background image

TX-RKS1

 

8

TX-RKS1 SPECIFICATIONS

AURASAFE mini damper module for

smoke control dampers (ventilated system)

Technical data

Inputs

2 Digital kontakt

Outputs

Open:  24 VDC, max. 15 VA
Closed: 24 VDC, max. 15 VA

Addressing

DIP-switch

Indicator

LED on the side

Terminals

Springclamps, max. 2,5 mm

2

Dimensions

85x85x40 mm

WIRING TERMINALS

A.  Damper input, Normal-Closed(NC)

B.  Damper input, Normal-Open(NO)

C.  Supply to damper actuator

D.  Supply/Bus input

 

 

2-wire bus supply. Two extra terminal-pairs 

 

 

for forwarding.

E.  Addressing DIP-switch

 

 

See separate description for addressing.

F.  Test-button for Manual test

 

 

See separate description.

G.  Cable fixation

H.  LED indicator

 

 

See separate description for indicator.

Output C

Input A

Input B

LED indicators

0

0

0

Blue, blinking slowly

0

0

1

Blue (damper closed)

0

1

0

Blue, blinking rapidly

0

1

1

Red, blinking rapidly

1

0

0

Green, blinking slowly

1

0

1

Green, blinking rapidly

1

1

0

Green (damper open)

1

1

1

Red, blinking slowly

ADDRESSING

The damper module is assigned an address via the DIP switches.

The modules are assigned a consecutive address between 0 - 99. It

is not necessary for the modules to be placed in order during

assembly.

Each of the 7 switches represents a value, as indicated on the right.

The sum of the activated switches gives the module address. As

Example 1 shows, switches 1, 3 and 6 are activated. They each count

for 1 + 4 + 32, ie the module’s address becomes 37.

The same address must not be given to more than one damper.

MANUELL TEST

As a part of installation and service, it is possible to perform a test

cycle directly on a simple damper module. The test button is held

down for approx. 5 seconds until the LED switches to fast flashing,

then release the test button. A test cycle will now start, where the

dampers open for approx. 180 seconds and then closes for 90

seconds.

Value:

Example 2: 

 

Address:

2 + 8 + 16 + 64 = 90

Example 1: 

 

Address:

1 + 4 + 32 = 37

Содержание Auranor AURASAFE mini

Страница 1: ...rs up to 100 fire dampers Digital error signal Connection to BMS by Modbus GB0351 02 22 AURASAFE mini Monitoring and control of fire dampers TROX Auranor Norge AS Auranorvegen 6 NO 2770 Jaren Phone 47...

Страница 2: ...fe Mini 1 TX CTRL1 Controller std 12 Dampers 2 TX CTRL2 Controller lite 8 Dampers 3 TX BO1 Boostermodule 4 TX BRS3 Dampermodule for fire and smoke dampers 5 TX RKS1 Dampermodule for smoke control damp...

Страница 3: ...and booster modules must have a 230V supply Figure 3 You can use the TX DREL1 Relay module to distribute the relay output of the AHU to 4 units TX INP1 Input module is used if smoke detector or fire...

Страница 4: ...wire bus for supply and communication with bus modules E Alarm relay output F Smoke fan ventilated system relay output G Service relay output Indicates if service is required for smoke detectors H Ve...

Страница 5: ...re bus for supply and communication with bus modules E Alarm relay output F Smoke fan ventilated system relay output G Service relay output Indicates if service is required for smoke detectors H Venti...

Страница 6: ...Supply B Supply Bus output for damper modules Extended 2 wire bus for supply and communication with dampers C Bus input 2 wire bus input from existing network D LED indicators See separate description...

Страница 7: ...1 Red blinking slowly ADDRESSING The damper module is assigned an address via the DIP switches The modules are assigned a consecutive address between 0 99 It is not necessary for the modules to be pla...

Страница 8: ...1 0 0 Green blinking slowly 1 0 1 Green blinking rapidly 1 1 0 Green damper open 1 1 1 Red blinking slowly ADDRESSING The damper module is assigned an address via the DIP switches The modules are assi...

Страница 9: ...linking slowly Reset smoke detector Blue blinking slowly Service detector Red blinking slowly Alarm ADDRESSING The module is assigned an address via the DIP switches It is not necessary for the module...

Страница 10: ...to turn off acoustic alarm C 24 VDC supply Bus input LED indicators Status Yellow Ventilation fault alarm ADDRESSING Fault panel does not need to be given an adress fixed address 127 FUNCTION In case...

Страница 11: ...ly PT1000 short circuited Red blinking slowly Alarm temperature or missing PT1000 ADDRESSING The damper module is assigned an address via the DIP switches The modules are assigned a consecutive addres...

Страница 12: ...mps max 2 5 mm2 Dimensions 85x85x40 mm Temperature 0 50 C WIRING TERMINALS A 24 VDC input supply With 24VDC supply connected to all 4 relay outputs are activated extra terminal set for continuation of...

Отзывы: