SAFETY ALERTS - SAFETY SIGNAL WORD DEFINITIONS 

 

 

 

 

 

 

 

This document contains safety alert pictorial Symbols and Words that point out areas and procedures that require 
special attention with regards to safety. These Symbols and Words are defined in ANSI Z535.4-1998, Product Safety 
Signs and Labels. 

         DANGER:  

 DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. 

         

WARNING:  

 WARNING indicates a potentially hazardous situation which, if not avoided, will result in death or serious injury. 

         

CAUTION:   

CAUTION indicates an imminently hazardous situation which, if not avoided, may result in minor or moderate injury. 
It may also be used to alert against unsafe practices. 

The safety alert pictorial symbol        appears in this document to make users aware of important operating and 
safety concerns. 

Tools and Test Equipment Required 

 

 

 

 

 

 

 

 

 

 

 

 

Miscellaneous hand tools 

 

DMM (digital voltmeter) 
 

Voltage Selection 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

 

If you have a 208, 220 or 240 V ATS the voltage range can be changed. The factory setting is either set to HIGH 
(220 to 240 V) or LOW (208 V) depending on ATS model ordered. If the factory preset is not desired, performing 
the following steps will change the voltage transfer points.  

2.

 

Make sure both Primary and Backup AC sources to the ATS are de-energized.  

3.

 

Remove the ATS case cover.  

4.

 

Locate the jumper at JP1 (HIGH) or JP2 (LOW). See figure 1.  

5.

 

To change the voltage selection simply move the Jumper from the JP1 (HIGH) to JP2 (LOW) position or JP2 (LOW) 
to JP1 (HIGH) position (depending on the factory preset of your ATS).  

6.

 

Replace the ATS case cover.  

Remote Status / Alarm Monitoring 

 

 

 

 

 

 

 

 

 

   

1.

 

A DB-9 female connector in the rear of the unit provides status / alarm signals for remote monitoring of the sta-

tus of the ATS.  

2.

 

Primary AC Input Status DB-9 Pins are: 

_5_

NO 

_1_

NC

_2_

COM  

3.

 

Backup AC Input Status DB-9 Pins are: 

_6_

NO

_3_

NC

_4_

COM

 

 

4.

 

When Primary AC Input is present and IN SPECIFICATION, there is an OPEN circuit between pin

_5_

and pin_

2_

When Primary AC input is OUT OF SPECIFICATION, there is a CLOSED circuit between pin_

5_

and pin_

2_

.  

5.

 

When Backup AC Input is present and IN SPECIFICATION, there is an OPEN circuit between pin

_6_

and pin 

_4_

When Backup AC input is OUT OF SPECIFICATION, there is a CLOSED circuit between pin_

6_ 

and pin_

4_

.  

6.

 

Maximum voltage and current that can be used for monitoring the status and alarm of the ATS Series is 120 VDC 
(VAC), 1 A (maximum DB-9 connector rating).  