Turbo Air ADM131 Скачать руководство пользователя страница 16

 

16 

System Operation.

Evaporator Superheat.

 

Evaporator superheat is generated from 

the compressor suction line  reducing 

system efficiency. 

Normally 6

  to 12

  is acceptable on 

most refrigeration systems. Preferably,  

6

  to 8

  on low temperature systems 

and 8

  to 10

  on medium temperature 

systems  are desired.  For systems 

operating at higher temperatures, the 

superheat can be adjusted to 12

 to 15

 

as required. 

The method of measuring evaporator 

superheat is found by P-T method. 

Obtain evaporator superheat by 

measuring the suction line temperature at 

the expansion valve bulb. Obtain pressure 

at a Schrader  fitting in the evaporator 

suction connection area, near the 

expansion valve bulb, and convert to 

temperature with a P-T chart. 

Subtract the converted temperature from 

the  measured temperature and the 

difference is superheat at the 

evaporator. 

Obtain the desired 

superheat by adjusting the expansion 

valve. 

Evaporator superheat greater than 14

 

can substantially reduce system capacity, 

while superheat less than 4

  has the 

potential for flood back. 

 

Compressor Superheat.

 

Compressor superheat has an effect on 

system capacity and efficiency. 

Compressor superheat 

affects 

compressor life and recommends a 

minimum of 20

  superheat at the 

compressor.  Too low a compressor 

superheat can permit liquid return to the 

compressor causing damage.   

Too high a compressor superheat can 

cause high discharge temperature, 

resulting in lubricant breakdown, 

compressor overheating and can lead to 

compressor damage or failure. 

Compressor superheat can be changed by 

adjusting the expansion valve, adding a 

suction-liquid line heat exchanger. 

Obtain compressor superheat by 

measuring the suction line temperature 

about 6 to 12 inches from the compressor 

service valve.   

Obtain pressure at the suction service 

valve and convert to temperature with a 

P-T chart. Subtract the converted 

temperature from the measured 

temperature and the difference is 

superheat at the compressor.

 

 

 

Содержание ADM131

Страница 1: ...s Up the Pace of Innovation Part No KUCTB2503 Refrigeration System Installation Operation Manual Please read this manual completely before attempting to install or operate this equipment Unit Cooler C...

Страница 2: ...Inspection 3 Locating Unit Cooler 4 Unit Cooler Piping 6 Expansion Valve Selection 7 Defrost 10 Locating and Mounting Condensing Unit 12 System Operation 13 Unit Cooler Troubleshooting 15 System Trou...

Страница 3: ...o prevent electric shock Please call the specialized installation company or trained personnel when you installing moving operating of the unit Field wiring must confirm to the requirements of units e...

Страница 4: ...commended location methods of Unit Cooler 1 Avoid placing Unit Cooler close to doors Install like Figure 3 or Figure 4 2 Avoid having them face each other when installing multiple units Install like F...

Страница 5: ...rd 7 The area above the unit cooler must be sealed or exposed in such away to allow hand cleaning without the use of tools When lagging or bolting unit flush to the ceilings seal the joint between the...

Страница 6: ...ing installation of the piping to prevent entrance of foreign matter Use only refrigeration grade copper tubing properly sealed against contamination Figure 8 Suction piping installation on an evapora...

Страница 7: ...gh walls or ceilings Precautions should be taken to see that the piping does not touch any structural the transmission of vibration into the building The piping chase must be thoroughly sealed to prot...

Страница 8: ...4 SC ADR196 19600 SBFSE B C HFESC 1 1 2 SC ADR218 21800 SBFSE B C HFESC 1 1 2 SC ADR273 27300 SBFSE C C HFESC 2 SC ADR393 39300 SBFSE C C HFESC 3 1 2 SC LED042 4200 R 404A 20 29 SBFSE A Z HFESC 1 2 SZ...

Страница 9: ...0 SBFSE B Z MLD220 22000 SSE 3 Z MLD253 25300 SSE 3 Z MLD332 33200 SSE 4 Z MLD388 38800 SSE 6 Z MLD442 44200 SSE 6 Z TTA056 5600 R 404A 25 4 SBFSE A C TTA084 8400 SBFSE A C TTA112 11200 SBFSE A C TTA1...

Страница 10: ...7 8 7 8 7 8 7 8 7 8 1 1 8 7 8 7 8 1 1 8 1 1 8 18000 5 8 7 8 7 8 7 8 7 8 7 8 7 8 1 1 8 7 8 7 8 1 1 8 1 1 8 7 8 1 1 8 1 1 8 1 1 8 24000 5 8 7 8 7 8 7 8 7 8 7 8 1 1 8 1 1 8 7 8 1 1 8 1 1 8 1 1 8 1 1 8 1...

Страница 11: ...3 8 1 3 8 1 5 8 1 5 8 1 2 1 2 5 8 5 8 1 All line size are basic for O D type L copper tube The above table is maximum suction size and riser size should not exceed horizontal size 2 Suction line size...

Страница 12: ...n and the compressor and fans will run continuously At this time fan power is supplied later than compressor power by fan delay thermostat If it does not a partial defrost results and the residual wat...

Страница 13: ...company Timer should be set correctly Determine the number of defrosts per day and the best time of day for it to occur Insert pins accordingly Set the fail safe time to terminate the defrost a few m...

Страница 14: ...ld be concrete or steel sufficient to support between 2 to 5 times the weight of condensing unit Condensing units must be mounted using pads to avoid vibration or shifting The anchor bolts should be u...

Страница 15: ...15 Figure 11 Spring Mount...

Страница 16: ...djusting the expansion valve Evaporator superheat greater than 14 can substantially reduce system capacity while superheat less than 4 has the potential for flood back Compressor Superheat Compressor...

Страница 17: ...ne in the high side only and with liquid metering devices If R 404A is used liquid must be charged and read up refrigerant explanatory Start up Use the following operating procedure after the installa...

Страница 18: ...Ice build up in coil quickly Fin spaced too narrow Replace coil Evaporating temperature too low Adjust expansion valve Decrease of air volume Check fan and clean air filter Unit cooler capacity is too...

Страница 19: ...cle too short Adjust defrost thermostat or timer for longer cycle Defective timer or defrost thermostat Replace defective component Ice accumulating on ceiling around evaporator on fan guard or blades...

Страница 20: ...ne solenoid not open Repair or replace coil Noisy Compressor Flooding of liquid refrigerant into crankcase Check expansion valve setting Improper piping support on suction or liquid line Relocate add...

Страница 21: ...itions are within allowable limits Discharge valve partially closed Open valve Dirty condenser coil Clean coil Overcharged refrigerant Reduce charge Compressor loses oil Lack of refrigerant Check for...

Страница 22: ...22 Field Wiring Diagram 1 Typical wiring diagram for single evaporator with or without defrost timer Diagram 2 Typical diagram for single evaporator defrost timer only...

Страница 23: ...23 Diagram 3 Typical diagram for single evaporator with defrost timer and single phase heater contactor Diagram 4 Typical diagram for single evaporator with defrost timer and 3 phase heater contactor...

Страница 24: ...24 Diagram 5 Typical diagram for single evaporator defrost timer only TTE TYPE...

Страница 25: ...25 4184 EAST CONANT ST LONG BEACH CA 90808 FAX 562 429 7154 Toll Free 888 900 1002 U S A Canada http www turboairinc net...

Отзывы: