background image

Output voltage
regulation (Economy
line mode)

+/- 10%

Output voltage
regulation (Battery
mode)

+/- 2%

Built-in UPS output
receptacles

4 5-15R outlet(s); 4 5-15/20R outlet(s); 1 L5-30R outlet(s)

Built-in controllable
switched load banks

Two switchable four-outlet load banks, (bank 1 - four 5-15/20R, bank 2 - four 5-15R outlets)

Output circuit breaker

15A branch rated (x2) - each breaker protects 4 outlets, L5-30R is unbreakered

Output AC waveform
(AC mode)

Sine wave

Output AC waveform
(battery mode)

Pure Sine wave

INPUT

Rated input current
(at maximum load)

24A

Nominal Input
Voltage(s) Supported

110V AC; 120V AC

UPS input connection
type

L5-30P

Input circuit breaker

40A

UPS Input cord
length (ft.)

10

UPS Input cord
length (m)

3

Recommended
Electrical Service

30A 120V

BATTERY

Full load runtime
(minutes)

5 min. (2400w)

Half load runtime
(minutes)

14 min. (1200w)

Expandable battery
runtime

Supports extended runtime with optional external battery packs

External battery pack
compatibility

BP72V15-2U

 (limit 1); 

BP72V28RT-3U

 (multi-pack compatible)

DC system voltage
(VDC)

72

Battery recharge rate
(included batteries)

Less than 6 hours from 10% to 80%

Replacement battery
cartridge (internal
UPS battery
replacement)

RBC96-3U

 (quantity 1)

Battery Access

Front panel battery access door

Содержание SmartOnline SU3000RTXL3U

Страница 1: ...terfaces support simultaneous communications via USB port DB9 serial port and SNMPWEBCARD slot Built in DB9 port offers both enhanced RS 232 enabled monitoring data plus contact closure monitoring ability HID compliant USB interface enables integration with built in power management and auto shutdown features of Windows and Mac OS X Supports simultaneous detailed monitoring of equipment load level...

Страница 2: ...ilt in power management and auto shutdown features of Windows and Mac OS X Included PowerAlert UPS monitoring software supports safe unattended shutdown monitoring and control via local connected servers plus any number of additional servers over IP UPS interface supports on battery low battery power restored AC voltage DC voltage output current monitoring battery charge current battery capacity A...

Страница 3: ... maximum load 24A Nominal Input Voltage s Supported 110V AC 120V AC UPS input connection type L5 30P Input circuit breaker 40A UPS Input cord length ft 10 UPS Input cord length m 3 Recommended Electrical Service 30A 120V BATTERY Full load runtime minutes 5 min 2400w Half load runtime minutes 14 min 1200w Expandable battery runtime Supports extended runtime with optional external battery packs Exte...

Страница 4: ...ow battery overload UPS fault and remote shutdown conditions Alarm cancel operation Power fail alarm can be silenced using alarm cancel switch Switches 2 switches control off on power status and alarm cancel self test operation SURGE NOISE SUPPRESSION UPS AC suppression joule rating 510 UPS AC suppression response time Instantaneous UPS Dataline suppression 1 line TEL DSL 1 in 1 out 10 100Base T E...

Страница 5: ...elsius Relative Humidity 0 to 95 non condensing AC mode BTU hr full load 1112 7 AC economy mode BTU hr full load 520 9 Battery mode BTU hr full load 1219 3 AC economy mode efficiency rating 100 load 94 COMMUNICATIONS Communications interface USB HID enabled DB9 Serial Contact closure EPO emergency power off Slot for SNMP Web interface Network monitoring port description Supports detailed monitorin...

Страница 6: ...ractive and Online Tower or Rack models 2200 3000VA or less 1 External Battery Packs BP72V15 2U BP72V15 2U External Battery Pack for UPS System 1 External Battery Packs BP72V28RT 3U BP72V28RT 3U External Battery Pack for UPS System 1 Power Cables P043 002 2 ft 10AWG Heavy Duty Power Cord with 20 AMP Breaker NEMA L5 30P to NEMA L5 20R 1 Power Distribution P044 06I 6 inch 12AWG Heavy Duty Power Adap...

Страница 7: ...ors temperature humidity and contact closure inputs Requires SNMPWEBCARD or switched PDU 1 SNMP Accessories SNMPWEBCARD For remote monitoring and control via SNMP Web or Telnet 1 Tower Stands 2 9USTAND Enables Tower Placement of Rackmount UPS Systems 1 UPS Accessories MODBUSCARD For remote monitoring and control via MODBUS protocol 1 UPS Accessories RELAYIOCARD Programmable Relay I O Card 1 More i...

Отзывы: