BATTERY
Full load runtime (minutes)
7 min. (1600w)
Half load runtime (minutes)
19 min. (800w)
DC system voltage (VDC)
48
Battery recharge rate
(included batteries)
Less than 4 hours from 10% to 90%
Replacement battery
cartridge (internal UPS
battery replacement)
RBC54
Battery Access
Battery access door
Battery replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 151V to 282V
Overvoltage correction
Input voltages between 245 and 282 are reduced by 12%
Undervoltage correction
Input voltages between 177 and 199 are boosted by 14%
Severe undervoltage
correction
Input voltages between 151 and 176 are boosted by 30%
LEDS ALARMS & SWITCHES
LED Indicators
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Alarms
Audible alarm indicates power-failure, overload and low-battery conditions
Alarm cancel operation
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation
SURGE / NOISE SUPPRESSION
UPS AC suppression joule
rating
480
UPS AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Installation form factors
supported with included
accessories
Tower
Primary form factor
Tower
UPS / Power Module
dimensions in primary
form factor (height x width
x depth / inches)
14.2 x 9.2 x 12
UPS / Power Module
dimensions in primary
form factor (height x width
x depth / cm)
36.2 x 23.5 x 30.5