solenoid 11 output 14 Enable input 42 Solenoid 12 output 15 Enable input 43 Solenoid 13 output 30 Solenoid valve common 44 Solenoid 14 output 31 Solenoid 1 output 45 Solenoid 15 output 32 Solenoid 2 output 46 Solenoid 16 output Fuse Table Voltage Value 230 V 1 A 115 V 1 A 24 Vdc Vac 3 A Jumper Configur...

Страница 11: ...11 Installation Casing Dimensions 12 16 Outputs ...

Страница 12: ...12 Installation Casing Dimensions 4 8 Outputs ...

Страница 13: ...f cycles after fan stop 1 F14 Pause time between solenoid valves in cycle with fan off 010 sec F15 Maintenance frequency in 10h 1 10h 100 1000h 100 F16 Maintenance deadline alarm on 1 or off 0 0 F17 Maintenance hour counter reset set 1 and confirm to reset the maintenance hour counter 0 F24 Exclusion of valve in short circuit 0 Warranty The warranty lasts for two years The manufacturer will replac...

Страница 14: ...id vale output voltage agree Check wiring between sequencer and solenoid valves Do alarm messages appear Check the alarm code with the table Do the alarms fail to activate signalling devices System wiring errors No power to alarm devices The alarm devices must be powered by voltage external to the sequencer Activating to open the respective relay The sequencer resets occasionally Check the there i...

Страница 15: ...omplies with the following directives Directive 2014 30 EU Electromagnetic Compatibility compliant with Harmonised European standards EN61000 6 2 2005 class B of EN61000 6 4 2001 Directive 2014 35 EU Low Voltage compliant with Harmonised European Standards EN 60947 1 2004 Supplementary Information A typical configuration of the product was tested Cesano Maderno 01 03 2016 F MESSINA C E O TURBO s r...

Отзывы: