Output voltage
regulation (Economy
line mode)
+/- 10%
Output voltage
regulation (Battery
mode)
+/- 2%
Built-in UPS output
receptacles
4 5-15R outlet(s); 4 5-15/20R outlet(s); 1 L5-30R outlet(s)
Built-in controllable
switched load banks
Two switchable four-outlet load banks, (bank 1 - four 5-15/20R, bank 2 - four 5-15R outlets)
Output circuit breaker
15A branch rated (x2) - each breaker protects 4 outlets, L5-30R is unbreakered
Output AC waveform
(AC mode)
Sine wave
Output AC waveform
(battery mode)
Pure Sine wave
INPUT
Rated input current
(at maximum load)
24A
Nominal Input
Voltage(s) Supported
110V AC; 120V AC
UPS input connection
type
L5-30P
Input circuit breaker
40A
UPS Input cord
length (ft.)
10
UPS Input cord
length (m)
3
Recommended
Electrical Service
30A 120V
BATTERY
Full load runtime
(minutes)
5 min. (2400w)
Half load runtime
(minutes)
14 min. (1200w)
Expandable battery
runtime
Supports extended runtime with optional external battery packs
External battery pack
compatibility
BP72V15-2U
(limit 1);
BP72V28RT-3U
(multi-pack compatible)
DC system voltage
(VDC)
72
Battery recharge rate
(included batteries)
Less than 6 hours from 10% to 80%
Replacement battery
cartridge (internal
UPS battery
replacement)
RBC96-3U
(quantity 1)
Battery Access
Front panel battery access door