Set Up
11
1.
Flow units
: CFM (cubic feet per minute), l/s (liters per second),
and m3/hr (cubic meters per hour). The A
CCU
B
ALANCE
indicates
flow already corrected to "standard" conditions (see Appendix A).
2.
Flow value
: See specifications for range and resolution.
3.
Flow direction arrow
: Indicates if supply or return air flow
calibration is being utilized by the A
CCU
B
ALANCE
.
Notice:
Be sure this arrow points in the direction of flow through the
A
CCU
B
ALANCE,
otherwise the measurements made will be
inaccurate. To change the direction of the arrow, press the
RETURN/SUPPLY
switch.
4.
Averaging mode
: The "
AVERAGE
" message will appear on the
display when you have selected the three-second or six-second
averaging mode (See
Averaging Mode
section later in this chapter).
5.
Hold indicator
. The "
HOLD
" message will appear along with a
flow value after you have activated the
HOLD
button.
6. "
LOW BATTERY
". Displayed when batteries are getting near the
end of their useful life.
7 . "
BATTERY
" will appear along with a value on the display during
power-up to indicate the percent of battery life remaining.
Preparing the Instrument for Use
Hood Assembly
The A
CCU
B
ALANCE
is shipped from the factory partially assembled
with the 2 ft x 2 ft nylon hood attached to the base. If you wish to use
another hood size, see
Changing Hoods
in Chapter 2.
Содержание AccuBalance 8370
Страница 2: ......
Страница 8: ...iv...
Страница 10: ...2 About this manual...
Страница 12: ...4 Introduction...
Страница 26: ...18 Chapter 1...
Страница 42: ...34 Chapter 2 Averaging Mode 3 sec Average 435 CFM 3 sec Average 1580 m3 hr 6 sec Average 132 l s...
Страница 56: ...48 Appendix D...
Страница 58: ...50 Appendix E...