Recommended
Electrical Service
15A 120V
BATTERY
Full load runtime
(minutes)
4.9 min. (1350w)
Half load runtime
(minutes)
14 min. (675w)
Expandable battery
runtime
Extended runtime supported via optional external battery packs
External battery pack
compatibility
BP36V15-2U
(limit 1);
BP36V42-3U
(multi-pack compatible)
DC system voltage
(VDC)
36
Battery recharge rate
(included batteries)
Less than 4.5 hours from 10% to 90%
Replacement battery
cartridge (internal
UPS battery
replacement)
RBC93-2U
Battery Access
Front panel battery access door
Battery replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Overvoltage
correction
Input voltages between 127 and 145 are reduced by 12%
Undervoltage
correction
Input voltages between 95 and 108 are boosted by 12%
Severe undervoltage
correction
Input voltages between 83 and 94 are boosted by 24%
LEDS ALARMS & SWITCHES
Front panel LCD
display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data,
plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for
detailed LCD configuration and monitoring options)
Alarms
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
Alarm cancel
operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Switches
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
570
UPS AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes