background image

Recommended
Electrical Service

15A 120V

Phase

Single-Phase

BATTERY

Full load runtime
(minutes)

8.5 min. (600w)

Half load runtime
(minutes)

20.7 min. (300w)

Expandable battery
runtime

Extended runtime supported via optional external battery packs

External battery pack
compatibility

BP24V15RT2U

 (limit 1); 

BP24V28-2U

 (limit 1); 

BP24V70-3U

 (multi-pack compatible); BP24V36-2US (multi-pack

compatible)

DC system voltage
(VDC)

24

Battery recharge rate
(included batteries)

Less than 4.5 hours from 10% to 90%

Replacement battery
cartridge (internal
UPS battery
replacement)

See Tripp Lite UPS Replacement battery selector

Battery Access

Front panel battery access door

Battery replacement
description

Hot-swappable, user replaceable batteries

VOLTAGE REGULATION

Voltage regulation
description

Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 147

Overvoltage
correction

Input voltages between 128 and 147 are reduced by 12%

Undervoltage
correction

Input voltages between 83 and 107 are boosted by 14%

LEDS ALARMS & SWITCHES

LED Indicators

Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data,
plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for
detailed LCD configuration and monitoring options)

Alarms

Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions

Alarm cancel
operation

Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available

Switches

3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions

SURGE / NOISE SUPPRESSION

UPS AC suppression
joule rating

570 joules

EMI / RFI AC noise
suppression

Yes

PHYSICAL

Installation form
factors supported
with optional
accessories

2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)

Содержание SmartPro SMART750RMXL2U

Страница 1: ...te cabling Switched output load banks enable scheduled and real time remote reboot and load shedding of select outlets Emergency Power Off EPO interface LCD display panel easily rotates for viewing in rackmount or tower configurations Audible alarm with push button momentary alarm cancel and silent mode configuration options Programmable self test Field replaceable hot swappable battery modules Pa...

Страница 2: ...r factor 0 8 Output Capacity Details Output derates to 450 watts in all external battery pack configurations Nominal Output Voltage s Supported 120V Frequency compatibility 60 Hz Output voltage regulation line mode 21 8 Output voltage regulation Battery mode 5 Built in UPS output receptacles 6 5 15R outlet s Built in controllable switched load banks Two switchable two outlet 5 15R load banks Outpu...

Страница 3: ...rvoltage correction Input voltages between 128 and 147 are reduced by 12 Undervoltage correction Input voltages between 83 and 107 are boosted by 14 LEDS ALARMS SWITCHES LED Indicators Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data plus configuration of voltage operating mode alarm function and a variety of additional options see m...

Страница 4: ...ng weight kg 21 1 Cooling method Fan UPS housing material Steel ENVIRONMENTAL Operating Temperature Range 32 to 104 degrees Fahrenheit 0 to 40 degrees Celsius Storage Temperature Range 5 to 122 degrees Fahrenheit 15 to 50 degrees Celsius Relative Humidity 0 to 95 non condensing AC mode BTU hr full load 109 COMMUNICATIONS Communications interface USB DB9 Serial EPO emergency power off Slot for SNMP...

Страница 5: ...rranty For Smart Line Interactive and Online Tower or Rack models 1500VA or less 1 SNMPWEBCARD For remote monitoring and control via SNMP Web or Telnet 1 ENVIROSENSE Monitors temperature humidity and contact closure inputs Requires SNMPWEBCARD or switched PDU 1 SRSWITCH Magnetic Door Switch Kit for front and rear doors requires ENVIROSENSE 1 RBC24V LCD 2U UPS Replacement Battery Cartridge for sele...

Страница 6: ...ET Single Phase Switched PDU 15A 120V 1U Horizontal Rackmount 16 NEMA 5 15R outlets NEMA 5 15P input plug 1 PDUMV15NET Single Phase Switched PDU 15A 120V 0U Vertical Rackmount 16 NEMA 5 15R outlets NEMA 5 15P input plug 1 More information including related products owner s manuals and additional technical specifications can be found online at www tripplite com en products model cfm txtModelID 3020...

Отзывы: