2SHUDWLQJ3ULQFLSOHRIWKH$XWRPDWLF3XPSV
7KLVH[SODLQVWKHFRQWUROIRUPE\DFRPELQDWLRQRIDQHOHFWURGHDQGDWLPHUIXQFWLRQ3OHDVHXQGHUVWDQGWKH
SHUIRUPDQFHRIWKLVSXPSDQGDSSO\LW
Start
operation
(Drainage)
Electrode Level Sensor
Pump
Water
Level
Condition
Drop
[Switch on]
Operation
(Drainage)
Stop
Operation
(Drainage)
Start
operation
(Drainage)
Drop
Drop
Rise
Drop
Electrode level sensor will submerge and the
pump will operate by the current.
When the water level drops and detaches
the electrode from the water surface, a timer
will start. Pump keeps draining.
The operation time with the timer will be
approx. 1 minute.
After 1 minute, the pump will stop.
* If the water is drained within 1 minute, the
pump continues to run in snore mode until
the set time comes.
When the water level rises and the water
surface touches to the electrode again for
more than one (1) second, pump will restart.
(Detection Time : more than one (1) second)
(Released the Electrode The timer is on)
(Detection Time : more than one (1) second)
* If the water surface touches to the electrode
for more than one (1) second within 1 minute,
the pump operates continuously even though
the timer is on.
Pump
Electrode
Level Sensor