INSTALLATION / OPERATION INSTRUCTIONS
Step 5
A.
The compressor is ready to operate. Plug in the
unit.
B.
Check the temperature control setting in the
upper left of the cabinet backside. The setting
should be at #5 to maintain an approximate
35˚F (1.6˚C). Temperature control is located in
lower rear of cabinet on ballast box.
Allow cooler to function several hours,
completely cooling cabinet before changing the
control setting.
C.
The coolers are designed to maintain
temperatures from 30˚F to 45˚F (-1˚C to
7˚C) degrees according to the control setting.
Excessive tampering with the control could lead
to service difficulties. Should it ever become
necessary to replace temperature control, be
sure it is ordered from your True dealer or
authorized service agent.
D.
Verify that the cabinet lights are working. The
lights are turned on/off by a switch position
above the evaporator housing.
E.
Good air flow in you True unit is critical. Be
careful to load product based on the load limit
stickers positioned on the inside left and right
walls of the merchandiser.
NOTE
If the unit is disconnected or shut off, wait five minutes before
starting again.
RECOMMENDATION
Before loading product we recommend you run your True
unit empty for two to three days. This allows you to be sure
electrical wiring and installation are correct and no shipping
damage has occurred. Remember, our factory warranty does not
cover product loss!
REPLACEMENT PARTS
TRUE maintains a record of the cabinet serial number for your
unit. If at any time during the life of your display case, a part
is needed, you may obtain this part by furnishing the model
number and serial number to the company from whom you
purchased the cabinet. Call Toll-Free: (800)-424-TRUE (Direct
to Parts Department). (800)-325-6152 (U.S.A. & Canada only)
or call: (636)-240-2400.
STARTUP
Serial Number
Step 4
A.
Before your new unit is connected to a power
supply, check the incoming voltage with a
voltmeter. If anything less than 100% of the
rated voltage for operation is noted, correct
immediately.
B.
All units are equipped with a 9 ft. (2.74m)
service cord, and must be powered at proper
operating voltage at all times. Refer to cabinet
data plate for this voltage.
True
requires that a sole use circuit be dedicated
for the unit. Failure to do so voids warranty.
WARNING
Compressor warranties are void if compressor burns out due to
low voltage.
WARNING
Power supply cord ground should not be removed!
NOTE
To reference wiring diagram - Remove rear louvered grill, wiring
diagram is positioned on the inside cabinet wall.
ELECTRICAL INSTRUCTIONS