Installation manual
Automatic exhaust valveType ATVC-100
Subject to change · All rights r
eserved ·
L-50-7-02e
Страница 1: ...Installation manual Automatic exhaust valve Type ATVC 100 Subject to change All rights reserved L 50 7 02e ...
Страница 2: ... 10 Maintenance and cleaning 10 1 General information This installation manual describes the automatic exhaust valve type ATVC 100 To ensure correct functioning of the automatic exhaust valve it is essential to read the provided installation manual before starting any work and to comply with it The manufacturer does not accept any liability for any malfunction or damage resulting from non complian...
Страница 3: ...t werden in Ex Bereichen im Freien ohne ausreichenden Schutz gegen Witterungseinflüsse in Atmosphären die planmässig oder ausserplan mässig aufgrund chemischer Reaktionen eine schädigende und oder Korrosion verursachende Wirkung auf das Produkt ausüben WARNUNG Verletzungsgefahr bei unzureichender Qualifikation Unsachgemässer Umgang kann zu erheblichen Personen und Sachschäden führen Alle Tätigkeit...
Страница 4: ...d duties understand any potential hazards related to the work under consideration and recognise and avoid any risks involved Limitation of liability The information in this manual has been compiled with refe rence to the applicable standards and guidelines the state of the art and our expertise and experience of many years The manufacturer does not accept any liability for damages resulting from N...
Страница 5: ...e transported to the installation location in their original packaging Use only lifting and transport gear designed for the required load Always secure the load against tipping and falling Cumbersome equipment should be transported with at least two people to prevent injury and damage Storage Please note Store the product only in its original packaging Protect the product from the effects of weath...
Страница 6: ... is closed the electro thermal drive heats up and causes the valve disc to open within 2 to 4 minutes delay during brief occupation of the room Air is exhausted through the opening between the valve housing and the valve disc The valve stroke 6 mm is always the same i e the valve disc always moves from the minimum setting to the maximum valve opening In the minimum setting the exhaust valve can ei...
Страница 7: ...at if the minimum setting is selected then the corre sponding operating volume curve must be taken into account Performance diagram Example as plotted Given Stat pressure drop ps 40 Pa Operating volume flow rate V 80 m3 h Solution Rotations for minimum setting 1 Basic volume flow rate Vo 10 m3 h Sound power level for Basic volume flow rate 25 dB A Operating volume flow rate approx 38 dB A 10 20 30...
Страница 8: ... on a table and loosen the brass knurled nut 5 by turning it one rotation in a clockwise direction Hold the exhaust valve at the electric drive as shown and using one finger of your free hand open the valve disc 2 by turning it the required number of rotations in an anticlockwise direction Place the exhaust valve on a firm base as shown e g a table hold it firmly with one hand against the base and...
Страница 9: ... diffusers are connected to just one volume flow controller it may be necessary to balance the volume flow rates 7 Electrical installation GEFAHR Stromschlag beim Berühren spannungsführender Teile Elektrische Ausrüstungen stehen unter gefährlicher elektrischer Spannung Nichtbeachtung kann Tod schwere Körperschäden oder Sachschaden verursachen An den elektrischen Komponenten dürfen nur Elektrofachk...
Страница 10: ...amination e g scrubbing sponges and scouring agents can damage the surface and is not permitted All technical components can be replaced if defective GEFAHR Stromschlag beim Berühren spannungsführender Teile Elektrische Ausrüstungen stehen unter gefährlicher elektrischer Spannung Nichtbeachtung kann Tod schwere Körperschäden oder Sachschaden verursachen An den elektrischen Komponenten dürfen nur E...