Connections
Inspection windows
Panels
Before initial commissioning:
Remove protective film, if any
Check the unit for leakages
Check inspection access doors and openings for
function
Insert the filters,
‘Filters, inserting’ on page 55
Set up the heating coil/cooling coil,
sioning the heating coil/cooling coil’ on page 56
Set up the sound attenuator,
Set up the rotary heat exchanger,
rotary heat exchanger’ on page 59
Set up the run around coil system,
sioning the run around coil system’ on page 57
Set up the plate heat exchanger,
plate heat exchanger’ on page 60
Remove the protective caps from the condensate
drains and connect the drain trap,
‘Connecting the condensate drain’ on page 34
Clean the air handling unit,
Ä
Operating manual,
Maintenance.
6.3 Setting up and adjusting AHU
casing units
6.3.1
Centrifugal fan
Operating point
The control system calculates the operating point and
sets the default setpoint value for the fan.
During commissioning ensure that the following values
are not exceeded:
Maximum fan speed
Minimum fan speed
Motor rating
Do not change the clearance between the rotor and the
bellmouth inlet.
Pressure measuring devices
Fig. 63: Pressure measurement point
1
Bellmouth inlet
2
Partitioning panel
M1 Pressure measurement point in the fan chamber
M2 Pressure measurement point on the bellmouth inlet
M3 Pressure measurement point in front of the parti-
tioning panel
The fans may be factory fitted with pressure measuring
devices (optional). The following pressure values are
measured at the pressure measurement point
( Fig. 63 /M2) in the bellmouth inlet ( Fig. 63 /1), the
pressure measurement point ( Fig. 63 /M1) in the fan
chamber, and the pressure measurement point
( Fig. 63 /M3) in front of the partitioning panel.
Pressure
Determined from
Static fan pressure
increase
Differential pressure
between M1 and M3
Effective pressure (
D
p
w
)
of the fan
The differential pressure
between M2 and M3 is
used to calculate the
volume flow rate.
Calculation of the volume flow rate
The K value is given on the TROX fan rating plate on
the air handling unit.
This value may be different from the K value on the
rating plate from the fan manufacturer (which should not
be used for the calculation).
Initial commissioning
Setting up and adjusting AHU casing units > Centrifugal fan
Air handling unit X-CUBE X2 / X-CUBE X2 compact
53