background image

Battery
replacement
description

Hot-swappable, user replaceable batteries

VOLTAGE REGULATION

Voltage regulation
description

Online, double-conversion power conditioning maintains 2% output voltage regulation during brownouts and
overvoltages

Overvoltage
correction

Corrects overvoltages to 150V (0-100% load)

Undervoltage
correction

Corrects undervoltages to 100V at full load (90V at 100V nominal)

Severe
undervoltage
correction

Corrects brownouts to 70V (70% load) & 55V (33% load)

LEDS ALARMS & SWITCHES

LED Indicators

7 front panel LEDs indicate line power availability, AC to DC conversion, battery mode operation, inverter mode, eco
mode operation, bypass mode operation and AC output status

Front panel LCD
display

Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data,
plus configuration of voltage, frequency, operating mode, alarm function and a variety of additional options

Alarms

Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions

Alarm cancel
operation

Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available

Switches

2 switches control off/on power status and alarm-cancel operation; 2 additional scroll-down and scroll-up / select
options enable LCD status viewing and configuration options

SURGE / NOISE SUPPRESSION

UPS AC
suppression joule
rating

570

UPS AC
suppression
response time

Instantaneous

UPS Dataline
suppression

1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet

EMI / RFI AC noise
suppression

Yes

PHYSICAL

Installation form
factors supported
with included
accessories

4 post 19 inch rackmount (mounting rail kit included)

Installation form
factors supported
with optional
accessories

2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)

Primary form factor

Rackmount

UPS / Power
Module
dimensions in
primary form
factor (height x
width x depth /
inches)

3.5 x 17.5 x 18.5

Содержание SmartOnline SU1500RTXLCD2U

Страница 1: ...bility HID compliant USB interface enables integration with built in power management and auto shutdown features of Windows and Mac OS X Includes PowerAlert monitoring software and complete cabling Em...

Страница 2: ...gs are reduced for some nominal voltage settings 127 120V 1350 watts 115V 1215 watts 110V 1148 watts 100V 1080 watts FREQUENCY REGULATION CONVERSION MODE Maximum output ratings are reduced in frequenc...

Страница 3: ...ed Electrical Service 15A 120V BATTERY Full load runtime minutes 4 2 min 1350w Half load runtime minutes 14 min 675w Expandable battery runtime Extended runtime supported via optional external battery...

Страница 4: ...ion and a variety of additional options Alarms Audible alarm indicates UPS startup power failure low battery overload UPS fault and remote shutdown conditions Alarm cancel operation Power fail alarm c...

Страница 5: ...ethod Fan UPS housing material Steel ENVIRONMENTAL Operating Temperature Range 32 to 104 degrees Fahrenheit 0 to 40 degrees Celsius Storage Temperature Range 5 to 122 degrees Fahrenheit 15 to 50 degre...

Страница 6: ...er bypass Hot swappable batteries Green high efficiency features High efficiency economy mode operation Individually controllable load banks Schedulable daily hours of economy mode operation CERTIFICA...

Страница 7: ...outlets 2 NEMA 5 15P inputs 1 PDUMNV15 Single Phase Monitored PDU 15A 120V 0U Vertical Rackmount NEMA 5 15R outlets NEMA 5 15P input plug 1 PDUMV15NET Single Phase Switched PDU 15A 120V 0U Vertical Ra...