Important Safety Instructions

•  Do not use this equipment within oxygen-enriched atmospheres, or within 0.3 m of a point at 

which an oxygen-enriched atmosphere is intentionally vented.

•  Use caution when lifting UPS. Because of the considerable weight of all UPS systems, at least 

two people should assist in lifting and installing them.

•  Install your UPS indoors, away from excess moisture or heat, dust or direct sunlight.
•  For best performance, the UPS should be used in a location that meets the following conditions: 

Temperature: 0 to 40° C; Humidity: 0 to 95% (non-condensing); 

Elevation: <2,000 m above sea level; Pressure: >95kPa

•  Leave adequate space around all sides of the UPS for proper ventilation. Do not obstruct its vents 

or fan openings.

•  Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner 

will seriously inhibit the unit’s internal cooling, eventually causing product damage not covered 

under warranty.

•  The UPS is not intended for patient contact. Avoid installations that will cause accidental patient 

contact.

UPS Connection Warnings

•  The UPS contains its own energy source (battery). The output terminals may be live even when 

the UPS is not connected to an AC supply.

•  Connect your UPS to a properly grounded AC power outlet. Do not modify the UPS’s plug in a 

way that would eliminate the UPS’s connection to ground. Do not use adapters that eliminate the 

UPS’s connection to ground.

•  Do not plug your UPS into itself; this will damage the UPS and void your warranty.
•  If you are connecting your UPS to a motor-powered AC generator, the generator must provide 

filtered, frequency-regulated output. 

•  To remove the UPS from the supply mains, the appliance inlet serves as a disconnect device. 
•  Once connected, do not limit access to the input plug. The plug must be accessible to be used as 

a means of disconnection.

•  When connecting the UPS to a power outlet, ensure the power outlet is provided with suitable 

overcurrent protection in accordance with national and local electrical codes. Ensure the 

overcurrent protection has a minimum of 1500A breaking capacity.

CAUTION: Do not remove cover for 5 minutes after disconnecting all sources of 

supply. Risk of electric shock—hazardous live parts inside. User must not remove 

cover. No user serviceable parts inside. Refer servicing to qualified service 

personnel. This UPS receives power from more DC sources; disconnection of the 

AC and DC source is required to de-energize the unit before servicing.
CAUTION: To ensure proper grounding with supply mains power, the input cord must 

be connected with an approved country-specific plug with a protective earth ground 

connection.
CAUTION: If this product is operated on battery (not connected to mains power), 

adequate safeguards should be employed to protect against accidental contact 

with AC power conductors.
CAUTION: Do not exceed total rated output.

WARNING: No modification of this equipment is allowed.

18-06-259-933821.indb   3

6/20/2018   3:08:23 PM

Содержание SMX Series

Страница 1: ...ic Operation 8 Guidance and Manufacturer s Declaration 11 Storage Service 12 Battery Warranty Information 13 Regulatory Compliance 13 Espa ol 14 Fran ais 27 40 Deutsch 53 SMX700HGL Series Number AG 03...

Страница 2: ...h dongle Inlet C14 with dongle Operation Continuous Continuous AC Input Protection Qty type rating Input breaker 2 x 5A thermal Input breaker 2 x 6A thermal Max Leakage Current uA Less than 100uA Less...

Страница 3: ...iminate the UPS s connection to ground Do not plug your UPS into itself this will damage the UPS and void your warranty If you are connecting your UPS to a motor powered AC generator the generator mus...

Страница 4: ...d type of batteries lithium iron phosphate should perform battery replacement The batteries are recyclable At the end of the UPS unit s life follow best practice by discharging the battery prior to di...

Страница 5: ...cleaning the UPS only a damp cloth should be used For disinfecting the UPS a damp cloth wetted with isopropyl alcohol may be used No other cleaning agent should be used UPS and Battery Disposal Alway...

Страница 6: ...mains or connecting any equipment to the UPS The installation procedure is as follows 3 Slightly slide the battery pack out 4 Remove insulation on the negative battery terminal 5 Connect the negative...

Страница 7: ...however maximum runtime for the unit s battery will only be accessible after it has been charged for 24 hours 3 Turn the UPS ON Press and hold the POWER button for one second The alarm will beep once...

Страница 8: ...scription CAUTION Do not unplug your UPS to test its batteries This will remove safe electrical grounding and may introduce a damaging surge into your network connections Results of a Self Test The te...

Страница 9: ...BATTERY CHARGE BATTERY POWER LED When the UPS is operating from utility power this multicolored LED indicates the approximate charge state of the UPS s internal batteries red indicates the batteries...

Страница 10: ...UPS load If breaker trips remove some of the load then reset it by pressing the breaker in Equipotential Connection Use this to connect any equipment that requires a chassis ground Power Sensitivity...

Страница 11: ...Immunity Test IEC 60601 Test Level Compliance Level Electromagnetic Environment Guidance Electrostatic Discharge ESD IEC 61000 4 2 6kV contact 8kV air Complies Floors should be wood concrete or ceram...

Страница 12: ...ite For more information on service visit www tripplite com support Before returning your product for service follow these steps 1 Review the installation and operation procedures in this manual to in...

Страница 13: ...d Battery Recycling Please recycle Tripp Lite Products The batteries used in Tripp Lite products are lithium iron phosphate batteries These batteries are highly recyclable Please refer to your local c...

Страница 14: ...a 21 Orientaci n y Declaraci n del Fabricante 24 Almacenamiento y Servicio 25 Informaci n de la Garant a de la Bater a 26 Cumplimiento de las Regulaciones 26 English 1 Fran ais 27 40 Deutsch 53 SMX700...

Страница 15: ...lave electr nica Entrada C14 con llave electr nica Operaci n Continua Continua Protecci n de Entrada de CA Canti dad Tipo Especificaci n Breaker t rmico de entrada 2 x 5A breaker t rmico de entrada 2...

Страница 16: ...o esto da ar al UPS y anular su garant a Si est conectando su UPS a un generador de CA activado por motor el generador de proporcionar una salida filtrada y con frecuencia regulada Para retirar el UPS...

Страница 17: ...onal de servicio autorizado usando el mismo n mero y tipo de bater as Litio Ferrofosfato Las bater as son reciclables Al final de la vida de la unidad del UPS siga las siguientes buenas pr cticas para...

Страница 18: ...debe usarse solo un trapo h medo Para desinfectar el UPS puede usarse un trapo humedecido con alcohol isoprop lico No debe usarse otro agente limpiador Desecho del UPS y la Bater a Cumpla siempre con...

Страница 19: ...o al UPS El procedimiento de instalaci n es como sigue 3 Deslice un poco hacia afuera el m dulo de bater as 4 Quite el aislamiento en la terminal negativa de la bater a 5 Conecte la terminal negativa...

Страница 20: ...ue inicial no obstante la autonom a m xima para la bater a de la unidad s lo ser accesible despu s de haberse cargado por 24 horas 3 Encienda el UPS Presione y sostenga por el bot n POWER por un segun...

Страница 21: ...o desconecte su UPS para probar las bater as Esto eliminar la conexi n segura a tierra y puede introducir una sobretensi n da ina en las conexiones de su red Resultados de un Auto diagn stico La prueb...

Страница 22: ...BATTERY POWER Carga de Bater a Potencia de la Bater a Cuando el UPS est operando de la energ a de la red p blica este LED indica el estado aproximado de carga de las bater as internas del UPS rojo in...

Страница 23: ...ga y entonces restabl zcalo oprimi ndolo Conexi n Equipotencial sela para conectar cualquier equipo que requiera una conexi n de tierra al bastidor Ajuste de Sensibilidad de Energ a Esta car tula est...

Страница 24: ...agn tico Orientaci n Descarga Electrost tica ESD IEC 61000 4 2 Contacto 6kV Aire 8kV Cumple Los pisos deben ser de madera concreto o losetas cer micas Si se cubren los colores con material sint tico l...

Страница 25: ...Tripp Lite Para informaci n adicional acerca del servicio visite www tripplite com support Antes de regresar su producto para servicio siga estos pasos 1 Revise los procedimientos de instalaci n y op...

Страница 26: ...l UPS Recicle por Favor los Productos de Tripp Lite Las bater as usadas en productos de Tripp Lite son bater as de Litio Ferrofosfato Estas bater as son altamente reciclables Para los requisitos de de...

Страница 27: ...ctionnement de base 34 Conseils et d claration du fabricant 37 Entreposage et entretien 38 Renseignements sur la garantie 39 Conformit r glementaire 39 English 1 Espa ol 14 40 Deutsch 53 SMX700HGL num...

Страница 28: ...lectronique Entr e C14 avec cl lectronique Fonctionnement Continu Continu Protection de l entr e CA qt type calibre Disjoncteur d entr e 2 x 5 A thermique Disjoncteur d entr e 2 x 6 A thermique Couran...

Страница 29: ...ient la mise la terre de l onduleur Ne pas brancher l onduleur sur lui m me cela aura pour effet d endommager l onduleur et d annuler la garantie Si l onduleur est branch une g n ratrice CA entra n e...

Страница 30: ...utoris utilisant des batteries de m me type et de m me num ro batteries de phosphate de fer lithi Les batteries sont recyclables la fin de la dur e de vie de l onduleur suivre les meilleures pratiques...

Страница 31: ...ur le nettoyage Un chiffon imbib d alcool isopropylique peut tre utilis pour d contaminer l onduleur Aucun autre agent nettoyant ne doit tre utilis limination de l onduleur et des batteries Toujours s...

Страница 32: ...u de brancher tout quipement l onduleur La proc dure d installation est la suivante 3 Glisser l g rement le module de batteries pour le sortir 4 Enlever l isolation sur la borne n gative de la batteri...

Страница 33: ...endant la dur e de fonctionnement maximale de la batterie de l appareil ne sera accessible qu apr s avoir t charg e pendant 24 heures 3 Mettre l onduleur sous tension Appuyer sur le bouton POWER alime...

Страница 34: ...u bouton POWER alimentation MISE EN GARDE Ne pas d brancher l onduleur pour v rifier ses batteries Cela aura pour effet d liminer la mise la terre de s curit et risque d introduire une surtension domm...

Страница 35: ...batterie alimentation par batterie lorsque l onduleur fonctionne partir du courant du secteur ce voyant DEL indique l tat approximatif de la charge des batteries internes de l onduleur rouge indique q...

Страница 36: ...e enlever une partie de la charge puis le r armer en l enfon ant en place Connexion d quipotentialit Utiliser pour raccorder de l quipement n cessitant une mise la masse au ch ssis R glage de la sensi...

Страница 37: ...iveau de conformit Environnement lectromagn tique Conseils D charge lectrostatique DES IEC 61000 4 2 Contact de 6 kV Air 8 kV Conforme Les planchers doivent tre de bois de b ton ou de carreaux de c ra...

Страница 38: ...ien sont galement offerts par Tripp Lite Pour obtenir plus de renseignements sur le service visiter www tripplite com support Avant de retourner le produit pour la r paration proc der comme suit 1 Pas...

Страница 39: ...s produits Tripp Lite Les batteries utilis es dans les produits Tripp Lite sont des batteries de phosphate de fer lithi Ces batteries sont hautement recyclables Se reporter aux codes locaux pour les e...

Страница 40: ...50 51 52 52 English 1 Espa ol 14 Fran ais 27 Deutsch 53 SMX700HGL AG 031B SMX1200XLHGL AG 031C 1111W 35th Street Chicago IL 60609 USA www tripplite com support 2018Tripp Lite 18 06 259 933821 indb 40...

Страница 41: ...Tripp Lite Tripp Lite 100 SMX700HGL SMX1200XLHGL 230 230 3 6 5 2 3 3 700 450 1000 750 50 60 50 60 I I C14 C14 2 x 5 2 x 6 100 100 14 3 15 9 Tripp Lite L1 L2 18 06 259 933821 indb 41 6 20 2018 3 08 40...

Страница 42: ...42 0 3 0 40 C 0 95 2000 95 1500 5 18 06 259 933821 indb 42 6 20 2018 3 08 40 PM...

Страница 43: ...te www tripplite com products battery finder Tripp Lite Tripp Lite Tripp Lite Tripp Lite 1 773 869 1234 Tripp Lite Tripp Lite http www tripplite com support recycling program SMX700HGL 12 3 39 6 5 RBC...

Страница 44: ...44 SMX700HGL USB 1 8 DB9 1 8 SMX1200XLHGL USB 1 8 DB9 1 8 18 06 259 933821 indb 44 6 20 2018 3 08 40 PM...

Страница 45: ...45 1 2 1 2 3 4 5 6 7 3 4 5 6 7 8 2 9 1 18 06 259 933821 indb 45 6 20 2018 3 08 42 PM...

Страница 46: ...3 BATTERY CHARGE 2 230 1 230 230 OUTPUT LOAD LEVEL 24 3 POWER NORM DELAY 1 2 3 NORM DELAY NORM DELAY 1 2 1 DB9 Tripp Lite PowerAlert 2 USB USB USB Tripp Lite PowerAlert 24 18 06 259 933821 indb 46 6 2...

Страница 47: ...T MUTE TEST MUTE TEST POWER 10 OUTPUT LOAD LEVEL OUTPUT LOAD LEVEL BATTERYWARNING 12 Tripp Lite http www tripplite com products battery finder Tripp Lite POWER OUTPUT LOAD LEVEL BATTERY CHARGE 18 06 2...

Страница 48: ...GE VOLTAGE CORRECTION OUTPUT LOAD LEVEL BATTERY CHARGE BATTERY POWER MUTE TEST BATTERYWARNING MUTE TEST 12 Tripp Lite http www tripplite com products battery finder Tripp Lite 18 06 259 933821 indb 48...

Страница 49: ...49 USB DB9 Tripp Lite PowerAlert USB DB9 www tripplite com DB9 USB http www tripplite com products battery finder Tripp Lite NORM DELAY 18 06 259 933821 indb 49 6 20 2018 3 08 43 PM...

Страница 50: ...ISPR 11 B IEC 60601 IEC 61000 4 2 6 8 30 IEC 61000 4 3 2 1 IEC 61000 4 5 1 2 IEC 61000 4 11 5 UT UT 95 40 UT UT 60 5 70 UT UT 30 25 5 UT UT 95 5 50 60 IEC 61000 4 B 3 UT 18 06 259 933821 indb 50 6 20...

Страница 51: ...0 95 Tripp Lite www tripplite com support 1 2 www tripplite com support 3 www tripplite com support Product Returns Returned Material Authorization RMA RMA Tripp Lite Tripp Lite RMA RMA 18 06 259 9338...

Страница 52: ...ite WEEE Tripp Lite Tripp Lite Tripp Lite Tripp Lite 1111W 35th Street Chicago IL 60609 USA www tripplite com support Tripp Lite SMX700HGL SMX1200XLHGL 5 10 20 30 www tripplite com 18 06 259 933821 in...

Страница 53: ...ation 59 Standardbetrieb 60 Leitfaden und Herstellererkl rung 63 Lagerung und Service 64 Garantiehinweise f r die Batterie 65 Regulatorische Konformit t 65 English 1 Espa ol 14 Fran ais 27 40 SMX700HG...

Страница 54: ...ngang C14 mit Dongle Eingang C14 mit Dongle Betrieb Kontinuierlich Kontinuierlich AC Eingangsschutz Anzahl Typ Nen nwert Eingangsunterbrecher 2 x 5 A thermisch Eingangsunterbrecher 2 x 6 A thermisch M...

Страница 55: ...ng trennen Stecken Sie die USV nicht in sich selbst ein da dies die USV besch digt und die Garantie nichtig macht Wenn Sie Ihre USV an einen motorgetriebenen Wechselstromgenerator anschlie en muss die...

Страница 56: ...eiter gegen eine Batterie mit demselben Anschlusswert und Typ Lithium Eisen Phosphat ausgewechselt werden Die Batterien sind recyclingf hig Wenn der Lebenszyklus der USV Einheit abgelaufen ist entlade...

Страница 57: ...r USV nur einen feuchten Lappen verwenden Zur Desinfektion der USV kann ein mit Isopropanol angefeuchteter Lappen benutzt werden Es sollten keine anderen Reinigungsmittel verwendet werden USV und Batt...

Страница 58: ...Ger te mit der USV verbinden Installationsverfahren 3 Schieben Sie die Batteriepackung etwas heraus 4 Entfernen Sie das Isolierband vom negativen Batterieanschluss 5 Verbinden Sie den negativen Batte...

Страница 59: ...ximale Laufzeit der Batterie wird jedoch erst erreicht nachdem diese 24 Stunden lang aufgeladen wurde 3 Schalten Sie die USV ein Halten Sie die POWER Taste eine Sekunde lang gedr ckt Nach einer Sekund...

Страница 60: ...t den Selbsttest jedoch nicht aus wenn sie ausgeschaltet ist siehe Beschreibung der POWER Taste ACHTUNG Stecken Sie die USV nicht aus um die Batterien zu testen Das deaktiviert die sichere elektrische...

Страница 61: ...bereitstellt BATTERY CHARGE BATTERY POWER LED Wenn die USV mit Netzstrom betrieben wird zeigt diese mehrfarbige LED den ungef hren Ladestatus der internen USV Batterien an Rot zeigt an dass die Batter...

Страница 62: ...st Wenn der Schalter ausgel st wird entfernen Sie einige Last und dr cken Sie den Schalter zum Zur cksetzen Spannungsausgleichverbindung Verwenden Sie diese Verbindung um Ger te anzuschlie en die eine...

Страница 63: ...wird St rfestigkeitstest IEC 60601 Teststufe Einhaltungsstufe Elektromagnetische Umgebung Leitfaden Elektrostatische Entladung ESD IEC 61000 4 2 6kV Kontakt 8kV Luft Einhaltung Der Boden sollte aus Ho...

Страница 64: ...e folgenden Schritte aus 1 berpr fen Sie die Installations und Betriebsverfahren die in diesem Handbuch beschrieben sind um sicherzustellen dass das Problem nicht durch falsche Handhabung verursacht w...

Страница 65: ...n Sie die Batterien Ihrer Tripp Lite Produkte dem Recycling zu Die in den Produkten von Tripp Lite verwendeten Batterien sind Lithium Eisen Phosphat Batterien Diese Batterien sind sehr gut recyclingf...

Страница 66: ...66 18 06 259 933821 indb 66 6 20 2018 3 08 47 PM...

Страница 67: ...67 18 06 259 933821 indb 67 6 20 2018 3 08 47 PM...

Страница 68: ...68 1111 W 35th Street Chicago IL 60609 USA www tripplite com support 18 06 259 93 3821_RevB 18 06 259 933821 indb 68 6 20 2018 3 08 47 PM...

Отзывы: