LAE CONTROL

SEQUENCE OF OPERATION

1.

  Cabinet is plugged in.

 

  a. Display will illuminate.

 

  b. Interior light will illuminate on glass door models only.  (If lights do not come on please see  

 

 

  instructions on following page(s).)  Solid door cabinet lights are controlled by door switch.

2.

  After the LAE control preprogrammed time delay of 3 minutes, the compressor and evaporator fan(s) will start if 

the control is calling for cooling.

  

    a.  Control may be already pre-programmed from the factory so at the start of every compressor cycle or  

  during a defrost cycle, the condenser fan(s) will reverse for 30 seconds to blow dirt off the condensing   
  coil.

3.

  The LAE control will cycle the compressor but may also cycle evaporator fan(s) on and off determined by the 

Set-Point and Differential temperatures. (If the Set-Point needs to be changed due to conditions please see 
instructions on the following page(s).)

  

    a. The 

Set-Point

 is the preprogrammed temperature which shuts off the compressor.

    
    b. The 

Differential

 is the preprogrammed temperature that is added to the Set-Point temperature that will  

  start the compressor.

 

Example:  

If the Set-Point is -9°F/-23°C and the Differential is 10°F/5°C 

 

 

(Set-Point) -9°F + 10 (Differential) = 1°F 

  

Or 

 

 

(Set-Point) -23°C + 5 (Differential) = -18°C 

 

 

The compressor and evaporator fan(s) will cycle off -9°F/-23°C  

 

 

and back on at 1°F/-18°C

4.

  The LAE control may be preprogrammed to initiate defrost by interval or at specific times of day. (If additional 

Defrost Intervals or Cycles are needed or a Manual Defrost is required due to conditions please see instruc-
tions on the following page(s).)

  

    a.  At this time the “dEF” will appear on the display and compressor will turn off until a preprogrammed    

  temperature or duration is reached.  During this time for freezers only, evaporator fan(s) will also  

 

  turn off and the coil heater and drain tube heaters will also be energized.

  
    b.  After the preprogrammed temperature or duration for defrost has been reached there may be a short   

  delay for both the compressor and evaporator fans to restart.  At this time “dEF” may still appear  

 

  on the display for a short time.

True Manufacturing recommends that ONLY the Set-Point and/or  

Defrost Interval may be adjusted due to certain conditions.

This sequence is NOT model specific.

If you have any questions, please contact the Technical Service Department. 

Phone: 800-325-6152  •  Email: [email protected]

Содержание T-12FG

Страница 1: ...eld Troubleshooting Freezer Units Only 25 26 Light Cover Install for T 12FG 27 Maintenance Care Cleaning Cleaning Condenser Coil 28 29 Stainless Steel Equipment Care Cleaning 30 31 Light Bulb Replacem...

Страница 2: ...www truemfg com True Food Service Equipment Inc...

Страница 3: ...ervice personnel Do not puncture refrigerant tubing Caution Risk of fire or explosion Flammable refrigerant used Consult repair manual owner s guide before attempting to service this product All safet...

Страница 4: ...www truemfg com True Food Service Equipment Inc 2 2...

Страница 5: ...helves in place so that children may not easily climb inside Refrigerant Disposal Your old refrigerator may have a cooling system that uses Ozone Depleting chemicals If you are throwing away your old...

Страница 6: ...N At Receptacle Box 1 Turn breaker off 2 Disconnect all wires from receptacle 3 Insulate red wire tape or wire nut 4 Connect black white and green wires to 3 prong plug NEMA 5 20R per instructions on...

Страница 7: ...is recommended for uncrating the unit A Remove the outer packaging cardboard and bubbles or styrofoam corners and clear plastic Inspect for concealed damage Again immediately file a claim with the fre...

Страница 8: ...G REMOTE UNITS This section applies to remotes only Remote cabinets must be ordered as remote We do not recommend converting from a standard self contained to remote system All remote cabinets must be...

Страница 9: ...inst the lower rail assembly see image 4 5 The bearing race on the castor or the top edge of the leg must make firm contact with the rail Unit leveling Four leveling shims have been provided for level...

Страница 10: ...n with the hand brakes WARNING Unit may tip forward if procedure F is not strictly followed G Units final location should be adequately ventilated Conditions where heat exceeds 100 F require an exhaus...

Страница 11: ...ons Doors can not be removed unless placed in specific locations stated in these instructions STEP 2 Two Door Units Slide the front door so it is centered on the cabinet The door can not be removed un...

Страница 12: ...10 8 6 6 6 5 5 4 4 3 2 40 10 8 8 6 6 5 5 4 4 3 2 2 45 10 8 6 6 6 5 4 4 3 3 2 1 50 10 8 6 6 5 4 4 3 3 2 1 1 Wire Gauge for 2 Voltage Drop in Supply Circuits 230 Volts Distance In Feet To Center of Load...

Страница 13: ...vel side to side and front to back Place a carpenter s level in the interior floor in four places A Position level in the inside floor of the unit near the doors Level should be parallel to cabinet fr...

Страница 14: ...N Before loading product we recommend you run your TRUE unit empty for two to three days This allows you to be sure electrical wiring and installation are correct and no shipping damage has occurred R...

Страница 15: ...www truemfg com True Food Service Equipment Inc 13 13 IF YOUR CABINET IS BUILT WITH THIS TEMPERATURE CONTROL PLEASE SEE THE FOLLOWING INSTRUCTIONS...

Страница 16: ...temperature that will start the compressor Example If the Set Point is 9 F 23 C and the Differential is 10 F 5 C Set Point 9 F 10 Differential 1 F Or Set Point 23 C 5 Differential 18 C The compressor...

Страница 17: ...lock settings If no appears the controller is unlocked If yes appears the controller is locked See images 3 and 4 C Once the lock setting has been set correctly release the info button Wait 5 seconds...

Страница 18: ...interior sign lights by the interior door switch depress the rocker switch to the ON position Light Switch is located on inside top right of the ceiling ON Position Solid Door models lights are contr...

Страница 19: ...ntrol Icons May need to unlock control WHY THE SET POINT IS THE TEMPERATURE AT WHICH THE COMPRESSOR WILL SHUT OFF Please note that the set point IS NOT the cabinet holding temperature HOW A To see the...

Страница 20: ...the Manual Defrost button until dEF appears B REAL TIME CLOCK RTC If controller is preprogrammed for RTC press the and hold the Manual Defrost button for 5 seconds until dh1 appears Release the Manual...

Страница 21: ...he set point press and hold the info button and the stand by button at the same time ScL will appear See image 1 B Push the up button until dFt appears See image 2 C Press and hold the info button to...

Страница 22: ...www truemfg com True Food Service Equipment Inc 20 20 DISPLAY...

Страница 23: ...228 DDY OS2 X 1 8 75 167 1 925 FID T3 80 176 1 669 FDD X 32 1 8 OS3 X 1 8 85 185 1 452 FTO TLD 90 194 1 268 FCM SIM 95 203 1 145 FDT X 1 8 ADR 100 212 0 974 FDH X 1 8 105 221 0 858 FT1 110 230 0 758...

Страница 24: ...r housing along the interior ceiling Shelf Clip Shelf Shelf T Series GDM 5 Airflow Guard Pillaster WARNING Do not use pliers or any crimping tools when installing shelf clips Altering shelf clips in a...

Страница 25: ...23F WARNING High usage high temperature and high humidity may require additional defrost settings per day Once clock is set grill is correctly reinstalled cabinet can be plugged in T 19F T 19FZ T 23F...

Страница 26: ...ssary to warm up the set points To make the adjustment insert the appropriate tool in each adjustment screw and turn 1 4 of a revolution clockwise to the right This procedure will adjust both the cut...

Страница 27: ...ually increase to infinity b If there is no movement of the ohmmeter indicator an open circuit is indicated c If the ohmmeter indicator moves to zero and remains there or on a low resistance reading a...

Страница 28: ...the nameplate rating may indicate a broken suction reed or broken connecting rod in the compressor DIAGNOSIS AND REPLACEMENT OF FREEZER CABINET COMPONENTS 1 Defrost Time Clock A Check timer motor to b...

Страница 29: ...rubber gasket and push rubber over the top lip of the lamp shield STEP 3 Be sure lamp cover is seated properly in rubber gasket IMPORTANT Before replacing light cover turn cabinet on and wait until i...

Страница 30: ...anchoring compressor assembly to frame rails and carefully slide out tube connections are flexible Step 4 Clean off accumulated dirt from the condenser coil and the fan with a stiff bristle brush Step...

Страница 31: ...abinet grill to expose the Condenser The Condenser looks like a group of vertical fins You need to be able to see through the condenser for the unit to function at maximum capacity Do not place filter...

Страница 32: ...plastic scouring pad or soft cloth when you cannot see the grain 3 Use alkaline alkaline chlorinated or non chloride containing cleaners While many traditional cleaners are loaded with chlorides the...

Страница 33: ...ituations environments of stainless steel A Soap ammonia and detergent medallion applied with a cloth or sponge can be used for routine cleaning B Arcal 20 Lac O Nu Ecoshine applied provides barrier f...

Страница 34: ...must also be the same capacity as the drier being replaced 3 Micron level vacuums must be achieved to insure low moisture levels in the system 500 microns or lower must be obtained All claims for labo...

Отзывы: