background image

 

Tripp Lite

1111 West 35th Street

Chicago, IL 60609 USA

Telephone: +(773) 869 1234

E-mail: 

[email protected]

Model #: SU2200RTXL2UN

SmartOnline 2.2kVA On-Line Double-Conversion UPS, Pre-installed SNMPWEBCARD, 2U Rack/Tower,
110/120V NEMA outlets

 

Highlights

2200VA / 2.2kVA / 1600 watt on-line double-conversion 2U rack/tower UPS 

110/120V +/-2% output at 50/60Hz, high 97% efficiency economy mode option

Expandable runtime, Hot-swap batteries; 19 in / 48.3cm installed depth

USB, RS232, EPO ports and PRE-INSTALLED SNMPWEBCARD

Front panel status LEDs with detailed load and battery metering

2 independently switchable output load banks

NEMA 5-20P input; L5-20R & 5-15/20R outlets

Description

 Tripp Lite Smart Online UPS systems offer high performance power protection ideal for critical server and network equipment in datacenters,
computer rooms and network closets. Online, double-conversion Uninterruptible Power Supply (UPS) maintains perfectly regulated output power by
continuously converting raw AC input to DC, then re-converting output back to AC. Fully regulated sine wave AC output with +/-2% voltage regulation
powers network equipment continuously, even during severe brownouts and overvoltages, all without depleting UPS battery reserves. Maintains
battery-derived AC output during power failures with zero transfer time. Extended runtime options available. High 97% efficient operation in optional
economy mode saves BTU heat output and energy costs. Network management interfaces support communications via USB, RS-232,
contact-closure and PRE-INSTALLED SNMPWEBCARD network interface. Built-in DB9 port offers both enhanced RS-232 data and basic contact
closure monitoring ability. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows
and Mac OS X. Includes PowerAlert monitoring software and complete cabling. Emergency Power Off (EPO) interface. LED display reports UPS
operating mode, line power availability, battery mode operation, inverter operation and output power availability. Audible alarm with push-button
momentary alarm-cancel. Programmable self-test. Battery independent restart. Fault-tolerant auto-bypass mode. Field-replaceable, hot-swappable
internal batteries and external battery packs. 

Package Includes

SU2200RTXL2UN UPS with Pre-installed SNMPWEBCARD

PowerAlert Software and cabling

Mounting hardware for 4 post rack enclosures

Instruction manual 

Features

Tripp Lite SU2200RTXL2UN 2200VA / 2.2kVA / 1600W on-line, double-conversion 3U rackmount UPS

Selectable 110/120V output (120V factory preset) 

NEMA 5-20P input, 6 NEMA 5-15/20R & 1 L5-20R 

Two switched 3-outlet load banks support remote reboot or programmable load shedding options

Supports 2% output voltage regulation and zero transfer time in double conversion mode

Economy mode option offers enhanced 97% efficiency operation, reduced power consumption and lower BTU emissions

14 minutes runtime at 50% load (800W) and 4.5 minutes at 100% load (1600W) with internal batteries

BP48V24-2U (limit 1) or BP48V60RT-3U (no limit) external battery packs available (some configurations require Tripp Lite's External

Battery Configuration Software)

LED Display reports UPS operating mode, line power availability, battery mode operation, inverter status and output power availability

Audible alarm with push-button momentary alarm-cancel

4 post installation hardware included, Optional 2POSTRMKITHD enables 2 post rack installation

Single line TEL / Network surge suppression

Electronic bypass maintains utility output during a variety of UPS fault conditions

Содержание SU2200RTXL2UN

Страница 1: ...liant USB interface enables integration with built in power management and auto shutdown features of Windows and Mac OS X Includes PowerAlert monitoring software and complete cabling Emergency Power Off EPO interface LED display reports UPS operating mode line power availability battery mode operation inverter operation and output power availability Audible alarm with push button momentary alarm c...

Страница 2: ...ower factor 0 7 Crest Factor 3 1 Nominal Output Voltage s Supported 110V 120V Nominal Voltage details 120V default Frequency compatibility 50 60 Hz Frequency compatibility details Output frequency matches input nominal on startup defaults to 60 Hz on cold start Output voltage regulation line mode 2 Output voltage regulation Economy line mode 10 Output voltage regulation Battery mode 2 Built in UPS...

Страница 3: ...ent description Hot swappable user replaceable sealed flame retardant non spillable batteries VOLTAGE REGULATION Voltage regulation description Online double conversion power conditioning Overvoltage correction 2 output voltage regulation during overvoltages to 150 Undervoltage correction 2 output voltage regulation during undervoltages to 80 Severe undervoltage correction 2 output voltage regulat...

Страница 4: ...height x width x depth inches 3 5 x 17 5 x 19 UPS Power Module dimensions in primary form factor height x width x depth cm 8 9 x 44 4 x 48 3 Installed whole system dimensions in secondary form factor height x width x depth cm 44 4 x 8 9 x 48 3 Rack Height 2U Secondary form factor Tower requires 2 9USTAND Installed whole system dimensions in secondary form factor height x width x depth inches 17 5 ...

Страница 5: ...PWEBCARD interface card Supports detailed monitoring of UPS and site power conditions PowerAlert software Included Communications cable USB and DB9 cabling included WatchDog compatibility Supports Watchdog application OS and hard reboot restart options for remote applications LINE BATTERY TRANSFER Transfer time No transfer time 0 ms in online double conversion mode Low voltage transfer to battery ...

Страница 6: ...120V 1U Horizontal Rackmount 13 NEMA 5 15 20R outlets NEMA 5 20P input plug 1 PDUV20 Single Phase Basic PDU 20A 120V 0U Vertical Rackmount 14 NEMA 5 15 20R outlets NEMA L5 20P input with 5 20P adapter 1 PDUMV20 Single Phase Metered PDU 20A 120V 0U Vertical Rackmount 28 NEMA 5 15 20R outlets NEMA L5 20P input with 5 20P adapter 1 PDUMH20AT Single Phase Auto Transfer Switch Metered PDU 20A 120V 1U H...

Отзывы: