Installation

Step 7 - Battery Voltage Sense

The voltage at the battery connection on the TriStar MPPT 150V may differ slightly from the 

voltage directly at the battery bank terminals due to connection and cable resistance. The 

Battery 

Voltage Sense

 connection enables the TriStar MPPT 150V to measure the battery terminal 

voltage precisely with small gauge wires that carry very little current, and thus have no voltage 

drop. Both battery voltage sense wires are connected to the TriStar at the 2-position terminal 

located between the push-button and the positive (+) terminal lug (see figure 2-1).

A battery voltage sense connection is not required to operate your TriStar MPPT 150V controller, 

but it is recommended for best performance.  If a TriStar meter will be added to the controller, the 

battery voltage sense will ensure that the voltage and diagnostic displays are very accurate.
The voltage sense wires should be cut to length as required to connect the battery to the voltage 

sense terminal.  The wire size can range from 16 to 24 AWG (1.0 to 0.25 mm

2

).  A twisted pair 

cable is recommended but not required. Use UL rated 300 Volt conductors. The voltage sense 

wires may be pulled through conduit with the power conductors.  
Fuse the positive (+) voltage sense wire as close to the battery as possible.  Size the fuse based on 

wire ampacity - a 1A fuse can be used for #24 wire.
Tighten the connector screws to 5 in-lb (0.56 Nm) of torque.

The maximum length allowed for each battery voltage sense wire is 98 ft (30 m).  
Be careful to connect the battery positive (+) terminal to the voltage sense positive (+) terminal.  

No damage will occur if the polarity is reversed, but the controller cannot read a reversed sense 

voltage.  Connecting the voltage sense wires to the RTS terminal will cause an alarm.

If a TriStar meter is installed, check the “TriStar Settings” to confirm the Voltage Sense and the 

RTS (if installed) are both present and detected by the controller.  MSView

TM

 PC software can 

also be used to confirm the voltage sense is working correctly.  

Step 8 - Network Connections

Network connections allow the TriStar MPPT 150V to communicate with other controller or com-

puters. A network can be as simple as one controller and one PC, or as complex as dozens of 

controllers monitored via the internet. Review section 5.0 for more information about networking 

and the connection(s) required for your system. 

WARNING:  Shock Hazard
Never route network cables in the same conduit as the power conductors

.

WARNING:  Shock Hazard
Only use 300 Volt UL rated communication cable.

AVERTISSEMENT :  Risque de décharge électrique
N’acheminez jamais les câbles réseau dans le même conduit que les 
conducteurs d’alimentation.

AVERTISSEMENT :  Risque de décharge électrique
N’utilisez qu’un câble de communication 300 V homologué UL.

Connect the appropriate network cables to the TriStar MPPT 150V at this time. Access to the 

network ports is easier before the power cables are attached. The ports are located inside the 

conduit wiring box on the lower circuit board as shown in figure 3-5.

RS-485

(4 position)

RS-232

(DB-9)

Ethernet

(RJ-45)

MeterBus

(RJ-11)

Figure 3-5. TriStar MPPT 150V network port locations

EIA-485 Connection

The four (4) position EIA-485 connector on the TriStar MPPT 150V must be removed to access 

the terminal screws. Remove the socket connector by firmly grasping the connector body and 

pulling away from the circuit board as shown in Figure 3-6.

Figure 3-6. Removing the RS-485 socket connector

Содержание TRAKSTAR TS-MPPT-45

Страница 1: ... www morningstarcorp com Solar Battery Charger With TrakStarTM Maximum Power Point Tracking Technology MODELS TS MPPT 30 TS MPPT 45 TS MPPT 60 TS MPPT 60M MAXIMUM POWER POINT TRACKING TRISTAR MPPT TM For the most recent manual revisions see the version at www morningstarcorp com ...

Страница 2: ... Controller Installation 18 4 0 Operation 34 4 1 TrakStarTM MPPT Technology 34 4 2 Battery Charging Information 36 4 3 Push button 43 4 4 LED Indications 44 4 5 Protections Faults Alarms 46 4 6 Inspection and Maintenance 49 5 0 Networking and Communication 51 5 1 Introduction 51 5 2 Morningstar MeterBusTM 52 5 3 Serial RS 232 53 5 4 EIA 485 formerly RS 485 55 5 5 Ethernet 56 6 0 Troubleshooting 59...

Страница 3: ... tight to avoid excessive heating from a loose connection Use properly sized conductors and circuit interrupters The grounding terminal is located in the wiring compartment and is identified by the symbol below Ground Symbol SAVE THESE INSTRUCTIONS This manual contains important safety installation and operating instructions for the TriStar MPPT 150V solar controller The following symbols are used...

Страница 4: ...de système et d application CAUTION Do not open or mutilate batteries Released electrolyte is harmful to skin and may be toxic PRUDENCE Ne pas ouvrir ou mutiler les piles L électrolyte est nocif pour la peau et peut être toxique This charge controller is to be connected to DC circuits only These DC connections are identified by the symbol below Direct Current Symbol The TriStar MPPT 150V controlle...

Страница 5: ...rotection et ayez de l eau fraîche à disposition en cas de contact avec l électrolyte Enlevez les montres bagues bijoux et autres objets mé talliques avant de travailler avec des piles Porter des bottes et des gants de caoutchouc Utiliser des outils avec poignées isolantes et évitez de placer des outils ou des objets métalliques sur le dessus de batteries Débrancher la source de charge avant de br...

Страница 6: ...l help you make full use of the many advantages the TriStar MPPT 150V can provide for your PV system 2 2 Versions and Ratings There are four versions of TriStar MPPT 150V controller TriStar MPPT 30 maximum 30 amps continuous battery current 12 24 and 48 Volt dc systems maximum 150 Volt dc solar input voltage RS 232 and MeterBusTM communication ports TriStar MPPT 45 maximum 45 amps continuous batte...

Страница 7: ...5 2 29 battery chargers A means shall be provided to ensure all pole disconnection from the power supply This discon nection shall be incorporated in the fixed wiring Using the TriStar MPPT 150V grounding terminal in the wiring compartment a permanent and reliable means for grounding shall be provided The clamping of the earthing shall be secured against accidental loosening The entry openings to ...

Страница 8: ...Star MPPT 150V controller DIN rail compatible See section 5 2 for more details Relay Driver RD 1 The Relay DriverTM accessory enables the TriStar MPPT 150V to control external devices Four 4 relay control ports can be configured in various combinations to perform the following tasks generator control 2 3 and 4 wire configurations dry contacts for alarms and other signals advanced load control vent...

Страница 9: ... requirements are noted on occasion for convenience however the installer should have a complete understanding of NEC and UL requirements for photovoltaic installations Installation 3 0 Read through the entire installation section first before beginning installation Be very careful when working with batteries Wear eye protection Have fresh water available to wash and clean any contact with battery...

Страница 10: ...through conduit or wire glands Table 3 1 below pro vides the knockout sizes and quantity on the TriStar MPPT 150V wiring box Knockout locations and dimensions are on the inside front cover Quantity Trade Size Hole Dimension 8 1 2 or M20 7 8 22 2 mm 6 1 1 23 64 34 5 mm 4 1 1 4 1 23 32 43 7 mm Table 3 1 Knockout sizes CAUTION Shock Hazard Always use bushings connectors clamp connectors or wire gland...

Страница 11: ...yhole on the TriStar MPPT 150V with the screw head Slide the TriStar MPPT 150V down over the keyhole 7 Check for vertical plumb with a level 8 Mark two 2 mounting hole locations in the wiring box 9 Remove the controller and drill 3 32 2 5 mm holes at the drill marks 10 Carefully align the keyhole on the TriStar MPPT 150V with the screw head Slide the TriStar MPPT 150V down over the keyhole 11 The ...

Страница 12: ...harges when the controller is con figured for automatic equalizations settings switch 7 Switch 7 Battery Equalization Choose between manual and automatic battery equalization charging In the manual equaliza tion setting an equalization will only occur when manually started with the push button or when requested from the equalize menu on the TriStar meter Automatic equalization will occur accord in...

Страница 13: ...t être raccourci si la totalité de la longueur n est pas nécessaire Assurez vous de réinstaller la bobine en ferrite sur l extrémité du RTS si une longueur de câble est enlevée Cette bobine assure la conformité avec les normes d émissions électromagnétiques Step 6 Grounding and Ground Fault Interruption WARNING This unit is not provided with a GFDI device This charge controller must be used with a...

Страница 14: ...occur if the polarity is reversed but the controller cannot read a reversed sense voltage Connecting the voltage sense wires to the RTS terminal will cause an alarm If a TriStar meter is installed check the TriStar Settings to confirm the Voltage Sense and the RTS if installed are both present and detected by the controller MSViewTM PC software can also be used to confirm the voltage sense is work...

Страница 15: ...of array terminals The battery positive terminal has a red cover the solar positive terminal has a yellow cover REMARQUE Pour la conformité CNE le TriStar MPPT 150V doit être installé selon des méthodes de câblage conformes à la dernière édition du Code électrique national NFPA 70 PRUDENCE Risque d incendie et de décharge électrique Branchez les bornes de la batterie avant la connexion des bornes ...

Страница 16: ...ire des tensions de circuit ouvert supérieures à 150 Vdc à la lumière du soleil Vérifiez que le coupe circuit ou l interrupteur d entrée solaire a été ouvert déconnexion avant d installer les câbles du système Figure 3 7 Power terminal locations Connect the four 4 power conductors shown in figure 3 7 above in the following steps 1 Confirm that the system input and output disconnect switches are bo...

Страница 17: ...TISSEMENT Risque d endommagement La connexion du réseau solaire sur la borne de la batterie endommagera le TriStar MPPT 150V de façon permanente AVERTISSEMENT Risque d endommagement La connexion du réseau solaire ou la connexion de la batterie avec une polarité inversée endommagera le TriStar MPPT 150V de façon permanente Confirm that the Solar and Battery polarities are correct Turn the battery d...

Страница 18: ...cuit voltage Voc rating will not exceed the TriStar MPPT 150V 150 Volt maximum input voltage rating at worst case coldest module temperature The solar module documentation should provide Voc vs temperature data Higher solar input voltage results in lower solar input current for a given input power High voltage solar input strings allow for smaller gauge solar wiring This is especially helpful and ...

Страница 19: ...battery from long term overcharge The green SOC LED will blink once every two 2 seconds during Float charging Once in Float stage loads can continue to draw power from the battery In the event that the system load s exceed the solar charge current the controller will no longer be able to maintain the battery at the Float set point Should the battery voltage remain below the Float set point for a c...

Страница 20: ...if the battery is fully recharged However a solar charged battery is seldom completely recharged so the soft lead sulfate crystals harden over a period of time Only a long controlled overcharge or equalization at a higher voltage can reverse the hardening of sulfate crystals Preparation for Equalization First confirm that all of the system loads are rated for the equalization voltage Consider that...

Страница 21: ...normal Absorption duration Float Time out Figure 4 4 Float exit time out charging profile After entering Float stage the controller will only exit Float if the battery voltage remains below Float voltage for 60 cumulative minutes In figure 4 4 a system load turns on at 3 30 hrs when the controller is in Float stage runs for one hour and turns off at 4 30 hrs The load current draw is larger than th...

Страница 22: ...battery The controller will begin Absorption or limit equalization at a lower battery voltage because the controller measures a higher voltage at the controller s terminals than is the actual battery voltage For example if the controller is programmed to start Absorption at 14 4V when the controller sees 14 4V at its battery terminals the true battery voltage would only be 14 1V if there is a 0 3V...

Страница 23: ... R R Battery service is required all three LEDs blinking until service is reset battery service notification is only enabled in custom settings or when any custom edit is programmed Battery Status General state of charge See battery SOC LED indications below Absorption state G blinking second on second off Equalization state G fast blink 2 5 times per second Float state G slow blink 1 second on 1 ...

Страница 24: ...s been working the LED s will indicate a failure However if the controller is restarted with a failed RTS the controller may not detect that the RTS is connected and the LEDs will not indicate a problem A TriStar meter or the PC software can be used to determine if an RTS is detected and working properly Battery Voltage Sense Failure G R sequencing with constant yellow If a fault in the battery se...

Страница 25: ... the controller Use of the RTS is recom mended for proper battery charging Heatsink Temperature Sensor Open Shorted The heatsink temperature sensor is damaged Return the controller to an authorized Morningstar dealer for service Battery Sense Out of Range Disconnected A battery sense wire is disconnected Inspect the battery sense connections This alarm is set when the voltage at the battery sense ...

Страница 26: ...neously Table 5 1 below provides a summary of supported features for each communication interface MeterBus RS 232 EIA 485 Ethernet Display system network data on a TriStar meter Connect a TSMPPT to a Relay Driver or other MS Accessory Connect multiple TSMPPT together in a network View and log data with MSViewTM PC Software View logged data stored in the TriStar MPPT 150V internal memory Update Tri...

Страница 27: ... five 5 controllers can be networked together with a single hub Multiple hubs can be daisy chained together to allow networks of up to 14 controllers and a meter Refer to the HUB 1 and TriStar Meter manuals for more information about Morningstar Meter BusTM networking 5 3 Serial RS 232 The serial port connection on the TriStar MPPT 150V is a standard 9 pin isolated RS 232 port See figure 3 5 for t...

Страница 28: ...nnect the TriStar MPPT 150V to other Morningstar controllers with the RSC 1 Serial to EIA 485 Adapter sold separately bridge an Ethernet connection through a TriStar MPPT 150V to an EIA 485 network The EIA 485 port has four 4 connections Power Data A Data B and Ground Data A B are differentially driven data lines that carry the network data Power and Ground connections pro vide power to the networ...

Страница 29: ...gram for both scenarios is shown in figure 5 3 below Ethernet Cross over Cable Figure 5 3 Ethernet network diagrams Factory Default Network Settings DHCP enabled Live View Web Address http tsmppt serial number IP 192 168 1 253 if DHCP is not enabled Subnet Mask 255 255 255 0 Gateway 192 168 1 1 Primary DNS Server 169 254 1 1 MODBUS TCP IPTM Port 502 The Live View web address is unique to each cont...

Страница 30: ...BETWEEN ALL TERMINALS AND GROUND BEFORE TOUCHING AVERTISSEMENT RISQUE DE CHOC ÉLETRIQUE NON ALIMENTATION OU AUX BORNES D ACCESSOIRES SONT ISOLÉS ÉLEC TRIQUEMENT DE L ENTRÉE DE C C ET DOIT ÊTRE ALIMENTÉS À UNE TENSION DAN GEREUSE SOLAIRE SOUS CERTAINES CONDITIONS DE DÉFAILLANCE LA BATTERIE POURRAIT DEVENIR TROP CHARGÉE TEST ENTRE TOUTES LES BORNES ET LA MASSE AVANT DE TOUCHER WARNING Shock Hazard A...

Страница 31: ... not work Power is supplied to the 4 wire bus on the Power Ground lines The bus requires voltage in the range 8 16 Vdc All bus connections are secure and each terminal is wired in parallel line A to line A line B to line B etc Problem Cannot connect to the controller via Ethernet Solution See the TriStar MPPT 150V Networking Companion Document available on our website LIMITED WARRANTY Morningstar ...

Страница 32: ...t Voltage All 150 Volts dc Battery Operating Voltage Range All 8 72 Volts dc Nominal Maximum Input Power 12 Volt 400 Watts 600 Watts 800 Watts 24 Volt 800 Watts 1200 Watts 1600 Watts 48 Volt 1600 Watts 2400 Watts 3200 Watts Voltage Accuracy 12 24 V 0 1 50 mV 48 V 0 1 100 mV Self consumption tare loss All 1 3 2 7 Watts Transient Surge Protection All 4500 Watts port These power levels refer to the m...

Страница 33: ... terminals Minimum wire size 0 25 mm2 24 AWG Maximum wire size 1 0 mm2 16 AWG Recommended torque 0 40 Nm 3 5 in lb Knockouts trade sizes M20 1 2 1 1 1 4 Mounting Vertical surface Environmental Operating Altitude Below 2000 meters Ambient Temperature Range 40 C to 45 C Storage Temperature 55 C to 85 C Humidity 100 N C Enclosure IP20 Type 1 indoor vented Protections Solar high voltage disconnect Sol...

Страница 34: ...ater TriStar MPPT 24 Volt Efficiency output power Watts efficiency 99 98 97 96 95 94 93 92 91 90 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 0 89 33 Vmp 66 Vmp 98 Vmp 26 Vmp Battery 25 6 V 25 C ambient firmware ver 08 or later TriStar MPPT 48 Volt Efficiency output power Watts efficiency 100 99 98 97 96 95 94 93 92 91 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 26...

Страница 35: ...at 30 C ambient temperature Ampacity for not more than three current car rying conductors in a raceway cable or earth buried 2 Voltage Drop Charts for 75 C Solid Copper Wire 1 Way Wire Distance feet 12 Volt System Wire Size AWG 60 Amps 55 Amps 50 Amps 45 Amps 40 Amps 35 Amps 30 Amps 25 Amps 20 Amps 15 Amps 2 0 27 8 30 3 33 4 37 1 41 7 47 7 55 6 66 7 83 4 111 2 1 0 22 0 24 1 26 5 29 4 33 1 37 8 44 ...

Страница 36: ... at 30 C ambient temperature Ampacity for not more than three current car rying conductors in a raceway cable or earth buried 2 Voltage Drop Charts for 90 C Solid Copper Wire 1 Way Wire Distance feet 12 Volt System Wire Size AWG 60 Amps 55 Amps 50 Amps 45 Amps 40 Amps 35 Amps 30 Amps 25 Amps 20 Amps 15 Amps 2 0 27 8 30 3 33 4 37 1 41 7 47 7 55 6 66 7 83 4 111 2 1 0 22 0 24 1 26 5 29 4 33 1 37 8 44...

Страница 37: ... 2005 EMC Immunity Industrial Environments EN 55022 2007 Class B EMC Emissions EN 60335 1 2002 Safety EN 60335 2 29 2005 Safety IEC 62109 1 2010 Safety of Power Converters in PV Systems TrisStar MPPTTM MeterBusTM are trademarks of Morningstar Corporation MODBUSTM and MODBUS TCP IPTM are trademarks of Modbus IDA www modbus ida org 2018 Morningstar Corporation All rights reserved MS 000946 v6 1 TUVR...

Отзывы: