By pressing MODE        for 3 seconds can activate the energy saving mode with         icon appearing on the screen. If energy saving is 
activated by button pressed, pressing any button will stop energy saving mode. For heating mode, if energy saving function is enabled, the 
set-point will be changed to remote setback heating set-point. The range of remote setback heating set-point is from 10 °C to 21 °C and 
default value is 18 °C. The value can be changed in ISU mode with step of 1 °C. For cooling mode, if energy saving function is enabled, the 
set-point will be changed to remote setback cooling set-point. The range of remote setback cooling set-point is from 22°C to 32°C and 
default value is 26 °C. The value can be changed in ISU mode with step of 1 °C .

FULLY TOUCH SCREEN SERIES

OPERATION INSTRUCTION

MODULATING VALVE CONTROL

Thermostat acquires the room temperature via its 
integrated sensor and maintains the set-point by 
modulating output.

POWER ON OR OFF

By pressing POWER button   

   

INCREASE / DECREASE

In the ON state, press UP        or       

     DOWN to increase or decrease 

the setting parameters.

FAN OPERATION

HEAT/COOL/VENT

Pressing the MODE button         to select heat 
         cool         or ventilation          mode.

TEMPERATURE DISPLAY

Both the room temperature and the set-point 
are displayed.

COMFORT MODE

In the comfort mode, the set point can be
changed by pressing UP      or DOWN      buttons. 

and manual heat/cool changeover.

KEY LOCK

The default status of “Key lock” is all keys available and it can be changed in 
ISU mode. Key lock function includes the following settings: All keys are 
available (Default) System button is locked out. Fan and system buttons are 
locked out . All buttons are locked . The following operating modes are available :

ENERGY SAVING MODE

FREEZE PROTECTION MODE

Freeze protection can be disable(default) or 
enabled via ISU mode. If freeze protection is 
enabled( it is not available in cooling only 
application) and thermostat is in OFF mode while 
the room temperature is below 6 °C , the 
thermostat will open heating device before the 
temperature rises to 8 °C

TIME SETTING

In ON/OFF states, press       and        for 5 seconds, you will hear Bee sound
“bibi” for twice, and the time area           will be flashing, 
press      to select minutes, hours or week, then press        or       
to adjust the relevant time, press         to confirm.

TO SELECT MANUAL AND PROGRAMMABLE

ADJUSTING OF WEEKLY PROGRAMMABLE

3

Press and hold       and      for more than 5 seconds, the icon of       or will 
flash, press       to select manual       or programmable          press         to 
confirm.

After selected programmable mode, press            for more than 5 seconds, you will hear Bee sound “ bibi” twice, then press        to 

select setting item of periods, time and temp. press      or       to adjust the relevant value, press to        confirm. The sequence: 5+2 

programmable mode, time adjusting temperature adjusting from 1-6 periods of Monday to Friday time adjusting temperature 

adjusting from 1-2 periods of Saturday and Sunday (5+2programable mode, 5 every mode has 6 periods and 2 every mode has 2 

periods)

Fan can be selected as manual or automatic 3-speed operation. In manual 

mode, the fan will be switched to the selected speed via controls output 

Gh,Gm,Gl (by pressing FAN button         ). In automatic mode, the fan speed 

will be switched upon difference between the room temperature and set 

point. When room temperature reaches set-point, valve will be closed 

meanwhile, fan will be turned off as well (fan can be changed to low

speed via ISU setting code 17).

Содержание TX986ML220-V2E

Страница 1: ...and DX single stagecompressor units We introduce Bacnet and Modbus communication in this series Option of 9 terminals 13 terminals power box can occupy addons Like AO AI DO and DI as per convenience...

Страница 2: ...e 4 pipe FCU Suitable Valve 2 line 3 line valve Relative Humidity 10 90 13 terminal power box fits in 86cm x 86 cm 9 terminal power box fits in 75cm x 75cm electrical junction box ORDERING PART NUMBER...

Страница 3: ...ROGRAMMABLE ADJUSTING OF WEEKLY PROGRAMMABLE 3 Press and hold and for more than 5 seconds the icon of or will flash press to select manual or programmable press to confirm After selected programmable...

Страница 4: ...ss to confirm Press and revise the values of the setting items press to confirm If you want to revise the other setting items please repeat above step b and c while setting press to exit the setting i...

Страница 5: ...ACTUAL CONDITION 0 INTERNAL SENSOR BUILT IN 1 EXTERNAL SENSOR 0 5 WORKING DAYS A WEEK 1 6 WORKING DAYS A WEEK 2 7 WORKING DAYS A WEEK 3 CLOSE THE PROGRAM SCHEDULE PS IF YOU SELECTED 7 WORKING DAYS A W...

Страница 6: ...2 DESCRIPTION 5 FL LOW SPEED FAN 6 N NEUTRAL IN 7 COM COM FOR MODULATING VALVE EXTERNAL SENSOR KEY CARD 8 AO ANALOG OUTPUT 0 10VDC 9 AI DI EXTERNAL SENSOR KEY CARD TERMINALS NO 1 R 24 V ACTIVE 3 FH H...

Страница 7: ...ck plate on the junction box by screw driver Install the thermostat about 5 feet 1 5m above the floor in an area with good air circulation at average temperature Do not install in locations where the...

Отзывы: