12
05: Bypass mode enable/disable
Interface
Setting
ENA:
Bypass mode enable
DIS:
Bypass mode disable
06: Bypass voltage range setting
Interface
Setting
Press the Down key or Up key to set the acceptable high
voltage point and acceptable low voltage point:
HLS:
Bypass high voltage point
LLS:
Bypass low voltage point
For 208/220/230/240 VAC models:
230-264: setting the high voltage point from 230Vac to
264Vac
170-220: setting the low voltage point from 170Vac to
220Vac
For 110/115/120/127 VAC models:
120-132: setting the high voltage point from 120Vac to
132Vac
85-115: setting the low voltage point from 85Vac to
115Vac
00: Exit setting
3-6. Operating Mode Description
Operating mode Description
LCD display
Online mode
When the input voltage is within
acceptable range, UPS will provide pure
and stable AC power to output. The UPS
will also charge the battery at online
mode.
ECO mode
Energy saving mode:
When the input voltage is within voltage
regulation range, UPS will bypass
voltage to output for energy saving.
Battery mode
When the input voltage is beyond the
acceptable range or power failure and
alarm is sounding every 4 second, UPS
will backup power from battery.