1.
Protective earth
TruConvert DC series 1000
Note
For the protective earth connection on the TruConvert DC series
1000, there is a thread on the rear side of the housing and a
threaded bolt on the cover hood.
To ensure safe operation,
both
protective earth connections
must be connected to the earthing system with
2 separate
PE
conductors.
1
M6 threaded bolt on cover
hood for protective earth con-
nection
2
Cover hood
3
M6 threaded bolt for protective
earth connection
Protective earth connections
Fig. 4-1
■
On the rear side of the housing: M6 internal thread
■
On the cover hood: M6 threaded bolt
The cross section of the protective earth is dependent on the
grounding concept
of the overall system.
■
1 x 4 mm
2
/ 1 x AWG 10
Fig. 4-2
■
The cross section of the protective earth must be calculated
by the system manufacturer according to the battery proper-
ties and fuse properties.
A67-0140-00.BKen-0
01-05
2020-07-01
Protective earth TruConvert DC series 1000
4
‐
3
View
Connection
Cable requirement
Grounding concept 1:
battery cables ungrounded
Grounding concept 2:
battery cables grounded on
one end
Содержание TruConvert DC 1000 Series
Страница 1: ...Operator s manual TruConvert DC series 1000 TruConvert System Control TruConvert Modular...
Страница 2: ......
Страница 6: ...II Good to know 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 36: ...3 12 Technical data dependent on device variant overview 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 38: ...7 Ethernet 4 10 8 RS 485 4 11 4 2 Interfaces 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 40: ...Fig 4 3 4 4 Protective earth TruConvert DC series 1000 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 48: ...4 12 RS 485 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 54: ...5 6 CSA certification 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 106: ...16 State diagram State machine Fig 7 19 7 38 State diagram 2020 07 01 A67 0140 00 BKen 0 01 05...