Frequency
compatibility details
Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to
50Hz or 50Hz to 60Hz (no de-rating)
Output voltage
regulation (line
mode)
+/- 2%
Output voltage
regulation (Economy
line mode)
+/- 10%
Output voltage
regulation (Battery
mode)
+/- 2%
Built-in UPS output
receptacles
4 L6-20R outlet(s); 2 L6-30R outlet(s)
Output circuit
breaker
20A double-pole (x2) protects 2 L6-20R outlets each, 30A double-pole (x2) protects 1 L6-30R outlet each
Output AC waveform
(AC mode)
Sine wave
Output AC waveform
(battery mode)
Pure Sine wave
INPUT
Rated input current
(at maximum load)
46A (200V), 44.2A (208V), 41.8A (220V), 40A (230V), 38.3A (240V)
Nominal Input
Voltage(s) Supported
200V AC; 208V AC; 220V AC; 230V AC; 240V AC
UPS input
connection type
Hardwire
UPS input
connection
description
3 wire single phase input (L1, L2, G)
Recommended
Electrical Service
50A
BATTERY
Full load runtime
(minutes)
5.5 min. (7200w)
Half load runtime
(minutes)
13.5 min. (3600w)
Expandable battery
runtime
Supports extended runtime with optional external battery packs
External battery
pack compatibility
BP240V10RT3U
;
BP240V557C-1PH
;
BP240V787C-1PH
;
BP240V1037C-1PH
;
BP240V1407C-1PH
DC system voltage
(VDC)
240
Battery recharge
rate (included
batteries)
Less than 6 hours from 10% to 90%
Battery replacement
description
Hot-swappable, user replaceable external battery packs
VOLTAGE REGULATION
Voltage regulation
description
2% output voltage regulation in standard online, double-conversion mode