The entire installation surface must not have any expansion
joints.
■
No joint of any kind may be located in the load-bearing point
range of the machine or within at least 275 mm (11 in) of it.
■
The distance of the plug bore holes to the edge of the base
plate must be at least 200 mm (8 in).
Floor quality
Note
The floor must be oil-proof.
■
Carrying capacity of the subsurface at least ks = 5000
kN/m
3
.
■
Minimum thickness: 200 mm (7.87 in).
■
Crosswise reinforcement 3.7 cm
2
/m, double-layered.
−
US specification: 2 layers of #5 rebar, spaced 12 in on
center, on both the top and bottom faces and oriented in
both the longitudinal and transverse directions.
■
Concrete quality (equivalent to strength class C 25/30).
A structural analyst must be consulted under the following condi-
tions:
■
The previously mentioned requirements for an elastically
embedded base plate are not met.
■
The system is to be set up on a ceiling plate/free-span base
plate.
■
The system is to be set up on fiber-reinforced concrete or
roller-compacted concrete.
■
The system is to be installed on a floor other than the one
named above.
The machine must be damped against oscillations if other sensi-
tive machines are located directly next to the machine or if the
machine is located on a free-span surface which cannot tolerate
these oscillations.
2
‐
8
Installation site - Version 1
B1161en
Expansion joints
Elastically cushioned base
plate
When is a structural analyst
generally required?
Vibration damping