UPS / Power Module
dimensions in primary form
factor (height x width x
depth / cm)
8.9 x 44.4 x 34.3
Installed whole system
total rack space height
(rack spaces)
2U
Secondary form factor
Tower (requires
2-9USTAND
)
UPS / Power Module weight
(lbs)
46
UPS / Power Module weight
(kg)
20.9
UPS Shipping dimensions
(height x width x depth /
inches)
9 x 24 x 20.2
UPS Shipping dimensions
(height x width x depth / cm)
22.9 x 61 x 51.4
Shipping weight (lbs)
53
Shipping weight (kg)
24.1
UPS housing material
Steel
Cooling method
Fan
ENVIRONMENTAL
Operating Temperature
Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC mode BTU / hr. (full
load)
105.2
Battery mode BTU / hr. (full
load)
600
COMMUNICATIONS
Communications interface
USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Network monitoring port
description
Supports detailed monitoring of UPS and site power conditions
PowerAlert software
Included
Communications cable
USB and DB9 cabling included
WatchDog compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time
2-4 milliseconds
Low voltage transfer to
battery power (setpoint)
83
High voltage transfer to
battery power (setpoint)
147
SPECIAL FEATURES