Table of alarms and signals.
When an alarm is activated, the display shows the corresponding message that flashes
alternating with the temperature; if fi tted and enabled, the buzzer and the alarm relay are also
activated.
All the alarms have automatic reset (that is, they stop when the causes are no longer present),
except for alarm ‘CHt’ which has manual reset (instrument on/off using the UP button or by
disconnecting the power supply).
Pressing the SET button mutes the buzzer, while the code displayed and the alarm relay only
go off when the causes of the alarm have been resolved.
The alarm codes are shown in the table below:
Table 7. Alarm codes table.
alarm
code
buzzer and
alarm relay
LED
alarm description
reset
enable alarm
parameters involved
E0
active
on
probe 1 error = control
automatic
E1
not active
on
probe 1 error = defrost
automatic
d0=0/1/4, F0=1
E2
not active
on
probe 1 error =
condenser/product
automatic
A4=10
IA
active
on
external alarm
automatic
A4=1, +A7
dOr
active
on
open door alarm
automatic
A4=7/8, +A7
LO
active
on
low temperature alarm
automatic
AL, Ad
HI
active
on
high temperature alarm
automatic
AH, Ad
EE
not active
on
unit parameter error
not possible
EF
not active
on
operating parameter error
manual
Ed
not active
on
defrost running
on first defrost
ended correctly
dP, dt, d4, A8
dF
not active
off
defrost running
automatic
d6=0
cht
not active
on
dirty condenser pre-alarm
automatic
A4=10
CHT
active
on
dirty condenser alarm
manual
A4=10
EtC
not active
on
clock alarm
by setting the
time
if bands active