background image

UPS / Power Module
dimensions in
primary form factor
(height x width x
depth / cm)

116.8 x 52.1 x 85.6

Installed whole
system maximum
rack depth (cm)

0

UPS / Power Module
weight (lbs)

538

UPS / Power Module
weight (kg)

244.3

UPS Shipping
dimensions (height x
width x depth / inches)

55 x 28.5 x 42.5

UPS Shipping
dimensions (height x
width x depth / cm)

139.7 x 72.4 x 108

Shipping weight (lbs)

687.8

Shipping weight (kg)

312.3

Cooling method

Fans

UPS housing material

Steel

ENVIRONMENTAL

Operating
Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature
Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

COMMUNICATIONS

Communications
interface

DB9 Serial; Slot for SNMP/Web interface

PowerAlert software

Included

Communications
cable

DB9 cabling included

LINE / BATTERY TRANSFER

Transfer time

No transfer time (0 ms.) in online, double-conversion mode

Low voltage transfer
to battery power
(setpoint)

Maintains continuous operation without using battery power during brownout/undervoltage conditions to 173-300V
AC (3-phase, 4-wire, wye). Below this point, output is maintained utilizing reserve battery power

High voltage transfer
to battery power
(setpoint)

Maintains continuous operation without using battery power during overvoltages to 276-477V AC (3-phase, 4-wire,
wye), reducing output within 1% of nominal. Above this point, output is maintained utilizing reserve battery power

SPECIAL FEATURES

Cold Start (startup in
battery mode during a
power failure)

Cold-start operation supported

High availability UPS
features

Automatic inverter bypass; Hot swappable batteries

Отзывы: