After the lock, temperature probe, power supply, battery, and wiring are connected per the installation
instructions, the system should be tested as follows to confirm full functionality.
SPECIFICATIONS:
Primary Power: 120 AC -12V DC 500mA UL Certified wall converter
Back Up Power: 9V NiCad rechargeable battery
Test Button: For Health Department to confirm proper locking function
Cooler Protection Temperature: 41F or greater for 30 minutes
Freezer Protection Temperature: 0F or greater for 30 minutes
Refill Cooler Timer Extension: 45 minutes
Refill Freezer Timer Extension: 90 minutes
Primary Power Loss: Automatically locks in 2 minutes, continues monitoring and automatically unlocks if power is restored before a
protection locking event occurs
FUNCTIONAL TESTING AT NORMAL OPERATING TEMPERATURE
To be completed with the unit at normal operating temperature, with the locked plugged in and the
rechargeable battery installed.
Wait for a minimum of 30 minutes for the unit to cool down and to charge the battery before proceeding.
The LED should be solid green before proceeding.
If the doors are locked, use the P1 key fob to unlock it by pointing the key fob at the lock LED and pressing the
center button of the key fob. When the GREEN LED lights, the lock is unlocked and the unit is at normal operating
temperature.
If the LED is flashing RED-GREEN, this indicates that the unit is unlocked and has not reached normal operating
temperature.
Note: If the lock does not function as indicated in the test instructions below, refer to the Troubleshooting Guide.
DOOR BRACKET ENGAGEMENT
Locking the unit:
Close the doors and point the P1 key fob at the lock LED and press
the fob button.
Confirm the LED is solid RED and the doors are
locked. If the doors are not locked, the alignment could be faulty.
Refer to the lock installation instructions.
Unlocking the unit:
Point the P1 key fob at the lock LED and press the fob button.
Confirm the LED is solid GREEN and the doors are unlocked.
HEALTH DEPARTMENT TEST PROCEDURE
LED Indicators:
Solid
GREEN
– unlocked and monitoring for faults
Flashing
RED
-
GREEN
– unlocked and waiting for unit to reach temperature
Solid RED
– locked intentionally, no faults
Single flashing
RED
– locked due to an over temperature event
Double flashing
RED
– power failure
Triple flashing
RED
– temperature probe failure or test button was pressed