Operation

 

FLOW SET UP

 

In 

Flow Setup

 mode, there are four types: Round Duct, Rectangle Duct, 

Duct Area, and K-Factor. Use the 

 or 

 soft keys to scroll through 

the types and then press the 

  

key to accept the desired type. To 

change the setting, highlight the 

Enter Settings

 option and press the 

 

key.  

Press/Kfact

 allows for calculating flow rate from diffusers or flow 

stations with pressure taps using the instruments pressure ports and 
K-factors. The K-factors are obtained from the diffuser or flow station 
manufacturer. For more information, refer to 

Application Note TSI-114

. 

 

Up to 5 K-factors can be pre-programmed for quick use. 

 

When 

Flow

 is set as the 

Primary

 measurement in the 

Display 

Setup 

menu, the K-factor will also be displayed. 

When measuring 

Flow 

as the 

Primary

 measurement, the parameters 

can be quickly changed by pressing the 

 

or 

 key while on the 

main measurement screen. Make adjustments with the 

 

or 

 arrow 

keys and press 

 to accept, or enter the 

Select

 

Kfactor

 menu to 

choose a different pre-programmed flow value. 

ACTUAL/STANDARD SETUP

 

Choose Actual/Standard measurements and parameters in the 
Act/Std Setup menu. Within this menu, you can also select Standard 
Temperature, Standard Pressure and a source for the actual 
temperature. The actual barometric pressure must be entered to 
convert air velocity and volume measurements to actual conditions. 
The Entered Temp range is from -40 to 1832°F (-40 to 1000°C). 

DATA LOGGING

 

Measurements 

Measurements to be logged are independent of measurements 
on the display, and must; therefore, be selected under 

DATA

 

LOGGING 

 Measurements

 

When set to 

ON

, measurement will be logged to memory. 

 

When set to 

DISPLAY

, measurement will be logged to memory 

if it is visible on the main running screen. 

 

When set to 

OFF

, measurement will not be logged to memory. 

www.calcert.com

[email protected]

1.800.544.2843

0

5

10

15

20

25

30

Содержание AIRFLOW Model PVM620

Страница 1: ...MICROMANOMETER ALNOR MODEL AXD620 AIRFLOW INSTRUMENTS MODEL PVM620 OPERATION AND SERVICE MANUAL P N 1980588 REV E FEBRUARY 2016 www calcert com sales calcert com 1 800 544 2843 0 5 10 15 20 25 30...

Страница 2: ...d by anyone other than a factory authorized service center with the one exception where requirements set forth in the manual allow an operator to replace consumables or perform recommended cleaning g...

Страница 3: ...of loss Buyer and all users are deemed to have accepted this LIMITATION OF WARRANTY AND LIABILITY which contains the complete and exclusive limited warranty of Seller This LIMITATION OF WARRANTY AND...

Страница 4: ...CHAPTER 3 OPERATION 5 Keypad Functions 5 Common Terms 5 Menus 6 DISPLAY SETUP 6 PRESSURE ZERO 6 SETTINGS 6 FLOW SET UP 7 ACTUAL STANDARD SETUP 7 DATA LOGGING 7 Measurements 7 Log Mode Log Settings 8 D...

Страница 5: ...ontainer Check the individual parts against the list of components below If anything is missing or damaged notify TSI immediately 1 Carrying case 2 Instrument 3 Pressure tubing 4 Static pressure tip 5...

Страница 6: ...of the danger of battery acid leakage Using the Optional AC Adapter When using the AC adapter the batteries if installed will be bypassed Be sure to provide the correct voltage and frequency which is...

Страница 7: ...setting a parameter Press the Menu soft key to select the Menu selections which are Display Setup Pressure Zero Settings Flow Setup Actual Std Set up Data Logging and Calibration Common Terms In this...

Страница 8: ...is where you will setup the desired parameters to be displayed on the running screen With a parameter highlighted you can then use the ON soft key to have it show up on the running screen or select t...

Страница 9: ...g the or key while on the main measurement screen Make adjustments with the or arrow keys and press to accept or enter the Select Kfactor menu to choose a different pre programmed flow value ACTUAL ST...

Страница 10: ...Data Use this to delete all data delete test or delete sample Memory This option displays the memory available Delete All under Delete Data will clear memory and reset the memory available LogDat2TM...

Страница 11: ...sing the CALIBRATION menu These field adjustments are intended to make minor changes in calibration to match a user s calibration standards The field adjustment is NOT intended as a complete calibrati...

Страница 12: ...10 Chapter 4 Storage Remove the batteries when storing the unit for more than one month to prevent damage due to battery leakage www calcert com sales calcert com 1 800 544 2843 0 5 10 15 20 25 30...

Страница 13: ...ow or dead batteries Replace batteries or plug in AC adapter Dirty battery contacts Clean the battery contacts Reading fluctuates unstable Fluctuating flow Reposition probe in less turbulent flow or u...

Страница 14: ...low Rate Range Actual range is a function of actual velocity pressure duct size and K factor Instrument Temperature Range Operating 40 to 113 F 5 to 45 C Storage 4 to 140 F 20 to 60 C Instrument Opera...

Страница 15: ...psi 190 in H2O 360 mmHg 48 kPa 2 Pressure velocity measurements are not recommended below 1 000 ft min 5 m s and are best suited to velocities over 2000 ft min Range can vary depending on barometric...

Отзывы: