dehumidifier TTK 75 ECO

Activities required before starting maintenance

Warning of electrical voltage

Do not touch the mains plug with wet or damp hands.

Switch the device off.

Hold onto the mains plug while pulling the power cable out
of the mains socket.

Warning of electrical voltage
Tasks which require the device to be opened must
only be carried out by authorised specialist
companies or by Trotec.

Refrigerant circuit

Danger
Natural refrigerant propane (R290)!

H220 – Extremely flammable gas.
H280 – Contains gas under pressure; may explode if
heated.

P210 – Keep away from heat, sparks, open flames and
other ignition sources. No smoking.
P377 – Leaking gas fire: Do not extinguish, unless leak
can be stopped safely.
P410+P403 – Protect from sunlight. Store in a well-
ventilated place.

The entire refrigerant circuit is a maintenance-free,
hermetically sealed system and may only be maintained or
repaired by specialist companies for cooling and air-
conditioning or by Trotec.

Safety signs and labels on the device

Check the safety signs and labels attached to the device at
regular intervals. Replace illegible safety signs!

Cleaning the housing

Clean the housing with a soft, damp and lint-free cloth. Make
sure that no moisture enters the housing. Protect electrical
components from moisture. Do not use any aggressive cleaning
agents such as cleaning sprays, solvents, alcohol-based or
abrasive cleaners to dampen the cloth.

Visual inspection of the inside of the device for dirt

1. Remove the air filter.
2. Use a torch to illuminate the openings of the device.
3. Check the inside of the device for dirt.

4. If you see a thick layer of dust, have the inside of the

device cleaned by a specialist company for cooling and 
air-conditioning or by Trotec.

5. Put the air filter back in.

Cleaning the air filter

Note

Ensure that the air filter is not worn or damaged. The
corners and edges of the air filter must not be
deformed or rounded. Before reinserting the air filter,
make sure that it is undamaged and dry!

The air filter has to be cleaned as soon as it is dirty. This is
brought to light e.g. by a reduced capacity (see chapter Errors
and faults).

1. Remove the air filter from the device.

Содержание TTK 75 ECO

Страница 1: ...TRT BA TTK75ECO TC220105TTRT01 005 EN TTK 75 ECO EN ORIGINAL INSTRUCTIONS DEHUMIDIFIER...

Страница 2: ...ting or using the device Always store the manual in the immediate vicinity of the device or its site of use Warning Read all safety warnings and all instructions Failure to follow the warnings and ins...

Страница 3: ...ce or an electric heater Please note that the refrigerant is odourless Only install the device in compliance with the national installation regulations Please observe the local regulations Observe the...

Страница 4: ...nufacturer s specifications and by persons having a certificate of qualification A corresponding repair manual is available from the manufacturer upon request Residual risks Danger Natural refrigerant...

Страница 5: ...nto the condensation tank below It is fitted with a float to measure the filling level Once the maximum filling level of the condensation tank is reached or in case the condensation tank is not instal...

Страница 6: ...sporting the device proceed as follows Set up the device in an upright position after transport Leave the device to rest for 12 to 24 hours so the refrigerant can accumulate within the compressor Wait...

Страница 7: ...ectric heater Only put up the device in an upright stable position on firm ground Do not create tripping hazards when laying the power cable or other electric cables especially when positioning the de...

Страница 8: ...r Assembly and start up you can switch it on Press the on off switch 2 The device starts to dehumidify in continuous operation Note Only use the device in an upright position otherwise the compressor...

Страница 9: ...redirects the hot gas to the evaporator and closes again after defrosting is completed so that drying operation can be continued via the regular refrigerant circuit Unlike air circulation defrosting...

Страница 10: ...operating range according to the technical data Ensure that the relative room humidity complies with the technical data Check the air filter for dirt If necessary clean or replace the air filter From...

Страница 11: ...nd or drain hose X Maintenance and care log Device type Device number Maintenance and care interval 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Check air inlets and outlets for dirt and foreign objects and...

Страница 12: ...d labels on the device Check the safety signs and labels attached to the device at regular intervals Replace illegible safety signs Cleaning the housing Clean the housing with a soft damp and lint fre...

Страница 13: ...lter into the device 4 Reinsert the air filter into the device Emptying the condensation tank If the condensation tank is full or not installed correctly the condensation tank indicator light 9 will b...

Страница 14: ...chnical annex Technical data Parameter Value Model TTK 75 ECO Max dehumidification performance 21 l 24 h Dehumidification performance 30 C and 80 RH 20 l 24 h Air flow rate 260 m3 h Operating range te...

Страница 15: ...LL red blue brown blue red white black brown blue blue VALVE FAN LAMP 3 4 N control chip N L fan comp R S C calculagraph water full lamp 2 way valve water full switch defrosting sensor blue blue brown...

Страница 16: ...charge Tube 4 Three Exit Tube II 17 Discharge Tube II 30 Three Exit Tube 5 Three Exit Tube 18 Defrost Tube 31 Bypass Valve 6 Gas In Tube 19 Air Baffle 32 Right Faceplate 7 Filter 20 Fan Wheel 33 Compr...

Страница 17: ...e national regulations by a company with the relevant certification European Waste Catalogue 160504 Declaration of conformity Declaration of conformity in accordance with the EC Machinery Directive 20...

Страница 18: ...Trotec GmbH Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com...

Отзывы: