Included battery pack
weight (kg)

108.5

UPS Shipping
dimensions (height x
width x depth / inches)

45.5 x 23.5 x 34.3

UPS Shipping
dimensions (height x
width x depth / cm)

115.6 x 59.7 x 87.1

Shipping weight (lbs)

448.8

Shipping weight (kg)

203.8

Cooling method

Fan

UPS housing material

Steel

ENVIRONMENTAL

Operating
Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.

Storage Temperature
Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr.
(full load)

4286

Battery mode BTU /
hr. (full load)

3187

Operating Elevation
(ft.)

0-3000m (0 to 10,000 ft.)

Audible Noise

60 dBA at front side 1 meter

Operating Elevation
(m)

0-3000 m

COMMUNICATIONS

Communications
interface

USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface

Network monitoring
port description

RS232 and contact closure communications are supported on one DB9 port

PowerAlert software

Included

Communications cable

USB and DB9 cabling included

LINE / BATTERY TRANSFER

Transfer time

No transfer time (0 ms.) in online, double-conversion mode

Low voltage transfer
to battery power
(setpoint)

65V (L1-N:L2-N)

High voltage transfer
to battery power
(setpoint)

140V (L1-N:L2-N)

SPECIAL FEATURES

Cold Start (startup in
battery mode during a
power failure)

Cold-start operation supported