![Tripp Lite SmartOnline SU5000RT3UHV Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/tripp-lite/smartonline-su5000rt3uhv/smartonline-su5000rt3uhv_specifications_1167887002.webp)
Communications ports support on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge
current, battery capacity, AC line frequency, timed inverter shutoff, activate self-test and output power control
Built-in Emergency Power Off (EPO) interface with cable
Includes 4 built-in output receptacles (2 L6-30R, 2 L6-20R)
L6-30P input plug-in connection
Front panel LEDs and LCD readout with scroll button enables visual confirmation of all major UPS functions and current site electrical
conditions
Front panel switches enable power on/off control, self-test and alarm cancel functions
Included adjustable mounting rails support installation in 4 post 19 inch rack enclosures. Optional 2POSTRMKITWM supports 2 post
rackmount installation
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user is required
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
$250,000
Ultimate Lifetime Insurance
(USA and Canada Only)
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
5000
Output kVA capacity
(kVA)
5
Output Watt Capacity
(watts)
3500
Output kW capacity
3.5
Output power factor
0.7
Crest Factor
3:1
Nominal Output
Voltage(s) Supported
200V; 208V; 220V; 240V
Nominal Voltage details
Voltage selection via front panel LCD interface
Frequency compatibility
50 / 60 Hz
Frequency
compatibility details
Output frequency matches input nominal on startup
Output voltage
regulation (line mode)
+/- 2%
Output voltage
regulation (Economy
line mode)
+/- 10%
Output voltage
regulation (Battery
mode)
+/- 2%
Built-in UPS output
receptacles
2 L6-20R outlet(s); 2 L6-30R outlet(s)
Output circuit breaker
20A double-pole breaker protects L6-20R outlets, L6-30R outlets are unbreakered
Output AC waveform
(AC mode)
Sine wave
Output AC waveform
(battery mode)
Pure Sine wave
INPUT