TSI Incorporated Q-TRAK 7575 Скачать руководство пользователя страница 1

 

 

 

 

 

Indoor Air Quality 

 

 

 

 

Q-T

RAK

™ 

Indoor Air Quality Monitor

 

Model 7575 

 
 

Operation and Service Manual 

 

 

 

ENERGY AND COMFORT

 

Содержание Q-TRAK 7575

Страница 1: ...Indoor Air Quality Q TRAK Indoor Air Quality Monitor Model 7575 Operation and Service Manual ENERGY AND COMFORT ...

Страница 2: ......

Страница 3: ...on with goods which are incorporated into other products or equipment or which are modified by any person other than Seller The foregoing is IN LIEU OF all other warranties and is subject to the LIMITATIONS stated herein NO OTHER EXPRESS OR IMPLIED WARRANTY OF FITNESS FOR PARTICULAR PURPOSE OR MERCHANTABILITY IS MADE WITH RESPECT TO SELLER S BREACH OF THE IMPLIED WARRANTY AGAINST INFRINGEMENT SAID...

Страница 4: ...its terms waived except by writing signed by an Officer of Seller Service Policy Knowing that inoperative or defective instruments are as detrimental to TSI as they are to our customers our service policy is designed to give prompt attention to any problems If any malfunction is discovered please contact your nearest sales office or representative or call Customer Service department at 800 874 281...

Страница 5: ...le Ports 5 Connecting the Thermocouples 5 Connecting the Optional Bluetooth Portable Printer Device 6 Connecting to a Computer 6 CHAPTER 3 OPERATION 9 Keypad Functions 9 Common Terms 10 Menus 11 DISPLAY SETUP 11 SETTINGS 12 FLOW SET UP 13 VOC SETUP 14 ACTUAL STANDARD SETUP 15 DATA LOGGING 16 Measurements 16 Log Mode Log Settings 16 Choose Test 21 Name Test 22 View Data 23 View Stats 23 View Sample...

Страница 6: ...LUG IN PROBES 39 These Application Notes can be found under TSI s web site http www tsi com TSI 109 Converting Standard Velocity to Actual Velocity TSI 124 Heat Flow Calculations TSI 138 Percent Outdoor Air Calculation and Its Use TSI 141 Turbulence Intensity Measurements TSI 142 Draft Rate A Determining Factor in the Quantification of Human Comfort TSI 147 Photo Ionization Detection PID Technolog...

Страница 7: ...ment and accessories from the shipping container Check the individual parts against the list of components below If anything is missing or damaged notify TSI immediately 1 Carrying case 2 Instrument 7575 X 3 USB cable 4 TRAKPRO CD ROM with data analysis software 5 AC adapter ...

Страница 8: ...Chapter 1 2 This page intentionally left blank ...

Страница 9: ...are used If NiMH batteries are used the DIP switch will need to be changed Refer to the next section DIP Switch Settings Carbon zinc batteries are not recommended because of the danger of battery acid leakage DIP Switch Settings To access the DIP switch remove the batteries from the battery compartment On the inside of the battery compartment there is a window with a single DIP switch see figure b...

Страница 10: ...onitor will be powered by the AC adapter Be sure to provide the correct voltage and frequency which is marked on the back of the AC adapter Connecting IAQ or Ventilation Probes The ventilation and IAQ probes have a D shape overmolding on the mini DIN connector which must align with the connector at the base of the 7575 monitor This will ensure the probe is properly connected and remains so during ...

Страница 11: ...g the probe as this prevents the robe from extending Retracting the Probe To retract the probe hold the handle in one hand while gently pulling the probe cable until the smallest antenna section is retracted Do not use the instrument or probes near hazardous voltage sources since serious injury could result Thermocouple Ports The 7575 series includes two thermocouple ports at the base of the monit...

Страница 12: ...keys to highlight Bluetooth Functions and press the key Highlight Discover Devices and press the key If other TSI Bluetooth printers are in the area turn them off before searching The Model 7575 will then search for and list all available Bluetooth devices For more information on establishing Bluetooth connections refer to TSI Applications Note TSI 150 Connecting to a Computer Use the Computer Int...

Страница 13: ...el 7575 is not intended for connection to a public telecommunications network Connect the USB data port only to another USB port on a safety certified computing device Protection provided by the instrument could be impaired if used in a manner other than specified in this user manual ...

Страница 14: ...8 Chapter 2 This page intentionally left blank ...

Страница 15: ...FF Key is bypassed If the ON OFF Key is pressed while the AC adapter is attached the instrument instructs you to Unplug the instrument to turn off unit To turn the instrument on again attach the AC adapter or press the ON OFF Key Arrow Keys Press to scroll through choices while setting a parameter Pressing the keys simultaneously will lock the keypad to prevent unauthorized adjustments to the inst...

Страница 16: ... number of test IDs is 100 Time Constant The time constant is an averaging period It is used to dampen the display If you are experiencing fluctuating flows a longer time constant will slow down those fluctuations The display will update every second but the displayed reading will be the average over the last time constant period For example if the time constant is 10 seconds the display will upda...

Страница 17: ...how up on the instrument screen or select the OFF soft key to turn off the parameter Use PRIMARY soft key to have a parameter show up on the instrument screen in a larger display A total of 5 parameters can be shown on the display 1 primary large font and 4 secondary Parameters shown in the Display Setup screen are dependent on the type of probe currently connected When set to PRIMARY measurement ...

Страница 18: ...tup Settings Flow Setup VOC Setup Actual Std Setup Data Logging Zero CO Applications Calibration Bluetooth Functions DISPLAY SETUP CO2 ON Temperature OFF RH OFF Dewpoint ON Wetbulb ON CO ON Baro Press OFF ON PRIMARY OFF MENU Display Setup Settings Flow Setup VOC Setup Actual Std Setup Data Logging Zero CO Applications Calibration Bluetooth Functions SETTINGS Language English Beeper Disable Select ...

Страница 19: ...llows can be used with this function AM 100 AM 300 AM 600 and AM 1200 If a horn model number is chosen the instrument will return to measuring mode and use a preprogrammed curve to calculate flow rate from velocity when using a thermoanemometer probe The air cone selection applies to the Model 995 Rotating Vane Anemometer and the Air Cone kit p n 801749 FLOW TYPE Round duct Rectduct Ductarea Horn ...

Страница 20: ...lar Weight of a specific gas allows for converting concentration PPM or PPB to mass concentration mg m3 Reset Isobutylene will restore the factory to factory conditions for Isobutylene 56 11 For more information refer to Application Note TSI 147 MENU Display Setup Settings Flow Setup VOC Setup Actual Std Setup Data Logging Zero CO Applications Calibration Bluetooth Functions VOC SETUP Response Fac...

Страница 21: ...r taken from a probe that measures temperature plug in probe or thermocouple For more information on Actual and Standard conditions refer to Application Note TSI 109 MENU Display Setup Settings Flow Setup VOC Setup Actual Std Setup Data Logging Zero CO Applications Calibration Bluetooth Functions ACTUAL STD SETUP Setting Standard Temp source Entered SETTING Standard Actual TEMP SOURCE Entered Temp...

Страница 22: ...l not be logged to memory Log Mode Log Settings The 7575 can be programmed to store measurements to memory in several different logging formats Manual Auto save Cont key Cont time Program 1 Program 2 MENU Display Setup Settings Flow Setup VOC Setup Actual Std Setup Data Logging Zero CO Applications Calibration Bluetooth Functions DATA LOGGING Measurements Log Mode Cont time Log Settings Choose Tes...

Страница 23: ...Auto Save Logging In Auto save mode the user samples are automatically logged to memory at the end of the sampling period To start logging press the key DATA LOGGING Measurements Log Mode Manual Log Settings Choose Test Test 001 Name Test View Data Delete Data Memory DATA LOGGING Measurements Log Mode Auto save Log Settings Choose Test Test 001 Name Test View Data Delete Data Memory LOG MODE Manua...

Страница 24: ...ing the key The instrument will continue logging until the key is pressed again DATA LOGGING Measurements Log Mode Auto save Log Settings Choose Test Test 001 Name Test View Data Delete Data Memory DATA LOGGING Measurements Log Mode Cont key Log Settings Choose Test Test 001 Name Test View Data Delete Data Memory SAMPLE TIME 00 05 Min Sec LOG MODE Manual Auto save Cont key Cont time Program 1 Prog...

Страница 25: ... time Logging In Cont time mode the user starts taking readings by pressing the key The instrument will continue taking samples until the time as set in Test Length has elapsed DATA LOGGING Measurements Log Mode Cont key Log Settings Choose Test Test 001 Name Test View Data Delete Data Memory DATA LOGGING Measurements Log Mode Cont time Log Settings Choose Test Test 001 Name Test View Data Delete ...

Страница 26: ...d Program 2 are customized data logging setup programs Setting them up is performed using TSI s TRAKPRO Data Analysis software TRAKPRO is a trademark of TSI Incorporated DATA LOGGING Measurements Log Mode Cont time Log Settings Choose Test Test 001 Name Test View Data Delete Data Memory DATA LOGGING Measurements Log Mode Cont time Log Settings Choose Test Test 001 Name Test View Data Delete Data M...

Страница 27: ... group of Samples that are used to determine statistics average minimum and maximum of a measurement application The 7575 can store 26 500 samples and 100 test IDs one sample can contain fourteen measurement types Example Each duct traverse will have its own Test ID consisting of several Samples Pressing NEW will advance to the next available Test ID Pressing DATES will list the date the Test was ...

Страница 28: ...me DATA LOGGING Measurements Log Mode Cont time Log Settings Choose Test Test 001 Name Test View Data Delete Data Memory DATA LOGGING Measurements Log Mode Cont time Log Settings Choose Test Test 001 Name Test View Data Delete Data Memory CHOOSE TEST Test 001 9 Samples Test 002 7 Samples Test 003 0 Samples Test 004 0 Samples Test 005 0 Samples Test 006 0 Samples Test 007 0 Samples Test 008 0 Sampl...

Страница 29: ...d in a Test ID DATA LOGGING Measurements Log Mode Auto save Log Settings Choose Test Test 001 Name Test View Data Delete Data Memory DATA LOGGING Measurements Log Mode Auto save Log Settings Choose Test Test 001 Name Test View Data Delete Data Memory VIEW DATA Choose Test Test 001 View Stats View Samples Print Test CHOOSE TEST Test 001 9 Samples Test 002 7 Samples Test 003 0 Samples Test 004 0 Sam...

Страница 30: ... must be established between the 7575 and the Model 8934 wireless printer or PC set up with Bluetooth communications View Samples Use the and arrow keys to view samples of all the measurement parameters stored in a Test ID TEST 001 CO2 Avg 750 ppm Min 747 ppm Max 752 ppm Samples 9 10 31 08 07 01 39 AM PRINT TEST 001 Temperature Avg 78 2 F Min 78 1 F Max 78 3 F Samples 9 10 31 08 07 01 39 AM PRINT ...

Страница 31: ... Model 8934 wireless printer or PC set up with Bluetooth communications For more information on establishing Bluetooth connections refer to TSI Applications Note TSI 150 TEST 001 Velocity Sample 1 218 ft min Sample 2 280 ft min Sample 3 316 ft min Sample 4 399 ft min Sample 5 188 ft min Sample 6 306 ft min Sample 7 313 ft min Sample 8 294 ft min Sample 9 309 ft min PRINT TEST 001 Temperature Sampl...

Страница 32: ...Test 001 Name Test View Data Delete Data Memory DELETE DATA Delete All Delete Test Delete Sample DELETE DATA Delete All Delete Test Delete Sample DELETE DATA Delete All Delete Test Delete Sample DELETE ALL Are you sure YES NO DELETE TEST Test 001 14 Samples Test 002 10 Samples Test 003 12 Samples Test 004 8 Samples Test 005 7 Samples Test 006 15 Samples Test 007 0 Samples Test 008 0 Samples Test 0...

Страница 33: ...nder Delete Data will clear memory and reset the memory available to 100 DELETE DATA Delete All Delete Test Delete Sample MEMORY Test ID 83 Sample 92 DELETE SAMPLE Test 001 14 Samples Test 002 10 Samples Test 003 12 Samples Test 004 8 Samples Test 005 7 Samples Test 006 15 Samples Test 007 0 Samples Test 008 0 Samples Test 009 0 Samples Test 010 0 Samples DATES ...

Страница 34: ...ICATIONS This menu option includes specialized measurement protocols used to perform various tests or investigations You can choose Draft Rate Heat flow Turbulence and Outside Air in the Applications menu For more information on these applications refer to the following information Draft Rate Application Note TSI 142 Heat Flow Application Note TSI 124 Turbulence Intensity Application Note TSI 141 ...

Страница 35: ...del 7575 contains a Bluetooth Functions menu which is used to adjust parameters to assist with wireless connections to other Bluetooth capable devices MENU Display Setup Settings Flow Setup VOC Setup Actual Std Setup Data Logging Zero CO Applications Calibration Bluetooth Functions APPLICATIONS Draft Rate Heatflow Turbulence Outside Air MENU Display Setup Settings Flow Setup VOC Setup Actual Std S...

Страница 36: ... security key to be entered into the computer if prompted The factory default PINcode is 0000 NOTE PINcode must be set to 0000 in order to use 8934 printer AutoConnects Specifies how many times the instrument will attempt to reattach to a paired device after the power is turned on For this option the instrument Discoverability setting must be enabled Settings are 0 to 5 times For more information ...

Страница 37: ...al software called TRAKPRO Data Analysis Software which is designed to provide you with maximum flexibility and power Follow the instructions on the label of the TRAKPRO software to install the software on your computer TRAKPRO software contains a very comprehensive Help Function This utility provides all the necessary information to guide you in all aspects of software operation The software is s...

Страница 38: ...32 Chapter 3 This page intentionally left blank ...

Страница 39: ... 3824 The Model 7575 can also be recalibrated in the field using the CALIBRATION menu These field adjustments are intended to make minor changes in calibration to match a user s calibration standards The field adjustment is NOT intended as a complete calibration capability For complete multiple point calibration and certification the instrument must be returned to the factory Cases If the instrume...

Страница 40: ...34 Chapter 4 This page intentionally left blank ...

Страница 41: ...Fluctuating flow Reposition probe in less turbulent flow or use longer time constant No response to keypad Keypad locked out Unlock keypad by pressing keys simultaneously Instrument Error message appears Memory is full Download data if desired then DELETE ALL memory Fault in instrument Factory service required on instrument Probe Error message appears Fault in probe Factory service required on pro...

Страница 42: ...36 Chapter 5 This page intentionally left blank ...

Страница 43: ...00 ft min 2 m s Type Thermistor Relative Humidity Range 5 to 95 RH Accuracy2 3 RH includes 1 hysteresis Resolution 0 1 RH Response time 20 seconds for 63 of final value Sensor type Thin film capacitive Outside Air Range 0 to 100 Resolution 0 1 Barometric Pressure Range 20 36 to 36 648 in Hg 517 15 to 930 87 mm Hg Accuracy 2 of reading CO Sensor Range 0 to 500 ppm Accuracy 3 of reading or 3 ppm whi...

Страница 44: ... 1 second to 1 hour user selectable Time Constant Intervals 1 sec 5 sec 10 sec 20 sec 30 sec user selectable External Meter Dimensions 3 8 in 8 3 in 2 1 in 9 7 cm 21 1 cm 5 3 cm Meter Probe Dimensions Model 982 Probe length 7 0 in 17 8 cm Probe diameter of tip 0 75 in 1 9 cm Meter Weight Weight with batteries 0 8 lbs 0 36 kg Power Requirements Batteries Four AA size alkaline or rechargeable or AC ...

Страница 45: ...ing Vane Air Velocity and Temperature Indoor Air Quality IAQ Probes Model Description 980 Indoor Air Quality Probe Temperature Humidity CO2 982 Indoor Air Quality Probe Temperature Humidity CO2 and CO Volatile Organic Compounds VOC Probes Model Description 984 Low Concentration ppb VOC and Temperature 985 High Concentration ppm VOC and Temperature 986 Low Concentration ppb VOC Temperature CO2 and ...

Страница 46: ...40 Appendix B This page intentionally left blank ...

Страница 47: ...rance tsi com Website www tsiinc fr Germany Tel 49 241 523030 E mail tsigmbh tsi com Website www tsiinc de India Tel 91 80 41132470 E mail tsi india tsi com China Tel 86 10 8251 6588 E mail tsibeijing tsi com Singapore Tel 65 6595 6388 E mail tsi singapore tsi com Contact your local TSI Distributor or visit our website www tsi com for more detailed specifications P N 6004850 Rev C Copyright 2012 b...