12/06/2012 7
GI202
Duct System and Blower
Metal ductwork should be used, and flexible connectors are required for supply and return air duct connections.
All TVA & TVT THERM GEO units have flanges for connecting your supply plenum and return ductwork.
If the duct system is installed in an uninsulated space, the metal ductwork should be insulated on the outside to
prevent heat loss, absorb noise, and prevent condensation during cooling.
If the TTHERM GEO is connected to existing ductwork, the ductwork must have the capacity to handle the air
volume required to unload the heat pump. Undersized ductwork will cause noisy operation due to high air
velocity, and poor operating efficiencies. Check the Duct Sizing Chart provided.
The TTHERM GEO heat pumps use a variable speed ECM blower motor. The GEO Logic controller determines
the speed of the motor based on mode and operation sequence. The blower speed can be fine-tuned to each
installation with the tweak switches described below.
The blower will not operate properly if ductwork is not attached. The ductwork provides static pressure to give
the blower motor a load to work against. All blower compartment covers must be in place for the heat pump to
operate correctly.
TVT - Blower CFM – Two Stage Compressor
Model
G Cool
Y Heat
Y Cool
Y2 Heat
Y2 Cool
Y 2 Heat + W2
E
TVT – 024
390
640
735
850
980
980
680
TVT – 036
515
900
965
1200
1290
1380
960
TVT – 042
575
985
1080
1310
1440
1500
1050
TVT – 048
660
1125
1235
1500
1650
1725
1200
TVT – 060
825
1400
1545
1875
2060
2160
1500
CFM Rounded
Y2 can be field fine-tuned or tweaked with a 4 position switch. The 4 positions are 0%, -6%, +6%, +12%
G can be field fine-tuned or tweaked with a 4position switch. The 4 positions are 0%, -6%, +6%, +12%
See figure 8 for location of 4 position switch
TVA - Blower CFM – Single Stage Compressor
Model
G Cool
Y Heat
Y Cool
Y Heat + W2
E
TVA - 036
515
1200
1290
1380
960
TVA
-
048
660 1500 1650 1725 1200
TVA
-
060
825 1875 2060 2160 1500
CFM Rounded
Y can be field fine-tuned or tweaked with a 4 position switch. The 4 positions are 0%, -6%, +6%, +12%
G can be field fine-tuned or tweaked with a 4position switch. The 4 positions are 0%, -6%, +6%, +12%
See figure 8 for location of 4 position switch
The “Y” tweak switch is the 2
nd
switch below the 10 pin thermostat socket.
The “G” tweak switch is the 3
rd
switch below the 10 pin thermostat socket.
Be very sure the tweak switches are set in their position indents.