MAIN PCB PROGRAMING
Code
Content
Perception Method
Freezer Operation State
F1
F-sensor
Malfunction
-. Sensor shorted.
-. The compressor runs for 30 minutes and
F0
-. Sensor disconnected.
stops for 5 minutes repeatedly.
D1
D-sensor
Malfunction
-. Sensor shorted
-. Defrost heater may operate it.
-. If F-sensor temperature is higher than
28.4℉, the heater goes off.
D0
-. Sensor disconnected
-. Defrost heater turns on for 20 minutes if
F-sensor is in error mode too.
C1
Cycle, Comp.
Malfunction
-. The temperature of D-sensor is
over 32℉
even though the compressor has been
running for 30 minutes.
- . Normal operation
(Compressor is automatically turned on and
off by F-sensor.)
-. Defrost heater will be on every time
F3
Defrost
Malfunction
-. The temperature of D-sensor doesn't
reach 43℉ within 30 minutes.
y
for 30 minutes.
-. If the D-sensor's temp. reaches 43℉
within 30 minutes, defrost heater will be
turned off immediately.
3-4) Change the Model
▶ Press the down (or -) keys five times during 88 LED displaying “SL”,
88 LED display Present Model Number. If the number is not “5” you have to
change the model number. ( Next Five Model is controlled by the same PCB ASSY)
MODEL
Top Mount
Refrigerator
Top Mount
Freezer
Bottom Mount
Refrigerator
Bottom Mount
Freezer
Glass Door
Freezer
ICE
Merchandiser
TRF-****
TFF-****
TSR-****
TSF-****
TGF-****
TGIM-****
N
b
0
1
2
3
4
5
Number
0
1
2
3
4
5
Содержание TGIM-23*
Страница 3: ...1 FEATURE CHART Model TGIM 23 Model TGIM 23 FRONT Model TGIM 23 SIDE...
Страница 4: ...FEATURE CHART Model TGIM 49 FRONT Model TGIM 49 SIDE...
Страница 9: ...3 WIRING DIAGRAM Model TGIM 23...
Страница 10: ...WIRING DIAGRAM Model TGIM 49...
Страница 24: ...REPLACEMENT OF MAIN COMPONENTS C Remove the Electrical Box Cover...
Страница 32: ...REPLACEMENT OF MAIN COMPONENTS G Replace the SMPS...