Parts and function

Smoke control dampers are used in mechanical smoke

extract systems. They are used for extracting smoke

gases and for providing additional supply air to one or

more fire compartments.

Smoke control dampers are made from calcium silicate

boards, and the electric actuator and the optional con-

trol module are encased so that the functional reliability

is ensured even in the event of a fire.

Regular maintenance of the smoke control damper is

required to ensure its functional reliability 

Ä

 9  ‘Mainte-

nance’ on page 31

.

Fig. 3: EK-EU smoke control damper

Casing

Damper blade

Travel stop

Inspection access (optional)

Rating plate

Cover of the actuator encasing (sectional view)

Actuator

Control module AS-EM or AS-EM/SIL2 (optional)

Connecting subframe (optional)

Smoke extract

Fig. 4: Smoke extract system

EK-EU in a solid shaft wall

EK-EU in a solid wall and a duct

EK-JZ on a vertical solid shaft wall

On a vertical smoke extract duct (shaft)

On a horizontal smoke extract duct

In a horizontal smoke extract duct

At the end of a horizontal smoke extract duct

EK-EU as additional supply air inlet

Cover grilles

During normal operation Type EK-EU smoke control

dampers remain closed. For smoke extract, the smoke

control dampers in the affected fire compartment open

so that smoke can be extracted. All other smoke control

dampers remain closed.

In the event of a fire, smoke control dampers that are

used as additional supply air inlets in the affected fire

compartment also open so that smoke can be extracted.

To ensure the creation of a layer that is nearly free from

smoke, smoke control dampers used as additional

supply air inlets should be installed near the ground.

The control input signal for the actuator may come from

a duct smoke detector or from the central fire alarm

system. Using cables with specific circuit integrity for the

supply voltage ensures that the actuator is supplied with

voltage even in the event of a fire and hence that its

function and the communication are maintained.

Supply air and smoke extraction in ventilation sys-

tems

When authorised by building authorities or authorised

bodies, smoke extract and supply air applications as

well as ventilation can be enabled in combined systems

with smoke control dampers. Depending on the system

layout, the damper blade can be fully opened, fully

closed or in the intermediate position. Depending on

where the dampers are installed, country-specific regu-

lations may apply to ventilation applications.

Parts and function

 

 

Smoke control damper Type EK-EU

11

Содержание EK-EU

Страница 1: ...Smoke control damper Type EK EU Installation and operating manual Read the instructions prior to performing any task according to EN12101 8 Declaration of Performance DoP EK EU 002 GB en...

Страница 2: ...e original Valid from 01 2017 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Germany Phone 49 0 2845 2020 Fax 49 0 2845 202 265 E mail trox trox de Internet http www troxtechnik com 04 2...

Страница 3: ...shing content Copying content Translating content Microcopying content Saving content to electronic systems and editing it TROX Technical Service To ensure that your request is processed as quickly as...

Страница 4: ...not avoided may result in property damage ENVIRONMENT Environmental pollution hazard Tips and recommendations Useful tips and recommendations as well as informa tion for efficient and fault free oper...

Страница 5: ...solid ceiling slabs 17 5 5 1 Mortar based installation 17 5 6 Fire resistant smoke extract ducts 19 5 6 1 In horizontal or vertical smoke extract ducts 19 5 6 2 Leading from vertical smoke extract du...

Страница 6: ...se in accordance with a fire protection concept that is based on the protection goal can authorise further installation options in air conditioning and ventilation systems also Incorrect use WARNING D...

Страница 7: ...ampers EN 13501 4 Fire classification of construction products and building elements Fire resistance tests on compo nents of smoke control EN 1751 Ventilation for buildings Air terminal devices Declar...

Страница 8: ...00 750 800 L mm 600 800 200 39 42 45 48 50 53 56 59 62 79 83 86 90 250 42 45 48 51 54 57 60 63 66 84 87 91 95 300 45 48 51 54 57 60 63 66 69 88 92 96 100 350 48 51 54 57 60 63 67 70 73 93 97 101 105 4...

Страница 9: ...89 1300 101 107 112 117 123 128 133 139 144 180 186 192 198 1400 107 113 118 124 129 135 140 146 151 189 196 202 208 1500 113 118 124 130 136 141 147 153 159 199 205 212 218 2 3 Open Close actuators O...

Страница 10: ...ible take the product in its transport packaging up to the installation location Transport protection devices The EK EU is delivered with cardboard transport protec tion that stabilises the casing dur...

Страница 11: ...dampers remain closed For smoke extract the smoke control dampers in the affected fire compartment open so that smoke can be extracted All other smoke control dampers remain closed In the event of a f...

Страница 12: ...of the smoke control damper Install the smoke control damper without torsion horizontal vertical Mortar based installation The perimeter gap s must be large enough so that mortar can be filled in even...

Страница 13: ...n both sides of the damper installation and operating side Insert screws both from the top damper and from the bottom damper do not insert all screws in one line but pre drill in an offset pattern Fig...

Страница 14: ...t the bottom Be sure to attach the boards to each other and also to attach them to the brick structure To do so use glue or screws Fig 9 3 screws should be at 200 mm from each other Boards Thickness m...

Страница 15: ...nt sleeve joints between the damper and the duct in the wall the damper can alternatively be placed outside the wall in the flow of the approved smoke extract duct 5 6 Fire resistant smoke extract duc...

Страница 16: ...t be closed off with mortar Entrapped air is to be avoided Connect the smoke extract duct to the EK EU 27 Follow the manufacturer s instructions here also Installation Supporting construction solid wa...

Страница 17: ...f actuator casing under ceiling slab Fig 11 2 with casing length L 800 mm For ceiling thickness 150 mm casing length L 800 mm The connection of a fire resistant smoke extract duct above the ceiling is...

Страница 18: ...dry wall screws pre drill holes with 3 mm 150 mm distance between screws Connect the smoke extract duct to the EK EU 27 Follow the manufacturer s instructions here also Installation while constructing...

Страница 19: ...sted to EN 1366 8 gross density 500 kg m wall thickness 35 mm or equivalent e g Promat type AD40 or L500 d 40 mm 1 Insert smoke control damper into the fire resistant smoke extract duct and suspend it...

Страница 20: ...smoke extract ducts with a solid design shaft Here installation is in the wall as per 5 4 Supporting construction solid walls on page 15 Personnel Specialist personnel Materials For angle section str...

Страница 21: ...angle sections at the joints at the smoke extract duct and the smoke control damper then link the sections with steel staples distance 150 mm Connect the smoke extract duct to the EK EU 27 Follow the...

Страница 22: ...g Promat type AD40 or L500 d 40 mm Glue e g Promat K84 or equivalent Steel staples 63 11 2 1 53 mm Requirements Smoke extract duct fire resistant tested to EN 1366 8 gross density 500 kg m wall thick...

Страница 23: ...the angle sections at the joints at the smoke extract duct and the smoke control damper then link the sections with steel staples distance 150 mm Connect the smoke extract duct to the EK EU 27 Follow...

Страница 24: ...board d 35 mm or equivalent Angle section by others Dry wall screws 4 100 mm Steel staples by others Personnel Specialist personnel Materials For angle section strips of fire rated PROMATECT LS board...

Страница 25: ...a fire resistant smoke extract duct underneath the smoke control damper according to the manufacturer s instructions 4 Connect the fire resistant smoke extract duct to the smoke control damper by plac...

Страница 26: ...rod 22 35 52 70 96 150 5 7 2 Fixing to the ceiling slab Fig 16 Fixing to the ceiling slab 1 Fire rated anchor with suitability certificate 2 Push through installation Use only fire rated steel anchors...

Страница 27: ...lity of the smoke control damper is not affected connection according to assembly and operating manual of the smoke control damper The sizing of the smoke extract duct used remains the responsibility...

Страница 28: ...Cover grilles If no smoke extract duct is connected to the smoke con trol damper a cover grille galvanised steel mesh aper ture 20 mm may be fixed instead to protect that side of the damper 6 3 Inspe...

Страница 29: ...everal actuators can be connected in parallel as long as the performance specifications are taken into consideration Actuators with 24 V AC DC Safety transformers must be used The connecting cables ar...

Страница 30: ...tion Position indicator OPEN position Socket for the crank handle Requirement The smoke control damper is closed 1 Insert the crank handle into the socket Fig 22 4 the crank handle is clip fixed to th...

Страница 31: ...ng on where dampers are installed country specific regulations may apply Maintenance The smoke control damper and the actuator are mainte nance free with regard to wear but smoke control dampers must...

Страница 32: ...damage Smoke control damper damper blade and seal must be intact Repair or replace the smoke control damper Specialist personnel Functional test of the smoke control damper 8 2 Functional test on page...

Страница 33: ...ply before working on any electrical equipment 1 Disconnect the wiring 2 Remove the smoke extract ducts 3 Close the smoke control damper 4 Remove the smoke control damper Disposal ENVIRONMENT Risk of...

Страница 34: ...stant smoke extract duct 19 20 22 24 Functional test 30 H Hotline 3 I Inspection 31 32 Inspection access 28 Installation position 12 Installation situations 12 L Limitation of liability 3 M Maintenanc...

Страница 35: ...Smoke control damper Type EK EU 35...

Страница 36: ...Valid from 01 2017 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Ger many Germany Phone 49 0 2845 2020 49 0 2845 202 265 E mail trox trox de http www troxtechnik com...

Отзывы: