background image

Built-in UPS output receptacles

Hardwire

Output AC waveform (AC mode)

Sine wave

Output AC waveform (battery mode)

Pure Sine wave

INPUT

Rated input current (at maximum
load)

97A (per phase, online)

Nominal Input Voltage(s) Supported

277/480V (3ph wye)

UPS input connection type

Hardwire

UPS input connection description

277/480V (3-Phase, 4 Wire, wye)

Phase

3-Phase

BATTERY

Expandable battery runtime

Battery set sold separate

External battery pack compatibility

BP480V26B

BP480V40C

BP480V55

BP480V78

BP480V103

BP480V140

Expandable runtime description

External battery pack wiring is contractor supplied

DC system voltage (VDC)

+/- 240

Battery recharge rate (included
batteries)

2 - 4 hours from 10% to 90%

Battery replacement description

Hot-swappable, replaceable batteries

VOLTAGE REGULATION

Voltage regulation description

Online, double-conversion power conditioning

Overvoltage correction

Maintains continuous operation without using battery power during overvoltages to 348/603 (3-Phase, 4-Wire, wye)

Undervoltage correction

Maintains continuous operation without using battery power during brownout / undervoltage conditions to 218/378
(3-Phase, 4-Wire, wye)

LEDS ALARMS & SWITCHES

LED Indicators

4-LED Display: Displays normal AC input, on battery power, bypass input and fault conditions

Alarms

Alarms warn against a variety of operational conditions: low-battery, overload, shutdown, bypass and more

Alarm cancel operation

Power-fail alarm can be silenced using alarm-cancel switch

Switches

ON button turns UPS's inverter ON. OFF button turns UPS's inverter OFF. LCD Display Control Buttons browses
through and selects items displayed on LCD screen. Emergency Power Off button turns UPS output OFF and
disables Bypass output. Manual Bypass breaker bypasses the UPS's inverter during maintenance.

SURGE / NOISE SUPPRESSION

EMI / RFI AC noise suppression

Yes

AC suppression joule rating

4675

AC suppression response time

Instantaneous

3 / 6 

 