5.5 Operation on a timer
The unit can be operated on a timer, but the power con-
sumption of the unit must be taken into account,
Chapter 8 ‘Technical data’ on page 21
tings of the unit are retained even when the supply
voltage is disconnected. The daily checks on the appli-
ance must be carried out.
5.6 Adapting the air change rate
The volume flow rate (air change rate) is programmed in
the factory to the specified room size. If it is necessary
to adjust the volume flow rate, this can be set on the
controller in the
‘Setpoint 1’
menu item as described
below.
In addition, the limit value for the filter change must be
set to the changed volume flow rate,
‘Level Max.’
menu
item.
Pulsation of the fan
The fan can pulsate when the door is open. As soon
as the door is closed, the fan runs properly again.
Fig. 13: TAP controller
Display
500 m³/h
- 1st line = Actual values and set-
point values
Setpoint 1
- 2nd line = Menu item
Function of keys
P
- Programming key and open menu
▼
- Menu selection, reduce value
▲
- Menu selection, increase value
▼ + ▲ - Esc key combination,
Escape = Exit menu
Setting the volume flow rate
1.
Press the
[▼]
[▲]
keys at the same time until
‘INFO’
appears.
2.
Press the
[▼]
key until
‘SETTING’
appears.
3.
Press the
[P]
key
ð
Setpoint 1 appears
4.
Press the
[P]
key again to activate setting mode.
ð
Setting value flashes
5.
Use the
[▼]
or
[▲]
key to set the desired value
[m³/h], setting range TAP-L: 400...1600 m³/h, TAP-
M: 200...1200 m³/h.
6.
Press the
[P]
key to accept the value.
Setting temperature limit for filter change
7.
Press the
[▼]
[▲]
keys at the same time.
ð
‘SETTING’
appears
8.
Press the
[▼]
key until
‘LIMITS’
appears.
9.
Press the
[P]
key
ð
‘Level Function’
appears
10.
Press the
[▼]
key until
‘Level Max.’
appears.
11.
Press the
[P]
key to activate setting mode.
ð
Setting value flashes
12.
Set the value using the
[▼]
or
[▲]
key according
to the table. Intermediate values can be interpo-
lated.
Volume flow
rate [m³/h]
Level max. [V]
TAP -L
TAP-M
200
–
4.1
400
4.1
5.3
600
4.9
6.5
800
5.8
7.7
1000
6.7
9.0
1200
7.6
10.0
1400
8.4
–
1600
9.3
–
13.
Press the
[P]
key to accept the value.
14.
Press the
[▼]
[▲]
keys at the same time.
ð
‘Limits’
appears
15.
Press the
[▼]
key until
‘Info’
appears.
16.
Press the
[P]
key to exit the settings menu.
ð
Volume flow rate and limit value for filter
change set to new values.
Software use
Adapting the air change rate
TROX AIR PURIFIERS TAP-L
TAP-M
17