Operation & Maintenance Manual

 

OMM1002 

 

 

  

 

Introduction

 

The SGUV Mk.2 is a flow meter specifically designed to meet the requirement for a direct reading flow meter for use in Au-
tomatic Sprinkler, Water spray or Deluge systems. It is approved for regular monitoring and testing of such systems by the 
LPCB (Loss Prevention Certification Board), under their 

Rules for Automatic Sprinkler

 

Installations

’ 

(LPS1045), in the UK. 

 

 

The SGUV Mk.2 provides a robust, direct reading flow meter for 50, 80, 100, 150 & 200 mm pipelines and is suitable for use 
in both Horizontal & Vertical pipes, with the flow in any direction:

 

 

• 

Horizontally: Left to Right 

 

                           Right to Left

 

• 

Vertically:     Upwards 

 

 

              Downwards

 

 

Full bore Isolation valves are located in the by

-

pass loop, allowing meter isolation for Filter cleaning & Tube replacement. 

The inline Filter avoids clogging of the by

-

pass loop with any pipeline debris. In addition, a Rodding device ensures that the 

secondary Restrictor Orifice remains clear of any smaller particles or algae. Bleed/Drain valves allow venting of trapped Air 
or draining of the isolated Indicator by

-

pass loop.

 

Principles of Operation 

 

The SGUV Mk.2 is a combination of two simple measuring elements:

 

 

1. Installed in the main pipeline is a sharp edged Orifice, mounted in a Carrier ring. This assembly produces a     

 

              

pressure drop proportional to the square root of the flow.

 

2. Installed across the main Orifice/Carrier assembly is an Indicator by

-

pass loop containing an accurately                                  

calibrated Restrictor (secondary Orifice). This Restrictor converts the main Orifice pressure drop into flow rate, which is 
directly proportional to the main pipeline flow. 

 

Materials of Construction

 

Carrier Assy

 

Orifice plate: Stainless Steel mounted in: carrier, steel, red polyester powder coated in two styles 

 

Indicator Assy

 

Housing: die

-

cast aluminum alloy, white polyester powder coated. Bezel: die

-

cast aluminum alloy, black 

polyester powder coated. Window: Perspex

 

 

Isolation valves; full bore brass ball valve, bright nickel plated. Rodding device: Stainless Steel. Filter ele-
ment: Stainless Steel with 1.5mm perforations. Filter housing: TPX.

 

 

Other pipes and connectors: copper and brass, bright nickel plated. 

 

Seals: nitrile and polyurethane. Bleed/drain valve seats: PTFE

 

Tube Assy

 

Tube: Borosilicate glass with 100 mm fused in ceramic scale.

 

Float: Stainless Steel

 

Float stops: Polypropylene 

 

Page 1 

 

Содержание SGUV MK.2

Страница 1: ...Measurement Control LTD PLATON Issue B 07 2017 TT Electronics Roxspur Measurement Control 2 Downgate Drive Sheffield South Yorkshire S4 8BT UK Ph 44 0 114 244 2521 www ttelectronics com RoxspurSales ttelectronics com Every effort has been made during the preparation of this document to ensure the accuracy of statements and specifications However we do not accept liability for damage injury loss or...

Страница 2: ...rier Installation Indicator Installation 3 3 3 Recommended Pipeline Configuration 4 Instrument Configuration Horizontal Pipelines 5 Instrument Configuration Vertical Pipelines 6 Operation 7 Maintenance 8 Glass Tube Cleaning or O Ring Glass Tube Replacement Filter Cleaning or O Ring Filter Element Replacement By pass Loop Air Removal 8 8 8 Spares 9 10 Returns Warranty 11 ...

Страница 3: ...Indicator by pass loop Principles of Operation The SGUV Mk 2 is a combination of two simple measuring elements 1 Installed in the main pipeline is a sharp edged Orifice mounted in a Carrier ring This assembly produces a pressure drop proportional to the square root of the flow 2 Installed across the main Orifice Carrier assembly is an Indicator by pass loop containing an accurately calibrated Rest...

Страница 4: ... Fire Security Products Services Part 5 Automatic Sprinkler Water Spray Deluge Systems Section 6 Direct Reading Flow Meters LPCB Ref NO Nominal Pipe Size mm Flow Range dm3 min Test Flow dm3 min Accuracy Test Flows dm3 min 088a 05 088a 10 088a 06 088a 11 088a 07 088a 12 088a 08 088a 13 088a 09 088a 14 50 80 100 150 200 150 750 300 2300 500 3500 900 8200 2500 12500 500 800 1300 1500 2200 2500 3500 4...

Страница 5: ...anges 3 Ensure that the Gaskets not supplies either side of the Carrier has an Inside Diameter I D greater than or equal to the pipe nomi nal bore Also ensure that when assembled no part of the gasket protrudes into the pipeline at any point Grooved Style 1 The Carrier should be mounted to the pipeline using two appropriately specified joints 2 Always lubricate gasket joints so as to avoid pinchin...

Страница 6: ...Operation Maintenance Manual OMM1002 4 Page 4 ...

Страница 7: ...Operation Maintenance Manual OMM1002 5 Page 5 ...

Страница 8: ...Operation Maintenance Manual OMM1002 6 Page 6 ...

Страница 9: ... 3 Bleed all air from the Indicator by pass loop before taking any flow readings 4 Make sure that the Isolating Valves J are fully open before taking any flow readings 5 Read the top edge of the Float 6 When not in use the Isolation Valves should be closed and the Indicator by pass loop drained Once the unit has been fully drained all the Bleed Drain Valves should then be closed Page 7 ...

Страница 10: ... end connectors by pulling noting which Insert came from which end connector To aid with their removal the plastic wedge can now be used as a sliding wedge 7 Remove 2x old O rings from each insert 8 Care should be taken that the new O rings C1 C2 are not damaged when assembling them to the inserts 9 Moistening the O rings with a suitable lubricant is advisable such that when re assembling to the e...

Страница 11: ...he Air has been removed 4 Open the Isolation Valve Spares The instruments should not require maintenance to replace parts if the instrument is used in accordance with these instruc tions However spare parts are available to meet most needs as detailed below For Complete Instruments see Table 4 For Major Assemblies see Table 5 For Components Sub Assemblies see Table 6 Complete assembled Instruments...

Страница 12: ...anged Grooved By Pass 50 LPCBC312 LPCB314 LGTF F1 5 LGTF F1 10 LPCB1 80 LPCBC512 LPCB514 LGTF F1 6 LGTF F1 11 100 LPCBC612 LPCB614 LGTF F1 7 LGTF F1 12 150 LPCBC812 LPCB814 LGTF F1 8 LGTF F1 13 200 LPCBC912 LPCB914 LGTF F1 9 LGTF F1 14 Table 5 Major Assemblies The Tube Float assemblies of a particular NB are universal between the 2 Carrier styles Two sets of codes have been included for simplicity...

Страница 13: ...of being contaminated they will be returned to you On receipt of the appropriate documentation the goods will be examined and assessed in accordance with the terms of any Warranty agreement Repairs Prior to any repair work being carried out you will be informed of our findings and any charges that may be incurred Replacement Prior to the supply of any replacements you will be informed of our findi...

Отзывы: