Tripp Lite SmartOnline SU80KX2 Скачать руководство пользователя страница 4

UPS / Power Module dimensions in
primary form factor (height x width x
depth / inches)

66.8 x 20.5 x 38.4

UPS / Power Module dimensions in
primary form factor (height x width x
depth / cm)

169.7 x 52.1 x 97.5

UPS / Power Module weight (lbs)

703

UPS / Power Module weight (kg)

319

UPS Shipping dimensions (height x
width x depth / inches)

76.1 x 28.5 x 48.2

UPS Shipping dimensions (height x
width x depth / cm)

193.3 x 193.3 x 122.4

Shipping weight (lbs)

907.4

Shipping weight (kg)

411.5

Cooling method

Fans

UPS housing material

Steel

ENVIRONMENTAL

Operating Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr. (full load)

14016

COMMUNICATIONS

Communications interface

DB9 Serial; Slot for SNMP/Web interface

PowerAlert software

Included

Communications cable

DB9 cabling included

LINE / BATTERY TRANSFER

Transfer time

No transfer time (0 ms.) in online, double-conversion mode

Low voltage transfer to battery
power (setpoint)

Maintains continuous operation without using battery power during brownout/undervoltage conditions to 173-300V
AC (3-phase, 4-wire, wye). Below this point, output is maintained utilizing reserve battery power

High voltage transfer to battery
power (setpoint)

Maintains continuous operation without using battery power during overvoltages to 276-477V AC (3-phase, 4-wire,
wye), reducing output within 1% of nominal. Above this point, output is maintained utilizing reserve battery power

SPECIAL FEATURES

Cold Start (startup in battery mode
during a power failure)

Cold-start operation supported

High availability UPS features

Automatic inverter bypass; Hot swappable batteries

Green & high efficiency features

High efficiency economy mode operation; Schedulable daily hours of economy mode operation

4 / 5 

 

Отзывы: