background image

compatible)

Line-interactive voltage regulation corrects brownouts and overvoltages from 155 to 274 volts back to usable 230V output levels, without

using battery power

Full line isolation prevents shock potential and operational problems in sensitive electronic equipment

Resistant to electrostatic discharge

Supports loads up to 1000VA/750W

27.5 min. half-load runtime (500VA/375W), 11 min. full load runtime (1000VA/750W)

6 protected outlets; 6-inch dongle with IEC C14 inlet

USB and DB9 communication ports

PowerAlert unattended shutdown software and complete cabling included

Complete surge protection, line isolation and EMI/RFI noise filtering

5 diagnostic LEDs indicate AC present, on battery, voltage correction, overload & battery low/replace

Battery replacement door and back panel grounding lug

Specifications

OUTPUT

Output Volt Amp
Capacity (VA)

1000

Output Watt Capacity
(watts)

750

Nominal Output
Voltage(s) Supported

230V

Frequency
compatibility

50/60 Hz (auto-selectable)

Output voltage
regulation (line mode)

-18%, +8%

Built-in UPS output
receptacles

6 C13 outlet(s)

INPUT

Rated input current (at
maximum load)

5A

Nominal Input
Voltage(s) Supported

230V AC

UPS input connection
type

C14 inlet

UPS Input cord length
(ft.)

6 inch dongle, 16 gauge

UPS Input cord length
(m)

1.83

Recommended
Electrical Service

10A 230V

Voltage compatibility
(VAC)

230

BATTERY

Full load runtime
(minutes)

11 min. (750w)

Half load runtime
(minutes)

27.5 min. (375w)

Expandable battery
runtime

Supports extended runtime with optional 

BP36V15-2U

 (limit 1) and 

BP36V42-3U

 external battery pack (multi-pack

compatible)

Содержание SmartPro SMX1200XLHG

Страница 1: ...ing one or more external battery packs BP36V15 2U limit 1 or BP36V42 3U multi pack compatible Line interactive voltage regulation corrects brownouts as low as 155V and overvoltages as high as 274V back to normal 230V levels saving battery reserves for use only during complete power failures Includes diagnostic LEDs and 2 built in communications ports 1 USB 1 DB9 that work with included PowerAlert ...

Страница 2: ...t on battery voltage correction overload battery low replace Battery replacement door and back panel grounding lug Specifications OUTPUT Output Volt Amp Capacity VA 1000 Output Watt Capacity watts 750 Nominal Output Voltage s Supported 230V Frequency compatibility 50 60 Hz auto selectable Output voltage regulation line mode 18 8 Built in UPS output receptacles 6 C13 outlet s INPUT Rated input curr...

Страница 3: ...3 and 199 are boosted by 10 Severe undervoltage correction Input voltages between 156 and 182 are boosted by 21 Direct pass through Input voltages between 200 and 244V AC are passed through unchanged LEDS ALARMS SWITCHES LED Indicators 5 LEDs indicate line power battery power overload voltage regulation and battery low replace status Alarms 3 function audible alarm indicates power failure conditio...

Страница 4: ...e Range 5 to 122 degrees Fahrenheit 15 to 50 degrees Celsius Relative Humidity 0 to 95 non condensing AC mode BTU hr full load 252 2 Battery mode BTU hr full load 252 2 COMMUNICATIONS Communications interface USB DB9 Serial Software and cabling included PowerAlert UPS monitoring software is included on CD ROM for all common network and standalone operating systems Ships with 2 cables 1 USB to USB ...

Страница 5: ...V15 2U External Battery Pack for UPS System 1 External Battery Packs BP36V42 3U BP36V42 3U External Battery Pack for UPS System 1 More information including related products owner s manuals and additional technical specifications can be found online at www tripplite com en products model cfm txtModelID 3868 Copyright 2012 Tripp Lite All rights reserved All trademarks are the sole property of their...