Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs
Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other
UPS types
Corrects line voltage conditions as low as 65V and as high as 150V back to selectable 100/110/120V (+/-2%) values
Standard internal battery set offers 14 min. runtime at half load (600W) and 5 min. at full load (1200W)
Extended runtime available with optional BP48V24-2U (limit 1) or BP48V60RT3U (no limit) external battery packs
Some external battery configurations require the use of Tripp Lite's
External Battery Configuration Software
(see manual)
Compact rackmount form factor installs using only 2 rack spaces (2U) with a maximum installed depth of only 19 in.
Ships with all mounting accessories for 4-post rackmount installation
Optional 2POSTRMKITWM enables 2-post rackmount or wallmount installation
Optional 2-9USTAND accessory enables small-footprint upright tower placement
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Network interfaces support simultaneous communications via built-in USB, DB9 serial / contact-closure and SNMPWEBCARD slot
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus
any number of additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current,
battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS
nominal voltage adjustment and UPS line to battery power voltage setpoints
Built-in Emergency Power Off (EPO) interface with cable
NEMA 5-15P input plug; NEMA 5-15R output receptacles
Integrated 2-bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (bank one
has 2 outlets, bank two has 4 outlets)
Front panel LEDs offer current monitoring and battery charge level information
UPS ships fully assembled in full compliance with DOT regulations; no time-consuming connection of internal batteries by user required
Single-line tel/DSL or network Ethernet surge suppression
$250,000
Ultimate Lifetime Insurance
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
1500
Output kVA capacity
(kVA)
1.5
Output Watt Capacity
(watts)
1200
Output kW capacity
1.2
Output power factor
0.8
Crest Factor
3:1
Nominal Output
Voltage(s) Supported
100V; 110V; 120V
Nominal Voltage
details
120V default
Frequency
compatibility
50 / 60 Hz
Frequency
compatibility details
Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start
Output voltage
regulation (line mode)
+/- 2%