background image

4

TRUE

SPEC SERIES®: STR, STA & STG, ROLL-IN AND ROLL-THROUGH

www

.

truemfg

.

com

4

230 Volts             Distance In Feet To Center of Load

  Amps  20 30 40  50  60 70  80 90 100 120 140 160

 

14 14  14  14  14 14  14 14  14 14  14  14

 

14 14  14  14  14 14  14 14  14 14  14  12

 

14 14  14  14  14 14  14 14  14 14  12  12

 

14 14  14  14  14 14  14 14  14 12  12  12

 

14 14  14  14  14 14  14 14  12 12  12  10

 

10 

14 14  14  14  14 14  14 12  12 12  10  10

 

12 

14 14  14  14  14 14  12 12  12 10  10  10

 

14 

14 14  14  14  14 12  12 12  10 10  10  8

 

16 

14 14  14  14  12 12  12 10  10 10  8  8

  18 

14 14 14 12 12 12 10 10 10 8  8  8

  20 

14 14 14 12 10 10 10 10 10 8  8  8

 

25 

14 14  12  12  10 10  10 10  8  8  6  6

 

30 

14 12  12  10  10 10  8  8  8  6  6  6

  35 

14 12 10 10 10 8  8  8  8  6  6  5

  40 

14 12 10 10 8 8  8 6  6 6  5  5

  50 

12 10 10 8  6 6  6 6  6 5  4  4

  60  12 

10 8 6 6 6 6 6 5 4 4 3

  70  10 

10 8 6 6 6 5 5 4 4 2 2

  80  10 8 8 6 6 5 5 4 4 3 2 2

  90  10 8 6 6 5 5 4 4 3 3 1 1

  100  10 8 6 6 5 4 4 3 3 2 1 1

115 Volt s            Distance In Feet To Center of Load

  Amps  20 30 40  50  60 70  80 90 100 120 140 160

 

14 14  14  14  14 14  14 14  14 14  14  14

 

14 14  14  14  14 14  14 14  14 14  14  12

 

14 14  14  14  14 14  14 14  14 12  12  12

 

14 14  14  14  14 14  14 12  12 12  10  10

 

14 14  14  14  14 14  12 12  12 10  10  10

 

14 14  14  14  14 12  12 12  10 10  10  8

 

14 14  14  14  12 12  12 10  10 10  8  8

 

14 14 14 12 12 12 10 10 10 8  8  8

  10 

14 14 14 12 12 10 10 10 10 8  8  8

  12 

14 14 12 12 10 10 10 8  8  8  8  6

  14 

14 14 12 10 10 10 8 8  8 6  6  6

  16 

14 12 12 10 10 8  8  8  8  6  6  6

  18 

14 12 10 10 8 8  8 8  8 8  8  5

  20 

14 12 10 10 8 8  8 6  6 6  5  5

  25 

12 10 10 8  8 6  6 6  6 5  4  4

  30  12 

10 8 8 6 6 6 6 5 4 4 3

  35  10 

10 8 6 6 6 5 5 4 4 3 2

  40  10 8 8 6 6 5 5 4 4 3 2 2

  45  10 8 6 6 6 5 4 4 3 3 2 1

  50  10 8 6 6 5 4 4 3 3 2 1 1

HOW TO CONNECT ELECTRICITY

Do not, under any circumstances, cut or remove the ground prong 
from the power cord. For personal safety, this appliance must be 
properly grounded.

The power cord of this appliance is equipped with a grounding plug 
which mates with a standard grounding wall outlet to minimize the 
possibility of electric shock hazard from this appliance.  Have the 
wall outlet and circuit checked by a qualified electrician to make sure 
the outlet is properly grounded.  If the outlet is a standard 2-prong 
outlet, it is your personal responsibility and obligation to have it replaced 
with the properly grounded wall outlet.  The unit should always be 
plugged into its own individual electrical circuit, which has a voltage 
rating that matches the rating plate.  This provides the best perfor-
mance and also prevents overloading building wiring circuits which 
could cause a fire hazard from overheated wires.  Never unplug your 
unit by pulling on the power cord. Always grip plug firmly and pull 
straight out from the outlet.  Repair or replace immediately all power 
cords that have become frayed or otherwise damaged.  Do not use 
a cord that shows cracks or abrasion damage along its length or at 
either end.  When removing the unit away from the wall, be careful 
not to roll over or damage the power cord.

ELECTRIC INSTALLATION & SAFETY 

INFORMATION

•   If the supply cord is damaged, it must be replaced by a special 

cord or assembly available from the manufacturer or its service 
agent.

•   Lamps must be replaced by identical lamps only.
•   Appliance tested according to the climate classes 5 and 7 

temperature and relative humidity.

ELECTRICAL INSTRUCTIONS

A.  Before your new unit is connected to a power supply, check the 

incoming voltage with a voltmeter. If anything less than 100% of 
the rated voltage for operation is noted, correct immediately.

B.  All units are equipped with a service cord, and must be 

powered at proper operating voltage at all times. Refer to 
cabinet data plate for this voltage.

TRUE RECOMMENDS THAT A SOLE USE CIRCUIT BE 
DEDICATED FOR THE UNIT.
WARNING:

 Compressor warranties are void if compressor burns 

out due to low voltage. 

WARNING:

 Power supply cord ground should not be removed!

WARNING: 

Do not use electrical appliances inside the food 

storage compartments of the appliances unless they are of the type 
recommended by the manufacturer.

NOTE:

  To reference wiring diagram, remove front louvered grill, 

wiring diagram is positioned on the inside cabinet wall.

WIRE GAUGE CHART

Содержание SPEC ROLL-IN Series

Страница 1: ...SERIES STR STA STG ROLL IN AND ROLL THROUGH TABLE OF CONTENTS SAFETY INFORMATION Safety Precautions 1 Proper Disposal Connecting Electricity Adapter Plugs 2 INSTALLATION Ownership Uncrating 3 How to C...

Страница 2: ...Risk of fire or explosion Dispose of properly in accordance with federal or local regulations Flammable refrigerant used CAUTION Risk of fire or explosion due to puncture of refrigerant tubing follow...

Страница 3: ...IANCE MUST BE PROPERLY GROUNDED The power cord from this appliance is equipped with a grounding plug which minimizes the possibility of electric shock hazard Have the wall outlet and circuit checked b...

Страница 4: ...responsible for damage incurred during shipment UNCRATING TOOLS REQUIRED Adjustable Wrench 1 2 inch socket Castor Bolts 3 4 inch socket Skid Bolts Level The following procedure is recommended for uncr...

Страница 5: ...ity of electric shock hazard from this appliance Have the wall outlet and circuit checked by a qualified electrician to make sure the outlet is properly grounded If the outlet is a standard 2 prong ou...

Страница 6: ...TRUE WILL NOT WARRANTY ANY UNITS THAT ARE CONNECTED TO AN EXTENSION CORD Removing shipping bolts SEALING CABINET TO FLOOR STEP 1 Position Cabinet Allow one inch between the wall and rear of the refri...

Страница 7: ...me contact with the ramp when the door is closing This can be checked by opening up the door 3 4 and allowing the door to close This process may have to be done several times before securing the sweep...

Страница 8: ...STEP 3 The hinge on the cabinet door can also be adjusted Remove cover from hinge located on the door Pull on the cover directly out from the door See image 3 This exposes the three Phillips screws a...

Страница 9: ...four inches of the evaporator housing Refrigerated air off the coil must circulate down the back wall NOTE If the unit is disconnected or shut off wait five minutes before starting again RECOMMENDATI...

Страница 10: ...may reflect the refrigeration cycle swings of up and down temperatures The most accurate temperature on a cabinet s operation is to verify the product temperature 4 There is not a defrost timer as th...

Страница 11: ...ether a The temperature control is sensing the air temperature b The temperature control should be set on the 4 or 5 c The warmest setting is 1 the coldest is 9 and 0 is the off position d The thermom...

Страница 12: ...ore than 3 4 turn After making adjustment measure temperature during three cycles before adjusting again NOTE Only adjust the screw small flathead on the face of the control next to the cam See Figure...

Страница 13: ...ontrol Take note as to which wire is on which spade terminal STEP 4 Pull out gently from cabinet NOTE Mechanical temperature controllers are affected when functioning at high altitude The cut in and c...

Страница 14: ...D ROLL THROUGH www truemfg com 13 O 9 8 7 6 5 4 3 2 1 2 O 9 8 7 5 4 3 2 1 CUT OUT CUT IN COLDER BUL NO CHART CCW Adjustment based on 360 complete turn Height 2000 42 3000 78 4000 114 5000 150 6000 186...

Страница 15: ...DEFROST TIME CLOCK OPERATION FOR UNITS WITH MECHANICAL CONTROL RECOMMENDED DEFROST SETTINGS TRUE Manufacturing has factory set your defrost time clock to a recommended time and duration defrost scena...

Страница 16: ...not a product temperature This cabinet temperature may reflect the refrigeration cycle of the Set Point and its Differential or it may show an average temperature The most accurate temperature on a ca...

Страница 17: ...the lock setting has been set correctly release the info button Wait 5 seconds for the display to show temperature See image 5 USING THE LAE ELECTRONIC CONTROL LOCKING AND UNLOCKING THE LAE CONTROLLER...

Страница 18: ...control repeat prior steps and a temperature will appear ON Position TURNING THE GLASS DOOR MODEL LIGHTS ON AND OFF May need to unlock control WHY Light may be controlled by LAE Controller or interior...

Страница 19: ...olding temperature HOW TO CHANGE THE SET POINT STEP 1 To see the set point press and hold the Info button See image 1 STEP 2 While still holding the Info button press the Up or Down button to change t...

Страница 20: ...er REGULAR TIME DEFROST TIM If controller is preprogrammed for TIM press and release the Manual Defrost button until dEF appears REAL TIME CLOCK RTC If controller is preprogrammed for RTC press the an...

Страница 21: ...e same time NOTE Depending on the version of control one of three parameters will appear ScL image 1a SPL image 1b MdL image 1c STEP 2 Push the Up button until dFt appears See image 2 STEP 3 Press and...

Страница 22: ...lication HOW TO CHANGE DISPLAY READOUT FROM FAHRENHEIT TO CELSIUS STEP 1 To change the display press and hold the Info button and the Stand by button at the same time MdL or SPL will appear See images...

Страница 23: ...ature of the T3 probe If probe T3 is not activated t3 will not appear of the display DISPLAYING TEMPERATURE PROBES T1 T2 T3 WHY To display temperature probe readings in different locations of the cabi...

Страница 24: ...32 1 8 6 7 Celsius AR2 28 SCL 1C ADO SPL X 32 1 8 AHM SPH X 32 1 8 AHT X 32 1 8 SP X 32 1 8 ACC C H IISM HYS X 1 8 IISL X 32 1 8 CRT IISH X 32 1 8 CT1 IISP X 32 1 8 CT2 IIHY X 1 8 CSD IIFC DFM HDS DFT...

Страница 25: ...P 3 Clean off accumulated dirt from the condenser coil and the fan with a stiff bristle brush After brushing the components off vacuum all dirt residue from the coil fan and surrounding areas See imag...

Страница 26: ...ft open the cabinet rainshield to expose the Condenser Spec Series models The Condenser looks like a group of vertical fins You need to be able to see through the condenser for the unit to function at...

Страница 27: ...N HELP PREVENT RUST ON STAINLESS STEEL 1 USING THE CORRECT CLEANING TOOLS Use non abrasive tools when cleaning your stainless steel products The stainless steel s passive layer will not be harmed by s...

Страница 28: ...ke sure power to the unit is either turned off or unplugged Be careful when removing the light bulb Please be aware of your local ordinances in disposing old bulbs These bulbs should be disposed in a...

Страница 29: ...3 Micron level vacuums must be achieved to insure low moisture levels in the system 500 microns or lower must be obtained All claims for labor or parts must be made directly through TRUE All claims sh...

Отзывы: