conditions
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other
UPS types
Corrects line voltage conditions as low as 65V and as high as 150V back to selectable 110/120V (+/-2%) values
Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs
Standard internal battery set offers 30 minutes runtime at half load (1200W) and 12 minutes at full load (2400W)
Optional BP72V15-2U external battery pack increases runtime (limit 1)
Optional BP72V28RT-3U external battery pack increases runtime (multi-pack compatible)
Some external battery configurations require the use of Tripp Lite's
External Battery Configuration Software
(see manual)
Compact rackmount form factor installs using only 3 rack spaces (3U) with a maximum installed depth of 26 inches
Ships with all mounting accessories for 4 post rackmount installation
Optional 2POSTRMKITWM enables 2 post rackmount installation
Optional 2-9USTAND accessory enables small-footprint upright tower placement
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Network interfaces support simultaneous communications via built-in USB, DB9 serial/contact-closure and SNMPWEBCARD slot
HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus
any number of additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current,
battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS
nominal voltage adjustment and UPS line to battery power voltage setpoints
Built-in Emergency Power Off (EPO) interface with cable
NEMA L5-30P input plug/NEMA 5-15/20R & NEMA L5-30R output receptacles
Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (each
bank has four outlets)
Front panel LEDs offer current monitoring and battery charge level information
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required
Single line TEL/DSL or network ethernet line surge suppression
$250,000
Ultimate Lifetime Insurance
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
3000
Output kVA capacity
(kVA)
3
Output Watt Capacity
(watts)
2400
Output kW capacity
2.4
Output power factor
0.8
Crest Factor
3:1
Nominal Output
Voltage(s) Supported
110V; 120V
Nominal Voltage
details
120V default
Frequency
compatibility
50 / 60 Hz
Frequency
compatibility details
Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start
Output voltage
regulation (line mode)
+/- 2%