background image

Installation form factors
supported with included
accessories

2 post 19 inch rackmount (mounting rail kit included)

Installation form factors
supported with optional
accessories

4 post rackmount (4POSTRAILKIT); Tower (2-9USTAND)

Primary form factor

Rackmount

UPS / Power Module
dimensions in primary
form factor (height x width
x depth / inches)

7 x 18 x 17.2

UPS / Power Module
dimensions in primary
form factor (height x width
x depth / cm)

17.8 x 45.7 x 43.8

Installed whole system
total rack space height
(rack spaces)

4U

Secondary form factor

Tower (requires 

2-9USTAND

)

UPS / Power Module
weight (lbs)

100.3

UPS / Power Module
weight (kg)

45.5

UPS Shipping dimensions
(height x width x depth /
inches)

12.8 x 23.3 x 22.8

UPS Shipping dimensions
(height x width x depth /
cm)

32.4 x 59.1 x 57.8

Shipping weight (lbs)

128.9

Shipping weight (kg)

58.5

UPS housing material

Steel

Cooling method

Fan

ENVIRONMENTAL

Operating Temperature
Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature
Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr. (full
load)

199.8

Battery mode BTU / hr.
(full load)

880.9

COMMUNICATIONS

Communications interface

USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface

Network monitoring port
description

Supports detailed monitoring of UPS and site power conditions

PowerAlert software

Included

Содержание SmartPro SMART2200CRMXL

Страница 1: ...sory when used in conjunction with SNMPWEBCARD reports temperature humidity and status of up to two directly connected contact closure sensors HID compliant USB interface enables full integration with built in power management and auto shutdown features of Windows and Mac OS X Supports detailed monitoring of equipment load levels self test data and utility power conditions via all 3 network interf...

Страница 2: ... interface Integrated 3 bank programmable PDU switching supports load shedding and remote reboot of up to 3 individual connected devices 3 stage metered current monitoring and battery charge status LEDs Utility power and voltage regulation LEDs Audible alarm Self test 2 post rackmount accessories included 2 9USTAND tower stands and UPSRMRII 4 post rackmount kit available Field replaceable hot swap...

Страница 3: ... maintains line power operation with an input voltage range of 83 to 145 Overvoltage correction Input voltages between 127 and 145 are reduced by 12 Undervoltage correction Input voltages between 96 and 108 are boosted by 12 Severe undervoltage correction Input voltages between 83 and 95 are boosted by 24 LEDS ALARMS SWITCHES LED Indicators 5 LEDs indicate line power battery power overload voltage...

Страница 4: ...ower Module weight kg 45 5 UPS Shipping dimensions height x width x depth inches 12 8 x 23 3 x 22 8 UPS Shipping dimensions height x width x depth cm 32 4 x 59 1 x 57 8 Shipping weight lbs 128 9 Shipping weight kg 58 5 UPS housing material Steel Cooling method Fan ENVIRONMENTAL Operating Temperature Range 32 to 104 degrees Fahrenheit 0 to 40 degrees Celsius Storage Temperature Range 5 to 122 degre...

Страница 5: ...ote registration is required for 3 year warranty Product Warranty Period Puerto Rico 2 year warranty 3 year with registration Note registration is required for 3 year warranty Connected Equipment Insurance U S Canada Puerto Rico 250 000 Ultimate Lifetime Insurance Related Items Optional Products Product Type Related Model Description Qty Extended Warranties WEXT5 2200 3000 5 Year Extended Warranty...

Страница 6: ...n PDUMV20 Metered PDU Power Distribution Unit Safe reliable power distribution with digital current meter 1 Power Distribution PDUMV20NET Switched Metered PDU with Remote Monitoring 0U Vertical Rackmount Power Distribution Unit for Networks with Individually Switchable Outlets Current Metering Remote Monitoring and Control 1 Rackmount Wallmount Kits 4POSTRAILKIT Enables 4 Post Rackmount Installati...