17

6.4.6.5 The slave forced cooling units will not be controlled by other signals except timer off signal. 

6.4.6.6 If AC is running in sleep mode and receives forced operation signal, it will quit the sleep mode. 

 

6.4.7 Timer function 

6.4.7.1 Timing range is 24 hours. 

6.4.7.2 Timer on.    The machine will turn on automatically when reaching the setting time. 

6.4.7.3 Timer off.    The machine will turn off automatically when reaching the setting time. 

6.4.7.4 Timer on/off.    The machine will turn on automatically when reaching the setting “on” time, and 

then turn off automatically when reaching the setting “off” time. 

6.4.7.5 Timer off/on.    The machine will turn off automatically when reaching the setting “off” time, and 

then turn on automatically when reaching the setting “on” time. 

6.4.7.6 The timer function will not change the AC current operation mode. Suppose AC is off now, it will 

not start up firstly after setting the “timer off” function. And when reaching the setting time, the timer 

LED will be off and the AC running mode has not been changed. 

6.4.7.7 The setting time is relative time. 

6.4.8 Sleep function mode 

6.4.8.1 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode and turns off.   

6.4.8.2. Operation process in sleep mode is as follow: 

When cooling, the setting temperature rises 1 /33.8    ( be lower than 30  / 86    ) every one hour, 

setting temperature stops rising and indoor  fan is fixed as low speed.     

When heating, the setting temperature decreases 1 /33.8    (

than 17  / 62.6    ) every 

later the setting temperature stops rising and indoor  fan is fixed as low speed.

(Anti-cold wind function has the priority) 

6.4.8.3 Timer off and remote controller off signals have the priority compared with sleep function. 

6.4.8.4 When user uses timer off function in sleep mode(or sleep function in timer off mode), if the 

timing is less than 7 hours, sleep function will be cancelled when reaching the setting time. If the timing 

is more than 7 hours, the machine will not stop until reaches the setting time in sleep mode. 

6.4.9 Auto-Restart function 

The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart 

module. In case of a sudden power failure, the module memorizes the setting conditions before the 

power failure. The unit will resume the previous operation setting (not including Swing function) 

two hours later

one hour, 2 hours

be higher

Содержание TAS-09MVHN

Страница 1: ...VMI 1102 A SERVICE MANUAL AIRCONDITIONER DC INVERTER MULTI TYPE MSV1I 09HRDN1 M TAS 12MVHN INDOOR VERTU DC INVERTER MULTI SERIES TAS 09MVHN...

Страница 2: ...ion 1 1 1 Safety Precaution 1 1 2 Warning 1 2 Function 6 3 Dimension 7 4 Wiring Diagram 8 6 Electronic function 10 6 1 Abbreviation 10 6 2 Display function 10 6 3 Main Protection 11 6 4 Operation Mode...

Страница 3: ...the product there is risk of fire or electric shock Always ground the product There is risk of fire or electric shock Install the panel and the cover of control box securely There is risk of fire of e...

Страница 4: ...of fire or electric shock Do not place anything on the power cable There is risk of fire or electric shock Do not plug or unplug the power supply plug during operation There is risk of fire or electri...

Страница 5: ...product damage Ventilate the product from time to time when operating it together with a stove etc There is risk of fire or electric shock Turn the main power off when cleaning or maintaining the pro...

Страница 6: ...or loss of property Do not block the inlet or outlet of air flow It may cause product failure Use a soft cloth to clean Do not use harsh detergents solvents etc There is risk of fire electric shock or...

Страница 7: ...ent types of batteries There is risk of fire or explosion Do not recharge or disassemble the batteries Do not dispose of batteries in a fire They may burn of explode If the liquid from the batteries g...

Страница 8: ...peration mode high med low breeze auto Indoor unit Operation by remote controller Sensing by temperature sensor Room temperature control Anti freezing control in cooling Time Delay Safety control Indo...

Страница 9: ...Dimension of installation hole 795 mm 31 30 inch 270 mm 10 63 inch 165 mm 6 5 inch 165 mm 6 5 inch 165 mm 6 5 inch TAS 12MVHN 845 mm 33 27 inch 286 mm 11 26 inch TAS 09MVHN TAS 12MVHN 160 mm 6 28 inch...

Страница 10: ...8 4 Wiring Diagram Indoor unit TAS 09MVHN TAS 12MVHN...

Страница 11: ...the unit to function abnormally 2 Room relative humidity less than 80 If the air conditioner operates in excess of this figure the surface of the air conditioner may attract condensation Please set t...

Страница 12: ...operation CLEAN AIR display optional Illuminated when Ionizer is activated TURBO operation display Illuminated when select TURBO function in cooling operation or in heating operation DIGITAL DISPLAY...

Страница 13: ...r certain time the unit will stop and the LED will display the failure 6 3 3 Indoor fan delayed open function When the system starts up the louver will be active immediately and the indoor fan will op...

Страница 14: ...e is the same as auto fan in setting temperature 6 4 2 Cooling Mode 6 4 2 1 Compressor running rules The compressor will run at corresponding frequency according to the gross amendatory capacity deman...

Страница 15: ...eed can be selected as high medium low and auto Auto fan in cooling mode acts as follow 6 4 2 3 Evaporator low temperature T2 protection When T2 4 39 2F the indoor has no capacity demand and resume ti...

Страница 16: ...HEAT _F2 HEAT _F11 HEAT _F12 Amendatory capacity demand 0 1 2 11 12 6 4 3 2 Indoor fan running rules Indoor fan speed can be set as high medium low or auto fan and the anti cold wind function is pref...

Страница 17: ...g If any one of following items is satisfied defrosting will stop and the machine will turn to normal heating mode T3 TCDE TCDE 15 The defrosting time achieves 10min 6 4 4 Auto mode This mode can be c...

Страница 18: ...the AC will run as below sequence When the machine is off pressing the touch button will carry the machine to forced auto mode after this if pressing the button once again the machine will turn into...

Страница 19: ...leep function mode 6 4 8 1 Operation time in sleep mode is 7 hours After 7 hours the AC quits this mode and turns off 6 4 8 2 Operation process in sleep mode is as follow When cooling the setting temp...

Страница 20: ...nning due to malfunctions or anti cold wind When indoor fan restarts after malfunctions being eliminated and anti cold wind being released Ionizer will be available again 6 4 11 Mode conflict The indo...

Отзывы: