WARNING!

THIS APPLIANCE MUST BE EARTHED

Meter

Incoming

supply

fuse

Meter

tails

Consumer

unit

Pull cord

isolating switch

Shower

unit

Fuse or

MCB

RCD

(can be part of

consumer unit)

80A or 100A

main switch

Table A

MCB

30/32A

32A
40A
40A
40A

40/45A

45A

cartridge

fuse

30A
35A
35A
45A
45A
45A
45A

unit 

rating

7.0kW
7.5kW
8.0kW
8.5kW
9.0kW
9.5kW

10.5kW

CIRCUIT PROTECTION

Fig.4

 Schematic of installation circuit

ELECTRICAL REQUIREMENTS

The installation, supply cable and circuit 

protection must conform with BS 7671 (IEE 

wiring regulations) and be sufficient for the 

amperage required.

The following notes are for guidance only:
1

 

The shower must only be connected to a 

230-240V ac supply. If you are installing a

shower with a kilowatt rating above 9kW, it

is advisable to contact the local electricity

supply company.

1.1

  The electrical rating of the shower is shown 

2

 

on the rating label 

(Fig.3)

 within the unit.

Before making any sort of electrical 

connection within the installation make 

sure that no terminal is live. If in any doubt, 

switch off the whole installation at the mains 

supply and remove the correct fuse.

3

 The shower must be connected to its own 

independent electrical circuit. 

IT MUST NOT

 

be connected to a ring main, spur, socket 

outlet, lighting circuit or cooker circuit.

3.1

  The electrical supply must be adequate for 

the loading of the unit and existing circuits.

4

 

Check your consumer unit (main fuse box) 

has a main switch rating of 80A or above 

and that it has a spare fuse way which will 

take the fuse or Miniature Circuit Breaker 

(MCB) necessary for the shower 

(Fig.4)

.

4.1

  If your consumer unit has a rating below 

80A or if there is no spare fuse way, then the 

installation will not be straightforward and 

may require a new consumer unit serving 

the house or just the shower.

4.2

  You will need to contact the local electricity 

company. They will check the supply and 

carry out what is necessary. 

  For close circuit protection 

DO NOT

 use a 

rewireable fuse. Instead use a suitably rated 

Miniature Circuit Breaker (MCB) or cartridge 

fuse 

(see Table A)

.

5.1

  A 30mA residual current device (RCD) 

MUST

 be installed in all UK electric and 

pumped shower circuits. This may be part of 
the consumer unit or a separate unit.

Triton Showers,

Triton Road, Nuneaton,

Warwickshire, CV11 4NR

xxxx

Fig.3

 

-

 Illustrative purposes only

 

Содержание ZANTE 4

Страница 1: ...the isolating switch when not in use This is a safety procedure recommended for all electrical appliances The showerhead and hose supplied with this product are a safety critical part of your shower Failure to use genuine Triton parts may cause injury and invalidate your guarantee FOR YOUR SERVICE REFERENCE NOTE DOWN THE PRODUCT CODE BELOW FROM THE FRONT OR TOP OF THE BOX ALTERNATIVELY REGISTER BY...

Страница 2: ...y tap or fitting other than those specified This appliance is intended to be permanently connected to the water mains and not connected by a hose set A suitable double pole isolation switch for supply disconnections must be incorporated in the fixed wiring circuit in accordance with current wiring rules See Electrical Installation section for further details Mains water pressure only Minimum inlet...

Страница 3: ... Building Regulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS EN 806 2 2 The supply pipe must be flushed to clear debris before connecting to the shower unit 2 3 DO NOT solder pipes or fittings within 300mm of the shower unit as heat can transfer along the pipework and damage components 2 4 DO NOT fit any form of ou...

Страница 4: ...T place items such as soap or shampoo bottles on top of the unit Liquid could seep through the joint between the cover and backplate and possibly damage the sealing rubber SPECIFICATION Electrical Nominal power Nominal power rating at 240V rating at 230V 8 5kW 40A MCB rating 7 9kW 40A MCB rating 9 5kW 40A MCB rating 8 7kW 40A MCB rating Water Inlet connection 15 mm diameter Outlet connection BSP m...

Страница 5: ...ical connections 14 Replacing the cover 15 Commissioning 16 Operating the shower 17 18 Operating functions 19 Cleaning 19 Instructions for installers and service engineers only 20 Spare parts 21 Fault finding 22 23 Water Cable entry points diagram 24 Guarantee service policy etc rear cover CONTENTS Page PRODUCT FICHE Model 8 5kW 9 5kW Load Profile XS XS Energy Efficiency Class A A Energy Efficienc...

Страница 6: ... cable entry area 6 Wall screw fixing 7 Terminal block 8 Power selector 9 Stabilising valve 10 Solenoid valve 11 Guide pockets 12 Can and element assembly 13 Thermal cut out main 14 Earth connection 15 Pressure relief device 16 Outlet temperature regulator 17 Neons 18 Trimplate Inside cover fig 2 19 Cover tags 20 Neon bracket 21 Start Stop switch NOTE Not all wiring shown for reasons of clarity 1 ...

Страница 7: ...f the whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring main spur socket outlet lighting circuit or cooker circuit 3 1 The electrical supply must be adequate for the loading of the unit and existing circuits 4 Check your consumer unit main fuse box has a main switch rating o...

Страница 8: ...ing in a bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket outlets in those rooms must be protected by a 30mA RCD 8 The current carrying capacity of the cable must be at least that of the shower circuit protection see Table B 8 1 To obtain full advantage of the power provided ...

Страница 9: ...tatic pressure must be no greater than 1000kPa 10 bar If in any doubt the pressure should be checked Note If the stated flow rates are not available it may not be possible to achieve optimum performance from the unit throughout the year During periods of high ambient temperatures it may be necessary to select a low power setting to achieve your preferred shower temperature The water supply can be ...

Страница 10: ...ER IMPORTANT If installing onto a tiled wall always mount the unit on the surface of the tiles NEVER tile up to the unit Refer to fig 6 for the correct siting of the shower Position the unit where it will NOT be in direct contact with water from the showerhead Position the shower unit vertically Allow enough room between the ceiling and the shower to access the cover top screws Leave enough space ...

Страница 11: ... or side the centre of the inlet valve to the wall surface is 21mm fig 10 Note If entry is from the rear the nut of the compression fitting will be partially behind the surface of the wall fig 10 This area MUST be left clear when plastering over the pipework in order to make the nut accessible for future adjustments IMPORTANT Always seal around the incoming pipework to prevent water entering the w...

Страница 12: ...the backplate over the top and bottom screws and fit the centre fixing screw into position Do not fully tighten the screws at this stage as the fixing holes are elongated to allow for out of square adjustment after the plumbing connections have been completed T00434 P1 27 21 00 2A P1 27 21 00 2A IN L E T IN L E T POM GF30 POM GF30 P1 27 21 00 2A IN L E T Fig 11 Fig 10 ...

Страница 13: ...er flush out the pipework to remove all swarf and system debris This can be achieved by connecting a hose to the pipework and turning on the mains water supply long enough to clear the debris to waste Procedure Turn off water supply either at the mains stopvalve or the isolating stopvalve Connect the mains water supply to the inlet of the shower via 15mm copper stainless steel or plastic pipe usin...

Страница 14: ...e insulation is trapped under the screws Loose connections can result in cable overheating Note The supply cable earth conductor must be sleeved The outer sheath of the supply cable must be stripped back to the minimum The supply cable must be secured either by routing through conduit or in trunking or by embedding in the wall in accordance with current IEE regulations The use of connections withi...

Страница 15: ...nside the cover fig 18 The neon with the yellow wires clips into the upper position and the remaining neon fits into the lower position Attached to the START STOP switch inside the cover is a two wire lead Connect the socket on the end of the lead to the plug leading from the backplate fig 19 Note The plug and socket can only fit one way Carefully locate the cover tags into the guide pockets on th...

Страница 16: ...s to the shower The power indicator will light Press the Start Stop button fig 20 and wait until water starts to flow from the flexible hose Slowly turn the temperature control fully anti clockwise to maximum flow position fig 21 It will take about thirty seconds for a smooth flow of water to be obtained while air and any debris is being flushed from the shower When there is a smooth flow of water...

Страница 17: ...t cannot be met due to low water pressure it will be necessary to operate the unit on this setting during the warmer months because of flow rate limitations entering the unit The double red symbol is a high power setting which allows the highest flow achievable for your preferred temperature This setting should normally be regarded as optimum shower performance throughout the year Temperature adju...

Страница 18: ...igher numbers Note It is advisable to be certain that the showering temperature is satisfactory by testing with your hand before stepping under the showerhead There will always be a time delay of a few seconds between selecting a flow rate and the water reaching the stable temperature for that flow rate CAUTION It is recommended that persons who may have difficulty understanding or operating the s...

Страница 19: ...hen the temperature has cooled sufficiently power to the elements will be automatically restored to the settings at the time of interruption Safety cut out The unit is fitted with a non resettable thermal cut out safety device In the event of abnormal operation which could cause unsafe temperatures within the unit the device will disconnect the heating elements It will require a visit from a quali...

Страница 20: ...ing switch off both the electricity supply and water supply at the mains The inlet filter is situated in the side of the inlet pipe fig 24 To gain access to the filter remove the trimplate and then unscrew the retaining nut from the side of the inlet pipe When cleaning the filter do not use a sharp object as it will cause damage It is preferable to use an old toothbrush or similar When refitting t...

Страница 21: ...011 Thermal cut out 22011180 Stabiliser valve Solenoid assembly P12120806 Pressure relief device PRD 82800450 Heater can assembly 8 5kW P12120701 9 5kW P12120702 Start Stop switch assembly 82301310 Outlet pipe Terminal block assembly S12721003 Inlet Assembly S12721002 Trimplate 7053638 Cover assembly White P19120602 including Start Stop switch assembly SPARE PARTS ...

Страница 22: ...e Reduce flow rate via temperature control Is water supply mains or tank fed If tank fed replumb to mains water supply or see 4 2 4 If mains fed make sure that the mains stopvalve is fully open and there are no other restrictions in the supply while shower is in use or see 4 2 4 Fit pump to give minimum pressure see rating label Contact Customer Experience for advice Readjust flow rate to give red...

Страница 23: ... 3 4 2 4 4 3 1 4 3 2 4 4 1 5 1 1 6 1 1 6 2 1 6 3 1 6 4 1 7 1 1 7 2 1 7 3 1 required see rating label Reduction in ambient water temperature Electrical malfunction or safety cut out operated Water pressure has dropped below minimum required Blocked showerhead Twisted blocked flexible shower hose Showerhead not removed while commissioning Water pressure above specified maximum for unit see rating la...

Страница 24: ... directive Triton Showers is fully registered with the Environment Agency under the following scheme Repic Producers take back scheme PTS registration number WEE EJ3466QV All our electric products are labelled accordingly with the crossed out wheeled bin symbol This indicates for disposal purposes at end of life that these products must be taken to recognised collection points such as local author...

Страница 25: ...Zante 4 electric shower 25 ...

Страница 26: ...Zante 4 electric shower 26 ...

Страница 27: ...Zante 4 electric shower 27 ...

Страница 28: ...iners Card Payment can also be made by pre payment of a pro forma invoice by cheque or postal order Telephone orders are based on information given during the call Before contacting Triton please verify your requirements using the Triton website or your professional installer Triton cannot accept liability for incorrect part identification TRITON UK STANDARD GUARANTEE This guarantee applies only t...

Отзывы: