Wiring the supply:

The T6 MCU requires a 115VAC supply. It is good practice for the supply to
be fused. Connect the supply to the two terminals marked “115VAC” on
output side of unit, as shown below.

Wiring the outputs:

Each output consists of a normally open relay contact that can switch up to
5 amps at 230vac. These contacts share a common terminal marked “COM”.
If the loads are the same voltage as the supply, install a jumper to the “Hot”
side of the 115vac as shown below. If the loads require a different voltage
than the supply, connect the common terminal of the outputs to a power
supply suitable for the load devices.

Noise transients, caused when an inductive load is de-energized, may cause
erratic behavior of electronic equipment as well as greatly shorten the life of
relay contacts. The use of a load suppressor, is recommended ( see the
Optional Equipment booklet ). Below is a typical 115vac load configuration.

black

LOADS

(115 vac)

115 vac

(“Hot”)

Common

(“Cold”)

white

5amp Fuse

black

Wiring the Inputs:

The inputs of the T6 are self-powered and optically isolated to offer high
noise immunity. The input voltage is +12vdc, which allows the inputs to
interface to a wide variety of switches and sensors. The device wired to the
input must be able to carry a minimum current of 10 milliampere. Input
devices are wired between the input number and either of the two common
terminals on the input side of the unit. This is illustrated below.

Warning!

The inputs are self-powered and can be damaged if connected

to an outside power source! Use a converter block ( see the Optional
Equipment booklet ) if the input device is not of a dry contact or of a
sinking configuration as required.

Electromechanical

devices such as mag-

netic reed switches, limit switches, push but-
ton switches and pressure switches are wired
with no regard to polarity ( positive/negative ).

Electronic

devices such as magnetic hall ef-

fect transistors, photo-transistors, and DC
proximity sensors must meet the following cri-
teria:

-

It must be of an open collector NPN ( like

symbol in illustration ). This is often referred
to as being in a sinking configuration.

-

It cannot have an off current ( leakage )

greater than .5 ma ( .005 amp ).

-

It must NOT be of a PNP or sourcing con-

figuration.

Note on three wire sensors:

The Auxiliary DC power supply terminal can

be used to support sensors that require up to 100ma of current. If more
current is needed, an external DC power supply is required ( see optional
equipment manual ). The Auxiliary supply measures between 10-14 volts,
which is suitable for most 3 wire proximity sensors.

switch

3wire prox.

sensor

POS

OUT

NEG

Note:

An MCU-04 can be used as a direct replacement of a MCU-01 to

MCU-03 controller. It has an additional Auxiliary power supply terminal.

Note:

The T6 Optional equipment manual is available on-line at

www.trolsystems.com. In the literature index choose to download the T6
Optional Equipment booklet.