6 – Internal Battery Connection
(continued)
6-2 Internal Battery Connection Procedure
Place the UPS system in bypass (or turn it completely off) and turn
•
off the internal battery circuit breaker switch, located on the rear of
the UPS system.
Remove the battery access bezels, located on the front of the UPS
•
system.
Remove the battery cartridge fuses from each fuse block.
•
Disconnect the blue and white jumper cables attached to each fuse
•
block.
Warning: When disconnecting the jumper cables, pull
them straight away from the fuse block with even force. Do not
wiggle them side-to-side, as this may damage the connector.
Remove the fuse block bracket. Note its orientation before
•
removal.